Technical specifications for CI867AK01 3BSE092689R1

  • Manufacturer:
    ABB
  • Part Number:
    CI867AK01 3BSE092689R1
  • Product Family:
    ABB Advant OCS and Advant-800xA
  • Product Type:
    3BSE092689R1
  • Operating Temp:
    -25°C to +70°C
  • Storage Temp:
    -40°C to +85°C
  • Humidity:
    5–95% RH (non-condensing)
  • Data Types:
    16-bit & 32-bit integers
  • Voltage:
    5 V DC
  • Power Consumption:
    Typically 1.5 W
  • Isolation:
    1500 V AC galvanic
  • Weight:
    0.44 kg
  • Estimated shipping dimensions:
    18.6x6.8x12.5cm
  • Tariff Code:
    8537101190
  • Country of origin:
    Sweden
  • Place of shipment:
    Xiamen, Fujian, China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals Specifications MODBUS TCP System Matching Installation Check

Features:

  • MODBUS TCP interface: Connects an AC 800M controller to external Ethernet devices.
  • Single Ethernet channel: Channel 1 supports full-duplex 10/100 Mbit/s communication.
  • Master and slave operation: Supports both MODBUS TCP operating roles.

CI867AK01 3BSE092689R1 is the ABB package for the CI867A communication interface and TP867 baseplate in compatible AC 800M installations.

The CI867A supports module redundancy and hot swap, while the Ethernet network must be connected through an industrial switch.

Confirm the installed System 800xA or Compact Control Builder version, IP plan, MODBUS roles, register mapping and redundancy design before replacement.

CI867AK01 3BSE092689R1 MODBUS TCP Communication Interface Manuals, Datasheets, Links

Communication data

  • Article number: 3BSE092689R1.
  • Protocol: MODBUS TCP master or slave.
  • Channel: One RJ-45 Ethernet channel at 10/100 Mbit/s.
  • Package: CI867A interface with TP867 baseplate.

Data-exchange planning

  • Master role: Define peer addresses, request rates, timeouts and function codes.
  • Slave role: Maintain a controlled unit-ID and register map.
  • Capacity planning: ABB documents up to 70 slave units and 8 master units per CI867A.
  • Network path: Connect the main Ethernet channel through an approved switch.

Compatibility checks

  • System release: Verify support in the installed System 800xA or Compact Control Builder baseline.
  • Version distinction: CI867A is a single-channel unit and must not be confused with the earlier two-channel CI867.
  • CEX-Bus: Confirm controller capacity, baseplate position and approved module count.
  • Redundancy: Match paired hardware, project configuration and switch paths.

Commissioning checks

  • Hardware: Verify the CI867A and TP867 labels, seating and CEX-Bus connection.
  • Ethernet: Check cable, switch port, link speed, IP address and duplicate-address risk.
  • Application: Restore the approved role, unit IDs, register map, polling and timeout settings.
  • Functional test: Prove data quality, communication alarms, hot swap and redundancy recovery.
Description

The CI867AK01 3BSE092689R1 Communication Interface Module is designed to enable seamless and reliable communication between devices in industrial environments. It provides high-speed, secure data transfer and supports multiple communication protocols, ensuring compatibility with a wide range of systems.


This module is ideal for connecting distributed control systems to various field devices, such as sensors, actuators, and other control systems. With its easy integration, high performance, and robust design, the CI867AK01 ensures uninterrupted data exchange and enhances operational efficiency. It is built to handle demanding environments while maintaining flexibility and reliability in communication.

Alternative Names
C1867AK01 3BSE092689R1 C1867AKO1 3BSE092689R1 C1867AKOI 3BSE092689R1 C1867AKO1 3BSEO92689R1 C1867AKO1 3BSEO92689RI
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
Which communication protocol and operating roles does CI867AK01 3BSE092689R1 support?
CI867AK01 uses MODBUS TCP and can be configured for master or slave operation. Define peer addresses, function codes, register maps, polling rates and timeout behavior in the approved controller project.
How should the CI867A Ethernet channel be connected and configured?
CI867A provides one full-duplex 10/100 Mbit/s RJ-45 Ethernet channel. Connect it to the main network through an industrial Ethernet switch and verify the IP address, subnet, switch port and duplicate-address protection.
Which System 800xA software versions should be checked before installing CI867AK01?
ABB documents CI867A support beginning with System 800xA 6.0.3.3 and 6.1.1 and subsequent supported versions. Confirm the installed controller and engineering-software baseline before replacing an earlier CI867 interface.
How should CI867AK01 module redundancy and hot swap be commissioned?
Use matching CI867A hardware and approved redundant project settings, then test each module path, communication continuity, alarm behavior and recovery without disrupting MODBUS TCP data exchange.
How many MODBUS TCP peers can one CI867A handle?
ABB documents a maximum of 70 slave units and 8 master units per CI867A. Actual polling load, response time, timeout settings and controller application demand must still be reviewed for the project.
What must be verified when replacing CI867K01 with CI867AK01 3BSE092689R1?