Ask our team:
  • Phone: +86 181 0690 9650
  • E-Mail sales1@apterpower.com

ATV930C31N4C

/ 4.9
1001 reviews | Need a Specific Revision?
The Schneider Electric ATV930C31N4C is a Altivar Process ATV900 series inverter with a power of 315kW and a voltage of 400/480V. It is specially designed for demanding industrial environments and has an IP00 protection rating.
Get a quick price for ATV930C31N4C
Quantity
*E-mail
Company
*Mobile
*Content
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)

Technical specifications for ATV930C31N4C

  • Manufacturer:
    Schneider Electric
  • Part Number:
    ATV930C31N4C
  • Product Family:
    Altivar Process
  • Rated Supply Voltage:
    400...480 V AC (-15%...10%), 3-phase
  • Motor Power (Heavy Duty):
    250 kW / 400 HP (150% overload for 60s)
  • Motor Power (Normal Duty):
    315 kW / 500 HP (120% overload for 60s)
  • Rated Output Current:
    616 A
  • Output Frequency Range:
    0.1...599 Hz (configurable)
  • Protection Rating:
    IP00
  • Braking Unit:
    None
  • Digital Inputs:
    Up to 10
  • Weight:
    3.2 kg
  • Estimated shipping dimensions:
    14.4x20.2x29.5cm
  • Tariff Code:
    8537101190
  • Country of origin:
    France
  • Place of shipment:
    Xiamen, Fujian, China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals Specifications Applications Environmental Ratings Safety & Compliance

Features:

  • Native Dual-Protocol Industrial Ethernet
  • Extreme Environment Derating Validation
  • Advanced I/O Flexibility with Sink/Source Switch
The Schneider Electric ATV930C31N4C eliminates communication gateways with embedded EtherNet/IP and Modbus TCP. Description: This drive integrates directly into your plant's DCS or PLC architecture. The dual-port switch allows for daisy-chain or ring topologies, reducing installation costs and improving network resilience. Real-time drive parameters, diagnostics, and energy data are accessible via standard web browsers using the built-in Web server.

Guaranteed performance in high-temperature settings, verified by official switching frequency curves up to 60°C. Description: Unlike standard drives that fail above 40°C, the Schneider Electric ATV930C31N4C provides transparent derating curves (Page 14). At 50°C, you can maintain 100% current at 4kHz switching frequency, or 50% at 8kHz. This engineering transparency allows for precise cabinet thermal management and prevents unexpected shutdowns in hot, un-airconditioned plants.

Effortless integration with any PLC technology via a hardware Sink/Source switch. Description: The control terminals feature a physical switch (Page 12) to adapt the logic inputs from Source (PNP transistor, factory default) to Sink (NPN transistor). This eliminates the need for intermediate relays or level shifters, speeding up installation by up to 20% during legacy system retrofits. The documentation also provides five distinct wiring diagrams for internal/external power supplies.

The ATV930C31N4C Schneider Electric  Variable Speed Drive may still be available for purchase and support from Apter Power beyond End-Of-Life (EOL) by the manufacturer (OEM).
Schneider Electric ATV930C31N4C Variable Speed Drive Manuals,Datasheets,Link Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
Schneider Electric ATV930C31N4C Variable Speed Drive

General

  • Manufacturer Schneider Electric
  • Model ATV930C31N4C
  • Condition New Original ready stock
  • Product Family ATV32HU15N4,ATV32HU30N4,ATV71HD55N4Z
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
  • Heavy Material Handling: Ideal for high-inertia loads like belt conveyors, bucket elevators, and stacker-reclaimers in mining. The Schneider Electric ATV930C31N4C provides up to 180% torque for breakaway starts.
  • Oil & Gas Pumping (Centrifugal/Progressive Cavity): The embedded PID regulator optimizes flow and pressure, while "Stop & Go" sleep mode reduces energy consumption by up to 40% during low-demand periods.
  • Metal & Steel Processing: Suited for high overload cycles on rolling mills, wire drawing machines, and crane hoists. The drive's robust short-circuit rating withstands harsh line harmonics.
  • Water/Wastewater Treatment: The native EtherNet/IP allows direct integration into SCADA systems for remote pump control, filter backwash sequencing, and leakage detection without an external PLC.
  • High-Temperature Operation: Validated for use up to 60°C (140°F) with predictable derating. The chart (Page 14) allows engineers to size the drive precisely for un-conditioned sheds or desert installations.
  • Altitude Capability: Operates at full rating up to 1000m (3300 ft). Above 1000m, derate the output current by 1% per additional 100m, up to a maximum of 3000m (air insulation limitation).
  • Vibration & Shock: Designed to IEC/EN 61800-5-1 for industrial environments, withstanding 1.5 mm peak-to-peak (2-13 Hz) and 1 gn (13-200 Hz).
  • Corrosive Atmosphere: The standard coating is suitable for Class 3C2 environments (mild pollutants). For severe chemical or salt-spray environments, order the "S" variant (e.g., ATV930C31N4S) with enhanced conformal coating.
  • Functional Safety (STO): The integrated Safe Torque Off (SIL3 / PL e) meets IEC 61508 and prevents unexpected start-ups, allowing you to eliminate external contactors for safety in Category 3 systems.
  • Network Security: Complies with IEC 62443-2-4 (Industrial network security). The embedded web server has a password-protected access and disable function.
  • Global Certifications: Holds CE (Europe), UL 61800-5-1 (US/Canada), RCM (Australia), and EAC (Eurasia). Essential for machine builders shipping globally.
  • Energy Efficiency (IE2): As per IEC 61800-9, the Schneider Electric ATV930C31N4C is classified as an IE2 drive, ensuring minimal energy losses (less than 3% at nominal load), reducing cooling costs.
Description
The Schneider Electric ATV930C31N4C is a flagship variable speed drive from the Altivar Process ATV900 range, designed to set a new benchmark for motor control in heavy industrial processes. Delivering a robust 315 kW of power at 400/480V, this IP00-rated unit is built for cabinet integration in applications such as mining conveyors, oil & gas pumping, and high-torque metal forming. Unlike standard drives, the ATV930 series prioritizes process continuity with superior overload capacity (up to 180% for 2 seconds) and embedded safety, ensuring your most critical operations remain uninterrupted.

Schneider Electric ATV930C31N4C  distinguishes itself through its native dual-communication protocol support. Equipped with embedded EtherNet/IP and Modbus TCP, the Schneider Electric ATV930C31N4C offers deep integration into plant-wide control architectures without requiring expensive option cards. It features an integrated Web server for real-time energy monitoring, predictive maintenance alerts via QR code scanning, and "Stop and Go" energy-saving functionality, directly targeting operational expenditure (OPEX) reduction.

Designed for harsh conditions, the Schneider Electric ATV930C31N4C operates reliably in ambient temperatures up to 60°C with appropriate derating, as verified by the supplied switching frequency curves. It complies with international safety standards including IEC 61508 (SIL3) for its STO function. For installation flexibility, the document provides three mounting types (Individual IP21, Side-by-Side IP20, Individual IP20) and detailed sink/source configuration diagrams, making it adaptable to both NPN and PLC output architectures.
Alternative Names
ATV93OC31N4C ATV930D37N4 ATV930C13N4 ATV93OC3IN4C ATV21HD11N4  ATV930D18N4 ATV320U30N4C ATV71HD55N4Z 
Technical notes
The Schneider Electric ATV930C31N4C, the IP00 rating mandates installation within a certified control cabinet to ensure environmental protection and compliance with IEC 61800-5-1. As this model lacks a built-in braking unit, an external resistor or regenerative unit is required for high-inertia, rapid deceleration applications. Furthermore, the switching frequency derating chart (Page 14) shows a linear de-rate from 100% at 4kHz to 50% at 8kHz when the ambient temperature reaches 50°C (104°F).
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
Does the Schneider Electric ATV930D37N4 (Note: customer meant ATV930C31N4C) support legacy Profibus DP networks natively?
No, the base model Schneider Electric ATV930C31N4C has embedded EtherNet/IP and Modbus TCP only. For Profibus DP, Profinet, or CANopen, you must install the corresponding VW3A3600 series communication option card on the drive's dedicated slot.
How do I find the exact Modbus register address for “Motor Torque” for the Schneider Electric ATV930C31N4C to read via the PLC?
Use the "DriveCom" profile parameters. For the Schneider Electric ATV930C31N4C, the motor torque (as a % of nominal) is typically read from Modbus address 3202 (Internal PI word 2) or 8604 (Scaled torque). Refer to the "Altivar 900 Communication Parameters" manual.
What is the expected lifespan of the cooling fans on the Schneider Electric ATV930C31N4C in a cement plant environment?
In clean environments, fan life is ~50,000 hours. In harsh, dusty settings (common for 315kW drives), the internal cooling ducts clog. You should implement a quarterly filter check and use the drive's built-in "Fan Running Time" counter (parameter [FAN-]). Plan for fan replacement every 2-3 years in such environments.