Features:
- Provides two-wire 4–20 mA field termination for the 5X00501G01 analog input module.
- Supports loop-powered transmitter circuits through the documented personality-module arrangement.
- Distinguishes the two-wire configuration from the separate four-wire terminal option.
The current ordering configuration is 5X00502G01, the two-wire 4-20 mA Ovation analog input personality module for 5X00501G01.
It provides loop-powered transmitter termination for the associated sixteen-channel analog input electronics module in the documented two-wire arrangement.
Before replacement, verify the 5X00501G01 electronic module, loop power, channel polarity, transmitter wiring and exact personality-module group code.
Availability is subject to Apter Power inventory and sourcing confirmation.
Verified resources for Emerson 5X00502G01:
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
- Terminates loop-powered two-wire 4–20 mA transmitters in Ovation systems.
- Provides field connections for sixteen-channel analog input assemblies using 5X00501G01.
- Supports replacement of the documented personality module without changing the electronic module.
- Configure the associated 5X00501G01 channels for two-wire 4-20 mA transmitter operation with this personality module.
- Match transmitter ranges and engineering units to the connected field instruments in the Ovation project database.
- Retain the exact 5X00502G01 group code when documenting the termination configuration or selecting a spare.
- Installs in the personality-module positions assigned to the 5X00501G01 assembly.
- Requires loop polarity and channel terminal assignments to follow the two-wire wiring diagram.
- Needs field power isolated before the personality module or transmitter wiring is serviced.
- The personality module provides the documented two-wire 4-20 mA field-termination arrangement.
- It does not replace the separate 1X00692H01 option specified for four-wire transmitter service.
- Loop polarity, power method, and terminal assignments must follow the published wiring arrangement.