- Use 68.5 A as the 4 kHz continuous-output limit and 42.2 A for standstill duty
- Include the 80 A rated DC input and other simultaneous axes in the shared-bus calculation
- Retain the HAS02 shield connection and verify brake voltage at the motor
HMS01.1N-W0110-A-07-NNNN is the R911310462 IndraDrive M single-axis inverter power section.
Its 110 A maximum output is intended for transient demand. At 4 kHz, continuous running current is 68.5 A and the documented standstill limit is 42.2 A.
Check the 254–750 VDC source, 80 A rated input, 640 W cabinet heat load, HAS02 shield hardware, X6 wiring and separately selected control section before commissioning.
Availability, condition, price, and shipping time for HMS01.1N-W0110-A-07-NNNN are confirmed during quotation.
Bosch Rexroth HMS01.1N-W0110-A-07-NNNN IndraDrive M Single-Axis Inverter Manuals, Product Family, Links
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
- Supply the inverter from the documented 254–750 VDC common bus
- Allow 80 A rated DC input plus simultaneous demand from every connected axis
- Include the 640 W continuous-current loss in the cabinet thermal calculation
- Use 42.2 A as the 4 kHz continuous-current limit at motor standstill
- Account for the reduction to 14.7 A at standstill when operating at 16 kHz
- Verify motor-brake voltage at the motor when cable length causes voltage drop
- Retain the assigned HAS02 shield plate and original motor-cable shield termination
- Check X6 motor-brake and temperature-monitoring connections before enabling torque
- Restore only the control section, firmware and parameter set approved for this axis
- Compare the documented 36.8 kW standard-motor profile at 460 V with the required duty
- Use the 68.5 A continuous limit for sustained motion rather than the 110 A maximum
- Evaluate clamping, vertical and dwell axes against the 42.2 A standstill limit