Ask our team:
  • Phone: +86 181 0690 9650
  • E-Mail sales1@apterpower.com
  • Lifecycle status

    Discontinued / Obsolete by OEM
    Apter Power supports FX2N-16CCL-M sourcing and CC-Link migration planning for installed FX systems.

FX2N-16CCL-M

/ 4.9
1001 reviews | Need a Specific Revision?
Mitsubishi Electric FX2N-16CCL-M is a discontinued CC-Link master block for legacy FX2N and FX2NC PLC systems, supporting one master station and up to 64 connected stations.
In Stock
Ships by Wednesday, October 28
Fast Shipping Available
Get a quick price for FX2N-16CCL-M
Quantity
*E-mail
Company
*Mobile
*Content
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)

Technical specifications for FX2N-16CCL-M

  • Manufacturer:
    Mitsubishi
  • Part Number:
    FX2N-16CCL-M
  • Product Family:
    Mitsubishi
  • Product Type:
    CC-Link System Master Block
  • Stock:
    1
  • Network:
    CC-Link
  • Station Role:
    Master station
  • Supported PLC Families:
    FX2N and FX2NC
  • Connected Stations:
    Up to 64
  • Transmission Speed:
    156 kbps to 10 Mbps
  • Internal Supply:
    5 VDC, 220 mA
  • Product Status:
    Discontinued September 2012
  • Weight:
    0.4 kg
  • Estimated shipping dimensions:
    8.5 x 9 x 8.7 cm
  • Tariff Code:
    Please confirm the destination before shipping
  • Place of shipment:
    Xiamen,Fujian,China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals Network Planning Installation Migration Fit Product Applications

Features:

  • Legacy CC-Link master: The block coordinates remote stations from an FX2N or FX2NC control platform.
  • Retained network map: Existing station allocations can be recovered when settings and program evidence are preserved.
  • Migration boundary: Discontinued status makes supportability part of the maintenance decision.
FX2N-16CCL-M belongs to installed FX systems whose application program and CC-Link layout were engineered around this master block.

A recovery project aims to reproduce the existing configuration; a modernization project redesigns hardware, software and validation around a supported platform.

Keeping those two paths separate prevents an apparently similar newer block from being accepted without program and network changes.

Apter Power can help confirm the Mitsubishi Electric FX2N-16CCL-M CC-Link Master Block, legacy system fit, configuration evidence and migration scope before quotation.
Mitsubishi FX2N-16CCL-M CC-Link System Master Block Manuals,Datasheets,Link
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
  • Station map: Export or record every occupied station and assigned data range.
  • Transmission setting: Preserve the network speed and physical switch positions.
  • Program dependency: Identify PLC code that reads or writes CC-Link buffers.
  • Cable baseline: Record termination, shield and diagnostic conditions before shutdown.
  • Power budget: Confirm the host PLC can supply the master block and adjacent expansion hardware.
  • Safe isolation: Remove controller and network power before changing the expansion bus.
  • Mechanical fit: Retain approved mounting, connector and cable-clearance arrangements.
  • Controlled restart: Bring the network online before enabling machine outputs.
  • Like-for-like path: Use the exact legacy block only when configuration and support risks are accepted.
  • New-platform path: Treat FX5-CCL-MS as a migration component, not a direct drop-in substitute.
  • Software conversion: Review buffer mapping, diagnostics and project tools during redesign.
  • Validation plan: Re-prove every remote station and affected machine function after migration.
  • Legacy production lines: Maintains CC-Link operation in installed FX2N control systems.
  • Machine recovery: Restores a failed master while the original network design is retained.
  • Planned migration: Provides the installed-base reference for a controlled modernization project.
  • Shutdown support: Helps prepare configuration and test evidence before limited maintenance windows.
Description
FX2N-16CCL-M adds CC-Link master-station control to legacy Mitsubishi FX2N or FX2NC PLC installations, coordinating cyclic data exchange with configured remote stations.

Because FX2N-16CCL-M is discontinued, maintenance decisions should separate a like-for-like recovery from a platform migration. Existing station allocation, network speed, program mapping and power budget remain essential evidence.

A replacement FX2N-16CCL-M is accepted only after the complete network returns without configuration alarms and every safety-relevant remote signal is proved. Migration to a newer controller requires a separate engineering plan.
Alternative Names
FX2N16CCLM FX2N 16CCL M
Technical notes
FX2N-16CCL-M is a discontinued network master for legacy FX systems. Back up the PLC program and record station allocation, network speed and switch settings before removal. Isolate controller and CC-Link power, then prove network diagnostics and critical remote I/O after restart. Stop if configuration data is missing or a newer master is being treated as drop-in.
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
What evidence should be captured before removing FX2N-16CCL-M?
Back up the PLC project and record station allocation, transmission speed, switch settings, cable termination and active diagnostics. Stop if those records cannot be recovered.
Can FX5-CCL-MS replace FX2N-16CCL-M without software changes?
No. Mitsubishi identifies FX5-CCL-MS as a newer alternative, but the controller platform, configuration method and program interfaces require an engineered migration rather than a drop-in exchange.
Why can a replacement FX2N-16CCL-M power up while every remote station stays offline?
Compare the restored network speed, station configuration, cabling and termination with the captured baseline. A powered master does not prove that its CC-Link setup matches the network.
How should maintenance commission FX2N-16CCL-M after a like-for-like exchange?
Recover normal network diagnostics first, then prove required remote inputs and guarded outputs against the PLC program before automatic operation resumes.
When should a plant stop sourcing another FX2N-16CCL-M and plan migration instead?
Choose migration when configuration evidence is weak, spare support is no longer acceptable, or wider FX hardware obsolescence makes repeated like-for-like recovery unsustainable.
What should accompany an urgent request for FX2N-16CCL-M?
Provide the complete model, installed PLC type, firmware or project evidence, station count, network speed, fault symptoms and required shutdown date so the recovery path can be reviewed.