Technical specifications for 5466-348

  • Manufacturer:
    Woodward
  • Part Number:
    5466-348
  • Product Family:
    Woodward easYgen Series
  • Rate Group:
    One driver per port, 5 milliseconds
  • Protoco:
    RS-485 UART
  • Baud Rate:
    417 kbaud
  • Parity:
    None
  • Data Bits:
    8
  • Stop Bit:
    1
  • Discrete inputs:
    16 × 24 V DC
  • Analog inputs:
    4 × 4-20 mA
  • Operating temperature:
    –20 … +70 °C
  • Weight:
    0.9 kg
  • Estimated shipping dimensions:
    2.5x24.5x26.1cm
  • Tariff Code:
    8537101190
  • Country of origin:
    USA
  • Place of shipment:
    Xiamen, Fujian, China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.
Description
5466-348 is a Netcon SIO Module developed by Woodward. SIO Module is equipped with three RS-485 ports. Each port is intended for use with EM or GS/LQ Digital Actuator Drivers.

The Woodward 5466‑348 is a high‑performance NetCon SIO (Serial Input/Output) communication module engineered as a critical interface component for Woodward’s NetCon 5000B control ecosystem, designed to enable seamless, real‑time data exchange between NetCon controllers and EM/GS/LQ series digital actuator drivers in heavy‑duty industrial applications such as power generation, oil & gas, marine propulsion, and industrial turbine control. 

As a core connectivity module in Woodward’s modular automation lineup, it addresses the demand for precise, low‑latency actuator control and monitoring—where reliable serial communication directly impacts system stability, operational safety, and process efficiency in 24/7 mission‑critical environments.

At its core, the 5466‑348 features three isolated RS‑485 UART communication ports, each dedicated to direct connection with Woodward EM or GS/LQ digital actuator drivers—industry‑standard devices used to regulate valve positions, turbine governor speeds, and other critical actuation functions. Each port operates at a fixed 417 kbaud rate (8 data bits, 1 stop bit, no parity) for ultra‑fast data transfer, with a 5ms per‑port update rate that ensures critical parameters (position demand, driver status, fault codes) are refreshed in near‑real time, eliminating latency in dynamic control loops.
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
What is 5466-348?
It is Netcon SIO Module developed by Woodward.
How many drivers can be connected to each RS-485 port?
Each RS-485 port allows for the connection of one driver. Therefore, the module can accommodate a total of three drivers, one for each port.
What is the update rate for critical parameters when using one driver per port?
When using one driver per port, the update rate for critical parameters is 5 milliseconds. This means that important data related to the actuator drivers can be refreshed every 5 milliseconds.