Features:
- Provides eight analog input channels with 13-bit conversion for Ovation process measurement.
- Accepts documented ±5 V, 0–20 mA, or 4–20 mA signal configurations.
- Uses a signal-specific personality module for voltage or locally and remotely powered current inputs.
The current ordering configuration is 1C31113G05, an eight-channel 13-bit Ovation analog input module for voltage or current signals.
It acquires process measurements using the selected ±5 V, 0-20 mA or 4-20 mA arrangement when paired with the correct personality module.
Before replacement, confirm signal range, loop-power method, personality module, field wiring and scaling for all eight inputs.
Availability is subject to Apter Power inventory and sourcing confirmation.
Verified resources for Emerson 1C31113G05:
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
- Measures up to eight voltage inputs from compatible process sensors and signal conditioners.
- Acquires 0–20 mA or 4–20 mA signals from locally powered process instruments.
- Supports remote-powered current loops when paired with the documented termination hardware.
- Select the documented personality module that matches voltage, local-powered-current, or remote-powered-current service.
- Configure each channel range and engineering-unit scaling in the Ovation project database.
- Retain the exact 1C31113G05 group code when checking electronic-module compatibility.
- Converts eight field signals into 13-bit process measurements for Ovation control strategies.
- Supports voltage and current input ranges documented for the installed personality module.
- Provides channel data for alarming, trending, and closed-loop process applications.
- Works with the voltage personality module documented for ±5 V input service.
- Supports local-powered current measurement with the corresponding current-input personality hardware.
- Supports remote-powered current loops only with the termination arrangement specified for that service.