Ask our team:
  • Phone: +86 181 0690 9650
  • E-Mail sales1@apterpower.com
  • Lifecycle status

    Active / Available from OEM
    Apter Power supports quotations, ABB documentation, cable review, and 5.5 kW drive sourcing.

ACS580-01-12A7-4 3AXD50000038953

/ 4.9
1001 reviews | Need a Specific Revision?
ABB ACS580-01-12A7-4 3AXD50000038953 is a 400 V ACS580-01 IP21 wall-mounted drive rated 12.6 A and 5.5 kW for general-purpose motor control.
In Stock
Ships by Friday, October 30
Fast Shipping Available
Get a quick price for ACS580-01-12A7-4 3AXD50000038953
Quantity
*E-mail
Company
*Mobile
*Content
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)

Technical specifications for ACS580-01-12A7-4 3AXD50000038953

  • Manufacturer:
    ABB
  • Part Number:
    ACS580-01-12A7-4 3AXD50000038953
  • Product Family:
    ABB Drives
  • Product Type:
    ACS580 General Purpose Wall-Mounted Drive
  • Stock:
    1
  • ABB Product ID:
    3AXD50000038953
  • Voltage Class:
    400 V
  • Nominal Output Current:
    12.6 A
  • Nominal Motor Power:
    5.5 kW
  • Maximum Current:
    15.3 A
  • Heavy-Duty Rating:
    9.4 A / 4.0 kW
  • Frame Size:
    R1
  • Maximum Losses:
    237 W
  • Protection:
    IP21 / UL Type 1
  • Control Panel:
    ACS-AP-S assistant control panel
  • Safety Function:
    Safe Torque Off integrated
  • EMC and Braking:
    Internal EMC C2 filter; integrated braking chopper
  • Weight:
    4.6 kg
  • Estimated shipping dimensions:
    12.5x37.3x22.3cm
  • Tariff Code:
    Please confirm the destination before shipping
  • Country of origin:
    Sweden
  • Place of shipment:
    Xiamen,Fujian,China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals Specifications Commissioning EMC & Grounding Option Planning

Features:

  • General-purpose motor control: The 5.5 kW/12.6 A nominal-use rating covers common variable-torque and constant-torque applications.
  • Built-in engineering functions: Safe Torque Off, EMC filtering, an assistant panel, coated boards, and a braking chopper reduce external hardware.
  • Application flexibility: Motor macros, energy functions, optional fieldbus adapters, and configurable I/O support plant integration.
ACS580-01-12A7-4 3AXD50000038953 balances motor-control capability with a compact R1 wall-mounted package for 400 V industrial systems.

The assistant panel supports commissioning and diagnostics, while the base hardware includes STO, EMC filtering, and a braking chopper; protocol adapters remain project-specific options.

Select the drive from measured motor current and duty, then validate the supply system, protection, cable, ventilation, EMC, control wiring, fieldbus, parameters, and fault-response plan.

Availability is subject to Apter Power's current inventory and sourcing confirmation.
ABB ACS580-01-12A7-4 3AXD50000038953 ACS580 General Purpose Wall-Mounted Drive Manuals, Datasheets, Link Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
ABB ACS580-01-12A7-4 3AXD50000038953 ACS580 General Purpose Wall-Mounted Drive Specs

General

  • ManufacturerABB
  • ModelACS580-01-12A7-4 3AXD50000038953
  • ConditionNew Original ready stock
  • Product FamilyABB ACS580-01 Drives
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.

Startup and motor matching

  • Motor data: Enter the verified nameplate voltage, current, frequency, speed, and power.
  • Duty check: Use actual load torque, overload duration, ambient conditions, and switching frequency.
  • Direction test: Prove motor rotation and process interlocks before coupling the full load.
  • Record: Archive parameters, option codes, firmware, fault history, and acceptance results.

Supply-system compatibility

  • TN-S system: The internal EMC filter is intended for a symmetrically grounded TN-S supply.
  • Other systems: Follow ABB instructions before connecting to IT, corner-grounded delta, midpoint-grounded delta, or TT systems.
  • Protective earth: Use the required PE conductors, shield terminations, and cable routing.
  • Motor cable: Select cable construction and length against EMC and drive hardware limits.

Controls and communication scope

  • Fieldbus: Select the ABB adapter that matches the plant protocol and engineering tool.
  • I/O: Map every command, reference, interlock, and feedback signal before wiring.
  • Safety: Integrate STO into the machine safety function; it is not a general isolation device.
  • Braking: Verify whether the integrated chopper, an external resistor, and thermal protection are required.
Description
ACS580-01-12A7-4 3AXD50000038953 is the 5.5 kW, 12.6 A nominal-use configuration in ABB’s ACS580-01 general-purpose drive family, designed to control standard induction and permanent-magnet motors in pumps, fans, conveyors, mixers, and similar industrial loads.

ACS580-01-12A7-4 3AXD50000038953 uses frame R1 with a maximum current of 15.3 A, heavy-duty rating of 9.4 A/4.0 kW, an assistant control panel, internal EMC filtering, Safe Torque Off, coated boards, and an integrated braking chopper.

ACS580-01-12A7-4 3AXD50000038953 simplifies cabinet and machine integration, but reliable operation still depends on correct motor sizing, overload duty, cable and fuse selection, earthing system, EMC configuration, ventilation, fieldbus options, and a validated startup record.
Alternative Names
ACS580-01-12A7-4 ACS580 01 12A7 4 ACS5800112A74 3AXD50000038953 ABB ACS580-01-12A7-4
Technical notes
ACS580-01-12A7-4 3AXD50000038953 is a R1, 400 V drive rated 12.6 A/5.5 kW nominal. Before energizing, verify motor nameplate data, overload duty, protective earth, cable and fuse sizing, STO wiring, and the supply earthing system. The internal EMC filter is intended for symmetrical TN-S networks and may require disconnection on IT, corner-grounded delta, midpoint-grounded delta, or TT systems.
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
Why can a 5.5 kW motor still require a larger drive than ACS580-01-12A7-4 3AXD50000038953?
ABB rates this configuration at 12.6 A/5.5 kW nominal but 9.4 A/4.0 kW heavy duty. A high-overload torque cycle can therefore require a different selection.
Which installation fault level accompanies the 16 A gG fuse listed for ACS580-01-12A7-4 3AXD50000038953?
ABB lists 128 A minimum installation short-circuit current with the 16 A gG fuse. Verify that the upstream network and protection design satisfy the full coordination conditions.
How should the 237 W maximum loss of ACS580-01-12A7-4 3AXD50000038953 influence R1 ventilation?
Use 237 W in the cabinet heat calculation; it is the highest documented loss among these four R1 ratings. Check airflow, spacing, ambient temperature, and adjacent equipment.
Can ACS580-01-12A7-4 3AXD50000038953 be replaced by ACS580-01-018A-4 without mechanical review?
No. The change moves from R1 to R2 and raises nominal current from 12.6 A to 17.0 A. Review enclosure fit, terminals, protection, cables, heat, and parameters.
Why is the 15.3 A maximum current not a continuous operating target for ACS580-01-12A7-4 3AXD50000038953?
ABB documents 12.6 A nominal and 9.4 A heavy-duty output. Continuous selection must follow motor current and duty, while 15.3 A remains a maximum capability figure.
What must be checked when retrofitting ACS580-01-12A7-4 3AXD50000038953 into wiring sized for a smaller R1 drive?