1001 reviews | Need a Specific Revision?
B&R X20AT4222 is a four-channel Pt100 and Pt1000 resistance-temperature input module with configurable sensor type, wiring mode, and filter time for the X20 System.
In Stock
Ships by Wednesday, October 28
Fast Shipping Available
Get a quick price for X20AT4222
Quantity
*E-mail
Company
*Mobile
*Content
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)

Technical specifications for X20AT4222

  • Manufacturer:
    B&R
  • Part Number:
    X20AT4222
  • Product Family:
    B&R X20 System
  • Product Type:
    Temperature Input Module
  • Stock:
    1
  • Temperature inputs:
    4 resistance-measurement inputs
  • Supported sensors:
    Pt100 and Pt1000, configurable per channel
  • Temperature range:
    -200 to 850 °C
  • Temperature resolution:
    0.1 °C
  • Connection type:
    2- or 3-wire, configurable per module
  • Direct resistance measurement:
    Supported
  • Digital converter resolution:
    16-bit
  • Filter time:
    Configurable from 1 to 66.7 ms
  • Conversion time:
    1 channel: 20 ms with 50 Hz filter; 2 to 4 channels: 40 ms per channel with 50 Hz filter
  • Resistance measurement ranges:
    0.1 to 4500 Ω or 0.05 to 2250 Ω
  • Open-circuit monitoring:
    Temperature value 0x7FFF; resistance value 0xFFFF
  • Electrical isolation:
    Channel isolated from bus; channels not isolated from one another
  • Required terminal block:
    X20TB12, ordered separately
  • Compatible bus modules:
    X20BM11 or X20BM15, ordered separately
  • Degree of protection:
    IP20
  • Operating temperature:
    -25 to 60 °C horizontal; -25 to 50 °C vertical
  • Dimensions:
    1.25 × 5.3 × 9.8 cm
  • Tariff Code:
    8538900000
  • Country of origin:
    Germany
  • Place of shipment:
    ​Xiamen, Fujian, China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals Sensor Setup Fault Values Timing Application
  • Measures four Pt100 or Pt1000 resistance-temperature channels
  • Supports direct resistance measurement with 16-bit sigma-delta conversion
  • Provides configurable filtering and explicit open-circuit fault values

X20AT4222 is a B&R temperature input module designed for X20 System I/O stations.

The module converts four resistance-temperature channels into controller values while allowing sensor type selection per channel and a module-level choice of 2- or 3-wire connection mode.

Before installation or replacement, verify the complete material number, Pt100 or Pt1000 sensor type, 2- or 3-wire mode, lead resistance, filter time, conversion timing, scaling, terminal and bus modules, and grounding.

Availability, condition, price, and shipping time for X20AT4222 are confirmed during quotation.

B&R X20AT4222 Temperature Input Module Manuals, Datasheets, Links

Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.

  • Pt100 or Pt1000 sensor type is configured independently for each channel
  • The choice between 2-wire and 3-wire connection is configured for the complete module
  • Internal linearization follows the documented EN 60751 sensor characteristic
  • An open temperature input is reported with the documented 0x7FFF value
  • An open resistance-measurement input is reported with the documented 0xFFFF value
  • Range and general-fault values must be handled explicitly in the controller application
  • Filter time is configurable from 1 to 66.7 milliseconds
  • Conversion time depends on the number of enabled channels and the selected filter
  • Unused channels and response-time requirements should be considered when configuring acquisition
  • Pt100 temperature acquisition in X20 machine-control stations
  • Pt1000 process-temperature measurement in distributed I/O systems
  • Direct resistance measurement in standard fieldbus control applications
Description
X20AT4222 is a B&R temperature input module for the X20 System distributed I/O platform.

It measures Pt100, Pt1000, or direct resistance signals with 16-bit conversion, internal linearization, configurable filtering, and open-circuit monitoring.

Before installation or replacement, confirm the complete material number, Pt100 or Pt1000 sensor type, 2- or 3-wire mode, lead resistance, filter time, conversion timing, scaling, terminal and bus modules, and grounding.
Alternative Names
X20AT4222 X20 AT 4222 X20-AT4222 B&R X20AT4222 BR X20AT4222 B&R X20 AT 4222 X20 System X20AT4222
Technical notes
X20AT4222 selects Pt100 or Pt1000 per channel but configures 2- or 3-wire mode for the module; verify sensor wiring, lead resistance, filter time, scaling, X20TB12, and X20BM11 or X20BM15 before replacement.
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
Can B&R X20AT4222 mix Pt100 and Pt1000 sensors?
Yes. Sensor type is configurable per channel, so Pt100 and Pt1000 selections can be assigned according to the project configuration.
Can B&R X20AT4222 mix 2-wire and 3-wire sensors on one module?
The wiring mode is configured per module, not per channel. Plan the four connected sensors around one validated 2-wire or 3-wire arrangement.
How does B&R X20AT4222 indicate a broken sensor wire?
The module returns the documented open-circuit fault value. The controller program should distinguish that value from valid temperature or resistance data.
How should lead resistance be handled with B&R X20AT4222?
Use the appropriate wiring method, preferably the validated 3-wire arrangement when lead compensation is needed, and verify conductor symmetry and terminal connections.
Why does the response time of B&R X20AT4222 change with configuration?
Conversion time depends on enabled-channel count and filter time. Choose filtering that balances noise rejection and the required control response.
Which accessories are required for B&R X20AT4222?
Order one X20TB12 terminal block and a compatible X20BM11 or X20BM15 bus module separately.
What should be saved before replacing B&R X20AT4222?
Record each channel's sensor type, the module wiring mode, filter time, scaling, fault-value handling, terminal mapping, and Automation Studio hardware configuration.