Features:
- Four 24 V DC safe source outputs
- 2 A / 50 W maximum per channel
- Two groups with a 6 A module total
FS-SDO-0424 serves higher-current DC actuators that exceed standard low-current output capacity.
Individual channel capacity does not override the 6 A total or field-distribution limits.
Suppression and return wiring control inductive energy and maintain predictable diagnostics.
The Honeywell FS-SDO-0424 4-Channel 24 V DC 2 A Safe Digital Output Module is available for quotation and technical support from Apter Power.
Verified resources for FS-SDO-0424:
Output Data:
- Safe output channels: 4
- Nominal field voltage: 24 V DC
- Maximum channel current: 2 A
Use the documented FS-SDO-0424 limits when calculating the complete field circuit.
Diagnostics:
- Short-circuit-protected outputs
- Secondary de-energization supervision
- Channel and field-supply diagnostics
Resolve all FS-SDO-0424 channel, wiring and system diagnostics before release to operation.
Compatibility:
- Resistive or inductive DC loads
- Suppression diode required for inductive loads
- Key coding A13/C5
Match FS-SDO-0424 to the approved Safety Manager module, termination and field-device arrangement.
Installation Check:
- Calculate group and total current
- Verify conductor and fuse ratings
- Prove energized and safe states
Complete and record the end-to-end functional test after installing FS-SDO-0424.