Features:
- Switches two changeover contact circuits from a 24 V DC control signal.
- Uses spring-clamp wiring in the compact MIRO 12.4 interface format.
- Provides safe separation between the input electronics and relay contact side.
The listing retains D-71570 exactly as supplied and records Article No. 6652102 as the matching hardware identifier.
It interposes controller outputs from higher-voltage or higher-current field loads through relay contacts.
Contact category, inrush and expected cycle life should be evaluated rather than relying only on the six-ampere headline rating.
Apter Power can review sourcing, documentation and system matching for D-71570.
Verified resources for Murrelektronik D-71570:
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
- PLC panels use the module to drive contactors or signalling circuits that cannot connect directly to a transistor output.
- Building and machine controls isolate two field circuits while using one 24 V command path.
- Service retrofits replace a worn relay interface without altering the controller program or load wiring arrangement.
- Safe separation is specified according to EN 60947-1 for the relay interface.
- IP20 construction requires installation inside a closed electrical cabinet.
- The connected load must respect the AC-15 or DC-13 utilisation-category rating rather than only the resistive maximum.
- The 24 V DC coil operates across the documented 19.2 to 30 V range at about 18 mA.
- Two changeover contacts provide flexible normally open and normally closed wiring.
- Switching capability decreases substantially for high-voltage DC inductive loads.
- Spring-clamp terminals support direct cabinet wiring without screw retightening.
- The narrow MIRO 12.4 format is intended for DIN-rail interface rows.
- Input polarity, contact commons and protective devices must be identified before conductor transfer.