Features:
- Ten relay outputs: Ten potential-free contacts switch separate field-load circuits.
- Mixed load use: Honeywell permits resistive and inductive loads within the published limits.
- Watchdog response: The relays de-energize when the FSC system shuts down.
Each channel is a relay-contact output rather than a solid-state source, which makes the load circuit electrically distinct from the module electronics.
The stated ceiling is 2 A per contact, with maximum switched power of 100 W or 1000 VA and a maximum of 30 VAC or 36 VDC under the documented condition.
The module uses A9 and C17 key coding and requires FSC software version 3.00 or later.
Apter Power supports Honeywell 10208/2/1 Relay Output Module sourcing with quotation, documentation and exact-model review.
Honeywell 10208/2/1 Relay Output Module Manuals,Datasheets,Link
Important Notice: Use the complete model and current Honeywell documentation when selecting or installing this module.
- Output form: Ten potential-free electromechanical relay contacts are provided.
- Contact rating: Each channel is rated up to 2 A within the overall voltage and power limits.
- Switched power: Honeywell lists 100 W for DC loads and 1000 VA for AC loads.
- Contact material: The data sheet specifies gold-flashed silver-cadmium-oxide contacts.
- Voltage ceiling: The documented maximum is 30 VAC or 36 VDC under the stated IEC condition.
- Inductive protection: A suppression diode must be mounted externally for inductive loads.
- Load types: Resistive and inductive circuits are both covered when their ratings remain within limits.
- Safety boundary: The contacts were not tested for fail-safe applications.
- Power demand: The module draws 25 mA from 5 VDC and 120 mA from 24 VDC.
- Module keying: Honeywell assigns A9 and C17 to the module holes.
- Rack keying: The matching large rack pins are A9 and C17.
- Software baseline: FSC software version 3.00 or later is listed.
- Resistive switching: The module can operate lamps and similar loads within its relay ratings.
- Inductive switching: Solenoids may be used when an external suppression diode is fitted.
- Ordinary control outputs: The ten channels suit non-safety FSC on/off control duties.