DSDI110A 57160001-AAA

/ 4.9
1001 reviews | Need a Specific Revision?
ABB DSDI110A 57160001-AAA is a 32-channel, opto-isolated 24 V DC digital input board for S100 I/O installations, supporting scanned or interrupt-controlled signal acquisition and event detection.
In Stock
Ships by Friday, October 30
Fast Shipping Available
Get a quick price for DSDI110A 57160001-AAA
Quantity
*E-mail
Company
*Mobile
*Content
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)

Technical specifications for DSDI110A 57160001-AAA

  • Manufacturer:
    ABB
  • Part Number:
    DSDI110A 57160001-AAA
  • Product Family:
    ABB Advant OCS and Advant-800xA
  • Product Type:
    Digital Input Board
  • Stock:
    1
  • Number of Input Channels:
    32
  • Channel Arrangement:
    4 groups of 8
  • Input Voltage:
    24 V DC
  • Input Isolation:
    Opto-isolated
  • Input Control:
    Scanning or interrupt
  • Event Capability:
    Event detection
  • Channel Type:
    DI
  • Dimensions:
    22.5 × 1.8 × 21.6 cm
  • Weight:
    0.34 kg
  • Tariff Code:
    8538900000
  • Country of origin:
    Sweden
  • Place of shipment:
    Xiamen, Fujian, China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals Input Handling Connections Diagnostics Application
  • ABB identifies DSDI110A 57160001-AAA as a 32-channel S100 digital input board.
  • The inputs are opto-isolated and arranged in four groups of eight for 24 V DC field signals.
  • Scanning, interrupt control and event detection are documented for this exact order number.

DSDI110A 57160001-AAA is an ABB digital input board used in documented S100 I/O configurations.

Its external signal behavior depends on the selected DSTD connection unit and matching DSTK cable, while the board handles 32 isolated inputs through scan or interrupt control.

Before installation or replacement, verify the rack position, connection unit, cable, field-voltage class, channel mapping, event settings, and controller project.

Availability, condition, price, and shipping time for DSDI110A 57160001-AAA are confirmed during quotation.

ABB DSDI110A 57160001-AAA Digital Input Board Manuals, Datasheets, Links

Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.

  • Input acquisition can be controlled by cyclic scanning or by interrupt.
  • Pulse catching may be configured when short-duration field events must be retained.
  • The four groups of eight provide the documented channel organization for controller mapping.
  • DSTD 150A and DSTD 190 are documented for standard 24 V DC input arrangements.
  • DSTD 195, DSTD 197 and DSTD 198 extend documented isolation or field-voltage options through DSTK 226L3.
  • DSTD 145, DSTD 147 and DSTD 148 support documented object-oriented connections through DSTK 226L5.
  • ABB S100 I/O self-diagnostics continuously monitor module operation.
  • Detected errors are reported through front-panel LEDs and operator-station alarm indications.
  • Malfunctioning inputs can be disabled and simulated by manual entry during controlled fault isolation.
  • S100 I/O acquisition of grouped 24 V DC binary field signals.
  • Interrupt-driven event input handling in Advant Master control installations.
  • Pulse-catching digital input service with ABB-documented DSTD connection hardware.
Description
DSDI110A 57160001-AAA is an ABB S100 I/O digital input board for Advant Master and compatible ABB control-system installations.

The board provides 32 opto-isolated 24 V DC inputs arranged as four groups of eight, with input acquisition controlled by scanning or interrupt and support for event detection.

Before installation or replacement, confirm the complete 57160001-AAA order number, connection unit, cable, event-handling configuration, rack position, field voltage, and saved controller application.
Alternative Names
DSDI110A 57160001-AAA DSDI 110A 57160001-AAA DSDI110A DSDI 110A 57160001-AAA ABB DSDI110A 57160001-AAA ABB DSDI 110A 57160001-AAA EXC57160001-AAA
Technical notes
DSDI110A 57160001-AAA uses model-specific DSTD connection units and DSTK cables; retain the 24 V DC grouping, scan or interrupt mode, and event configuration during replacement.
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
Which connection unit should be retained with ABB DSDI110A 57160001-AAA?
Match the installed field-voltage and isolation arrangement. ABB documents DSTD 150A or DSTD 190 for direct 24 V DC service, with other DSTD units and cables used for specific isolated, higher-voltage, or object-oriented arrangements.
Can ABB DSDI110A 57160001-AAA capture short input events?
Yes. ABB documents scanned or interrupt-controlled acquisition and permits pulse-catching configuration, but the controller application must retain the original event-handling setup and channel assignment.
Is ABB DSDI110A 57160001-AAA a direct substitute for every 32-channel S100 input board?
No. Channel count alone is insufficient. The 24 V DC input class, four-group arrangement, connection unit, cable, isolation method, and controller configuration must match the installed S100 assembly.
What should be checked when ABB DSDI110A 57160001-AAA uses an isolated connection unit?
Confirm the exact DSTD model, DSTK cable, field-voltage class, group commons, galvanic-isolation requirement, terminal labeling, and the input assignment stored in the controller project.
Can ABB DSDI110A 57160001-AAA be used with 120 V AC or 230 V AC field signals?
Only through the ABB-documented DSTD 197 or DSTD 198 connection arrangements and the required DSTK 226L3 cable. The board must not be wired directly as though it were a native AC-input module.
What must be preserved before replacing ABB DSDI110A 57160001-AAA?
Preserve the rack location, complete order number, connection-unit identity, cable type, field wiring, channel map, interrupt or scan selection, and event-detection settings so the replacement follows the existing S100 design.
Why might an ABB DSDI110A 57160001-AAA input fail after the board itself has been replaced?
A persistent fault may originate in the selected DSTD connection unit, DSTK cable, field supply, group common, terminal wiring, or project configuration rather than the input board alone.