Features:
- True TMR (Triple Modular Redundant) Architecture
- High-Density Isolated Inputs with 16 Channels
- Broad Environmental Compliance (ATEX & UL)
The T9833 is specifically designed to support triple-redundant analogue input configurations. It interfaces directly with three separate analogue input modules (e.g., T9432), ensuring that a single point of failure does not interrupt signal acquisition, making it ideal for high availability requirements.
The assembly provides termination for 16 isolated analogue input channels. This high density allows for significant space savings in the cabinet, while the channel-to-channel isolation (rated at 1500 Vdc) protects the controller from field-side surges and ground loops in complex industrial environments.
Rigorously tested for harsh environments, the T9833 supports an extended ambient temperature range of -25°C to +60°C. It is UL listed for Hazardous Locations (Class I, Division 2) and ATEX certified (Ex ec IIC T4 Gc), ensuring reliable operation in oil & gas and petrochemical facilities.
The T9833 ICS Triplex Analogue Input Termination Assembly may still be available for purchase and support from Apter Power beyond End-Of-Life (EOL) by the manufacturer (OEM).
ICS Triplex T9833 Analogue Input Termination Assembly Manuals,Datasheets,Link
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
ICS Triplex T9833 Analogue Input Termination Assembly
General
- Manufacturer ICS Triplex
- Model T9833
- Condition New Original ready stock
- Product Family T9831,T9832,T9801
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
- Real-time Signal Conditioning: Converts field loops (4-20 mA) into digital values for the TMR processor with high accuracy.
- Fault Propagation Management: Utilizes "Safe State" conditioning; if a failure occurs on two of the three input legs, the system votes out the bad value.
- Line Monitoring: Actively injects a diagnostic current to verify loop integrity (open/short circuit detection) without requiring external hardware.
- High Density per Slot: Monitors up to 16 field devices in a single termination footprint, reducing overall cabinet weight and complexity.
- Operating Temperature: -25°C to +60°C (-13°F to +140°F), supporting extreme outdoor and engine room installations.
- Pollution Degree: Designed for Pollution Degree 2 environments (non-conductive pollution only).
- Hazardous Location Suitability: Certified for Class I, Division 2 (Groups A, B, C, D) and ATEX Zone 2 (Ex ec IIC T4 Gc).
- Corrosion Protection: Conformal coating on the printed circuit board meets US MIL-146058C standards, protecting against humidity and airborne contaminants.
- Emergency Shutdown Systems (ESD): Provides critical pressure and temperature monitoring for SIL 3 rated logic solvers.
- Fire & Gas Systems (F&G): Interfaces with 4-20 mA gas detectors and flame sensors in TMR configurations to prevent nuisance trips.
- Subsea & Offshore Modules: Supports Cold Junction Compensation (CJC) for thermocouples monitoring wellhead conditions.
- Turbine Control: High-density analogue input for monitoring bearing vibrations and exhaust temperatures in power generation.