Features:
- High-Precision 16-Channel Analog Input Module Supporting Voltage And Current Signals
- Robust RFI Immunity And Industrial-Grade Isolation Ensure Reliable Operation In Harsh Environments
- Fast 250ms Module Publish Rate With Stable Gain Drift Across Wide Temperature Ranges
The Honeywell TC-IAH161 Analog Input Module is designed to provide accurate and reliable measurement of analog signals in industrial automation systems. Supporting 16 channels of voltage (±10.25 V, 0–10.25 V, 0–5.125 V) and current (0–20.5 mA with internal 250 Ω resistor), TC-IAH161 enables precise monitoring of process variables, making it ideal for applications in manufacturing, energy, and process control industries.
This module addresses challenges related to signal integrity and interference. With input impedances greater than 1.0 MΩ for voltage and 249 Ω nominal for current, along with RFI immunity maintaining errors below 2% of range at 10 V/m (27–1000 MHz), the TC-IAH161 ensures consistent and stable readings even in electrically noisy environments. User-to-system isolation is 100% tested at 2550 VDC for 1 second, providing safety and protection for both equipment and operators.
Designed for efficient integration, the Honeywell TC-IAH161 features a 36-position TC-TBCH terminal block for easy wiring and maintenance. Its 16-bit resolution across all ranges, 250 ms publish rate, low power consumption of 4.1 W max, and minimal gain drift (15 ppm/°C voltage, 20 ppm/°C current) offer a combination of precision, speed, and stability that makes it superior to typical analog input modules. This makes TC-IAH161 a dependable choice for modern industrial control systems requiring both accuracy and operational reliability.
The TC-IAH161 Honeywell Analog Input Module may still be available for purchase and support from Apter Power beyond End-Of-Life (EOL) by the manufacturer (OEM).
Honeywell TC-IAH161 Analog Input Module Manuals, Datasheets, Drivers, Link
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
Honeywell TC-IAH161 Analog Input Module Specs
General
- Manufacturer Honeywell
- Model TC-IAH161
- Condition New Original ready stock
- Product Family TC-PRS021,TC-FTEB01,TC-IXL062
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
- Petrochemical & Refining: Used to monitor critical temperature grids, pressure lines, and fuel flows across extensive pipeline infrastructure.
- Oil & Gas (Upstream & Midstream): Aggregates data from remote wellheads, offshore platforms, and tank farms, processing multiple instrument inputs into a single chassis footprint.
- Power Generation Utilities: Monitors turbine variables, boiler pressures, and auxiliary cooling loop sensors.
- Channel Density & Signal Range: Features 16 high-density channels. It accepts multiple voltage ranges (±10.25 V, 0–10.25 V, 0–5.125 V) and a current range of 0–20.5 mA (typically mapping 4–20 mA field loops).
- HART Protocol Integration: Each individual channel is equipped to pass digital HART (Highway Addressable Remote Transducer) data superimposed over the 4–20 mA analog signal. This lets the control system read secondary variables, device diagnostics, and calibration parameters from smart field transmitters.
- Physical Wiring Interface: Connects to field wiring via the TC-TBCH 36-position removable terminal block. It supports standard single-ended current wiring configurations using external interface modules (like the Allen-Bradley/Rockwell 1492-AIFM16-F-5 series due to hardware form-factor cross-compatibility).
- Galvanic System Isolation: Engineered with rigorous user-to-system isolation tested at 2,550 VDC for 1 second. This safety barrier isolates external electrical faults, lightning transients, or field shorts, preventing them from blowing out the backplane or CPU.
- RFI/EMI Noise Immunity: Offers strong defense against electromagnetic environments, keeping measurement errors below <2% of the total range when subjected to significant Radio Frequency Interference (10 V/m fields sweeping from 27 to 1,000 MHz).
- Open-Circuit / Wire-Break Detection: Incorporates immediate fault diagnostics. If a physical wire snaps or an instrument loses power, the module flags an out-of-bounds negative full-scale reading in under 5 seconds, immediately alerting the HMI operator to the broken channel loop.