Ask our team:
  • Phone: +86 181 0690 9650
  • E-Mail sales1@apterpower.com
  • Lifecycle status

    Active / Available from OEM
    Apter Power validates INICT12 host software context, NTMP01 settings, point-database needs, and condition before procurement.

INICT12

/ 4.9
1001 reviews | Need a Specific Revision?
ABB INICT12 gives a host computer command-driven access to Cnet point data through a two-port RS-232-C interface.
In Stock
Ships by Wednesday, October 28
Fast Shipping Available
Get a quick price for INICT12
Quantity
*E-mail
Company
*Mobile
*Content
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)

Technical specifications for INICT12

  • Manufacturer:
    ABB
  • Part Number:
    INICT12
  • Product Family:
    ABB Bailey
  • Product Type:
    Harmony Rack Cnet-to-Computer Transfer Module
  • Stock:
    1
  • Memory:
    512 KB ROM; 512 KB RAM; 128 KB NVRAM
  • Power requirements:
    +5 V DC at 2 A; 10 W
  • Ports:
    2 RS-232-C through NTMP01
  • Communication rate:
    User-selectable up to 19.2 kbaud
  • Tag capacity:
    10,000 point definitions
  • Mounting:
    One standard module mounting unit slot
  • Tariff Code:
    Please confirm the destination before shipping
  • Country of origin:
    Sweden
  • Place of shipment:
    Xiamen,Fujian,China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals Specifications Host Interface Serial Integration Replacement Scope

Features:

  • Host point access: Exposes Cnet data through a command-driven computer interface.
  • Two serial ports: Uses NTMP01 for RS-232-C connectivity and DTE/DCE selection.
  • Defined database scale: Stores up to 10,000 point definitions.
ABB INICT12 bridges host software to the Symphony communication network without serving as a controller or general Ethernet gateway.

Its command-response behavior makes the host driver and point database as important as the physical module during recovery.

Integration work should begin with the installed INICI12 wiring and software context, particularly when other sites use the different INICI03 architecture.

Provide the ABB INICT12 port settings, NTMP01 jumper state and host-software details when requesting integration or sourcing support.
ABB INICT12 Harmony Rack Cnet-to-Computer Transfer Module Manuals, Datasheets, Link Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
ABB INICT12 Harmony Rack Cnet-to-Computer Transfer Module Specs

General

  • Manufacturer ABB
  • Model INICT12
  • Condition New Original ready stock
  • Product Family Symphony Harmony / INFI 90
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.

INICI12 Communication Path:

  • Network front end: INNIS01 connects the interface node to Cnet.
  • Transfer engine: The module executes commands from the host.
  • Physical access: NTMP01 provides the two RS-232-C ports.

Command-Driven RS-232-C:

  • Maximum rate: User-selectable up to 19.2 kbaud.
  • Port mode: NTMP01 jumpers select DTE or DCE.
  • Software role: The host issues commands and interprets replies.

Data and System Continuity:

  • Point database: Protect as many as 10,000 definitions.
  • Time service: Retain the configured synchronization behavior.
  • System functions: Revalidate security, status monitoring and module configuration commands.
Description
Within an INICI12 host interface, ABB INICT12 works with an INNIS01 as the Cnet-to-computer transfer module. It gives a computer access to point data on either a central or satellite Cnet through a command-and-response software connection.

The host reaches ABB INICT12 through two RS-232-C ports on an NTMP01 termination unit at selectable rates up to 19.2 kbaud. Firmware commands support data acquisition, process monitoring and control, time synchronization, status monitoring, security and module configuration across as many as 10,000 point definitions.

When integrating ABB INICT12, preserve the host command software, serial framing and point database, then confirm the NTMP01 DTE or DCE jumper setting. ABB distinguishes this serial INICI12 path from INICI03 hardware that can also use SCSI, so interface assumptions must follow the installed architecture.
Alternative Names
ABB INICT12 Computer Transfer Module Bailey INICI12 Host Interface Board Harmony Rack Cnet Serial Gateway INFI 90 Computer Interface Module
Technical notes
Deploy ABB INICT12 with an INNIS01 and an NTMP01 configured for the required DTE or DCE host connection. The interface is limited to RS-232-C at up to 19.2 kbaud and 10,000 point definitions; preserve the host command software, port settings and point database before replacement.
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
What hardware creates an INICT12 host interface to Cnet?
The transfer module combines with an INNIS01 as the INICI12 interface, while an NTMP01 termination unit presents the two RS-232-C host ports.
How does a computer exchange data with INICT12?
Host software sends a command, the module executes it and returns a response. Supported functions include point access, monitoring, control, time synchronization and configuration.
What point capacity should be planned for INICT12?
ABB specifies up to 10,000 point definitions, so the host database should be checked before migrating a larger interface configuration.
Why can INICT12 fail to communicate after a cable replacement?
Check the NTMP01 DTE/DCE jumper, cable pinout, port selection, baud and framing, host command software and the restored interface database.
Can INICT12 use the SCSI connection documented for INICI03?
No SCSI port is specified for the INICI12 path. ABB documents its host connection as RS-232-C at rates up to 19.2 kbaud.
What should be backed up before exchanging INICT12?
Save the point definitions, host interface configuration, serial parameters, security settings, time-synchronization setup and healthy communication diagnostics.
How should INICT12 be acceptance-tested after installation?
Verify command-and-response traffic, point reads, permitted control actions, time synchronization, status reporting and both configured serial ports under the site procedure.