Technical specifications for X20CS1030

  • Manufacturer:
    B&R
  • Part Number:
    X20CS1030
  • Product Family:
    B&R X20 System
  • Product Type:
    RS485/RS422 Communication Module
  • Stock:
    1
  • Serial interface:
    1 × RS485/RS422
  • Connection:
    X20TB12 12-pin terminal block
  • Maximum transfer rate:
    115.2 kbit/s
  • Maximum distance:
    1200 m
  • RS485 station count:
    Maximum 32 stations
  • RS422 receiver count:
    Maximum 10 receivers
  • FIFO buffer:
    1 kB
  • Controller:
    16C550-compatible UART
  • Required terminal block:
    X20TB06 or X20TB12, ordered separately
  • Compatible bus modules:
    X20BM11 or X20BM15, ordered separately
  • Module pitch:
    12.5 mm +0.2 mm
  • Degree of protection:
    IP20
  • Operating temperature:
    -25 to 60 °C horizontal; -25 to 50 °C vertical
  • Dimensions:
    1.25 × 5.3 × 9.8 cm
  • Tariff Code:
    8538900000
  • Country of origin:
    Germany
  • Place of shipment:
    Xiamen, Fujian, China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals Serial Setup Topology Termination Application
  • Provides one isolated RS485 or RS422 serial interface
  • Supports up to 115.2 kilobits per second over distances up to 1200 meters
  • Includes a 1 kilobyte FIFO and an integrated terminating resistor

X20CS1030 is a B&R rs485/rs422 communication module designed for the X20 System.

The module connects serial devices to an X20 station and can be positioned as a normal electronic module anywhere on the remote backplane.

Before installation or replacement, verify the complete material number, RS485 or RS422 mode, baud rate and frame format, station count, cable length and topology, termination state, biasing and grounding, X20TB06 or X20TB12, compatible bus module, and device protocol.

Availability, condition, price, and shipping time for X20CS1030 are confirmed during quotation.

B&R X20CS1030 RS485/RS422 Communication Module Manuals, Datasheets, Links

Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.

  • RS485 or RS422 operation is selected for the connected device and topology
  • Baud rate and serial frame format must match every communicating device
  • The interface uses a 16C550-compatible UART with a one-kilobyte FIFO
  • RS485 supports a documented maximum of 32 stations
  • RS422 supports a documented maximum of 10 receivers
  • Cable type, grounding, biasing, and total length must suit the selected physical layer
  • The serial terminating resistor is integrated in the module
  • Termination status is indicated for commissioning and troubleshooting
  • Termination should be enabled only at the appropriate physical end of the network segment
  • Connecting RS485 multidrop serial devices to an X20 station
  • Connecting RS422 remote devices and multiple receivers
  • Long-distance serial integration of complex field equipment
Description
X20CS1030 is a B&R rs485/rs422 communication module for the X20 System automation platform.

It provides one software-configurable RS485 or RS422 channel with a 1 kB FIFO, transfer rates up to 115.2 kbit/s, long-distance serial wiring, and an integrated terminating resistor.

Before installation or replacement, confirm the complete material number, RS485 or RS422 mode, baud rate and frame format, station count, cable length and topology, termination state, biasing and grounding, X20TB06 or X20TB12, compatible bus module, and device protocol.
Alternative Names
X20CS1030 X20 CS 1030 X20-CS1030 B&R X20CS1030 BR X20CS1030 B&R X20 CS1030
Technical notes
X20CS1030 provides one isolated RS485/RS422 channel; verify serial mode, baud and frame settings, station count, topology, integrated termination, grounding, terminal block, bus module, and device protocol before replacement.
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
How should RS485 or RS422 mode be chosen on B&R X20CS1030?
Select the physical layer required by the connected device and topology, then match baud rate, frame format, pin assignment, grounding, and protocol configuration.
When should the terminating resistor on B&R X20CS1030 be enabled?
Enable termination only when the module is located at the physical end of the applicable bus segment; duplicate or misplaced termination can degrade the signal.
What should be checked when B&R X20CS1030 receives corrupted serial data?
Verify baud rate, parity, stop bits, RS485 versus RS422 mode, conductor polarity, shield and ground, termination, biasing, cable length, and the remote device protocol.
Can B&R X20CS1030 connect all 32 RS485 stations at maximum distance and speed?
The published maxima are not automatically simultaneous design guarantees. Validate cable quality, topology, node loading, termination, environment, and the device protocol for the actual network.
Is the serial interface of B&R X20CS1030 isolated?
Yes. B&R specifies the RS485/RS422 interface as isolated from the bus and I/O power supply, but the complete installation still needs correct grounding and shielding.
Which terminal block is required for B&R X20CS1030?
B&R lists X20TB06 and X20TB12 as compatible terminal blocks, ordered separately; use the documented terminal assignment for the chosen serial mode.
What should be saved before replacing B&R X20CS1030?
Record interface mode, baud and frame settings, protocol parameters, node addresses, topology, termination and biasing, terminal mapping, and Automation Studio configuration.