B&R X20AI2632 is a two-channel high-speed analog input module for ±10 V or 0 to 20 mA signals with simultaneous 16-bit conversion for the X20 System.
In Stock
Ships by Wednesday, October 28
Fast Shipping Available
Get a quick price for X20AI2632
Quantity
*E-mail
Company
*Mobile
*Content
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)

Technical specifications for X20AI2632

  • Manufacturer:
    B&R
  • Part Number:
    X20AI2632
  • Product Family:
    B&R X20 System
  • Product Type:
    High-Speed Analog Input Module
  • Stock:
    1
  • Analog inputs:
    2 differential inputs
  • Input ranges:
    ±10 V or 0 to 20 mA
  • Digital converter resolution:
    Voltage ±15-bit; current 15-bit
  • Conversion time:
    50 µs for all inputs
  • Conversion behavior:
    Simultaneous input conversion
  • Voltage input impedance:
    20 MΩ
  • Current input load:
    Less than 400 Ω
  • Permissible input signal:
    Maximum ±30 V or ±50 mA
  • Input filter:
    Third-order low-pass, 10 kHz cutoff
  • Common-mode range:
    ±12 V
  • Voltage nonlinearity:
    Less than 0.01%
  • Current nonlinearity:
    Less than 0.015%
  • Required terminal block:
    X20TB06 or X20TB12, ordered separately
  • Compatible bus modules:
    X20BM11 or X20BM15, ordered separately
  • Degree of protection:
    IP20
  • Dimensions:
    1.25 × 5.3 × 9.8 cm
  • Tariff Code:
    8538900000
  • Country of origin:
    Germany
  • Place of shipment:
    ​Xiamen, Fujian, China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals Sampling Signal Setup Diagnostics Application
  • Simultaneously converts two differential analog channels
  • Accepts ±10 V or 0 to 20 mA through signal-specific terminals
  • Provides 16-bit conversion in 50 microseconds with a 10 kHz hardware filter

X20AI2632 is a B&R high-speed analog input module designed for X20 System I/O stations.

The module brings two fast analog process or machine signals into the X20 station with common conversion timing and software-visible diagnostics.

Before installation or replacement, verify the complete material number, voltage or current mode, terminal assignment, source characteristics, common-mode voltage, sampling requirements, scaling, X20TB06 or X20TB12, X20BM11 or X20BM15, and controller timing.

Availability, condition, price, and shipping time for X20AI2632 are confirmed during quotation.

B&R X20AI2632 High-Speed Analog Input Module Manuals, Datasheets, Links

Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.

  • Both channels are converted simultaneously
  • The documented conversion time is 50 microseconds for all inputs
  • Controller task timing must be coordinated with the required acquisition rate
  • Voltage and current inputs use different terminal assignments
  • Software channel type and engineering-unit scaling must match the wired signal
  • The 10 kilohertz hardware filter defines the analog input bandwidth
  • Undershoot and overshoot use signal-specific documented digital values
  • Inputs include protection against accidental wiring with supply voltage
  • Channel indicators and software support fault localization during commissioning
  • Fast ±10 V feedback acquisition in machine-control systems
  • High-speed 0 to 20 mA process-signal measurement
  • Simultaneous two-channel analog capture in distributed X20 I/O
Description
X20AI2632 is a B&R high-speed analog input module for the X20 System distributed I/O platform.

It simultaneously converts two differential voltage or current inputs in 50 microseconds with 16-bit resolution, signal-specific terminals, and a 10 kHz hardware input filter.

Before installation or replacement, confirm the complete material number, voltage or current mode, terminal assignment, source characteristics, common-mode voltage, sampling requirements, scaling, X20TB06 or X20TB12, X20BM11 or X20BM15, and controller timing.
Alternative Names
X20AI2632 X20 AI 2632 X20-AI2632 B&R X20AI2632 BR X20AI2632 B&R X20 AI 2632 X20 System X20AI2632
Technical notes
X20AI2632 simultaneously converts two channels in 50 microseconds; verify voltage or current terminals, loop power, common-mode range, 10 kHz hardware filtering, scaling, X20TB06 or X20TB12, and task timing before replacement.
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
When is B&R X20AI2632 preferable to a standard-speed analog input?
Use it when two channels must be sampled simultaneously with a documented 50 microsecond conversion time and the process bandwidth justifies the faster hardware.
Can B&R X20AI2632 measure 4 to 20 mA directly?
Its official range is stated as 0 to 20 mA. A 4 to 20 mA signal lies inside that range, but scaling and fault detection must be implemented appropriately in the controller project.
How is signal mode selected on B&R X20AI2632?
Connect the signal to the correct voltage or current terminals and configure matching channel type and scaling in Automation Studio.
Are B&R X20AI2632 channels individually isolated?
No. The pair is isolated from the bus, but the two channels are not isolated from one another.
What can cause clipping on B&R X20AI2632?
Excess signal amplitude, wrong terminal assignment, reversed current-loop polarity, common-mode voltage outside range, or incorrect software mode can force undershoot or overshoot values.
Which terminal blocks can be used with B&R X20AI2632?
B&R documents X20TB06 or X20TB12, together with an X20BM11 or X20BM15 bus module.
What should be recorded before replacing B&R X20AI2632?
Record signal mode, terminals, scaling, sample timing, filter assumptions, loop power, grounding, fault handling, accessories, and project configuration.