Ask our team:
  • Phone: +86 181 0690 9650
  • E-Mail sales1@apterpower.com

FC-33

/ 4.9
1001 reviews | Need a Specific Revision?
The Automation Direct FC-33 is a full-featured DIN rail-mounted signal conditioner suitable for a wide range of applications and allows for flexible signal adjustment to meet system requirements.
Get a quick price for FC-33
Quantity
*E-mail
Company
*Mobile
*Content
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)

Technical specifications for FC-33

  • Manufacturer:
    Automation Direct
  • Part Number:
    FC-33
  • Product Family:
    Automation Direct
  • Input Ranges:
    0–5V, 0–10V, 0–20mA, 4–20mA
  • Input Impedance:
    250 Ω ±0.1% (current input), 200K Ω / 400K Ω (voltage input)
  • Maximum Load / Current:
    550 Ω @ 24V sink/source
  • Sample Duration Time:
    10 ms
  • Filter Characteristic:
    -3 dB @ 3 Hz, -6 dB/octave
  • Linearity Error:
    0.05% FSO maximum
  • Operating Temperature:
    0 to 60°C (32 to 140°F)
  • Storage Temperature:
    -20 to 70°C (-4 to 158°F)
  • Relative Humidity:
    5 to 90% (non-condensing)
  • Weight:
    0.1 kg
  • Estimated shipping dimensions:
    2.2x12.8x11.5cm
  • Tariff Code:
    8537101190
  • Country of origin:
    China
  • Place of shipment:
    Xiamen,Fujian,China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.
Description
The Automation Direct FC-33 is a versatile DIN rail mount signal conditioner designed for selectable input and output types. It provides 1500VDC isolation between input and output, as well as 1500VDC isolation from the 24V power supply, ensuring reliable operation in demanding industrial environments. The FC-33 supports a broad range of field-configurable input and output types, including 0–5V, 0–10V, 0–20mA, and 4–20mA, making it suitable for a variety of applications.

This signal conditioner features user-selectable factory calibration and includes OFFSET (zero) and SPAN (full scale) adjustments for precise signal control. The OFFSET adjustment allows modification from 0 to 25% of the full-scale input, while the SPAN adjustment covers 80 to 102% of full scale, giving flexibility in adapting signals to system requirements.

The FC-33 is particularly useful for eliminating ground loops and interfacing sensors with PLC analog input modules. Its three-way isolation solves many configuration challenges, allowing setups such as sinking input with sourcing output, or translating signals from current input to voltage output and vice versa.

This capability is especially beneficial in systems with limited channels. For instance, if a system has eight 4–20mA channels, and seven are already in use, the FC-33 enables seamless integration of an additional transmitter with a 0–10V output, maximizing system efficiency and flexibility.
Alternative Names
FC 33 FC-11 FC33 FC-T1 FC-R1 FC-P3
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
What is the Automation Direct FC-33?
The Automation Direct FC-33 is a DIN rail mount, DC selectable input isolated signal conditioner. It provides 1500VDC isolation between input and output, and 1500VDC isolation from 24V power, input, and output. It supports field-configurable input/output types including 0–5V, 0–10V, 0–20mA, and 4–20mA.
What is the load impedance and maximum load/current?
The load impedance is 2K Ω minimum for voltage output and 0 Ω minimum for current output. The maximum load is 550 Ω at 24V sink/source.
What are the practical applications of the FC-33?
The FC-33 is useful for eliminating ground loops, interfacing sensors to PLC analog input modules, and signal translation (e.g., current input to voltage output or voltage input to current output). It’s particularly beneficial in systems with limited channels, allowing different types of transmitters to be integrated seamlessly.
Does the FC-33 have calibration or adjustment features?
Yes, the FC-33 features user-selectable factory calibration along with OFFSET (zero) adjustment from 0–25% of full-scale input and SPAN (full-scale) adjustment from 80–102% of full scale.