Technical specifications for X20DO2623

  • Manufacturer:
    B&R
  • Part Number:
    X20DO2623
  • Product Family:
    B&R X20 System
  • Product Type:
    Digital SSR Output Module
  • Stock:
    1
  • Digital outputs:
    2
  • Output variant:
    SSR with zero-cross switching
  • Output circuit:
    L-switching
  • Nominal voltage:
    100 to 240 VAC
  • Maximum voltage:
    264 VAC
  • Rated frequency:
    47 to 63 Hz
  • Nominal output current:
    1 A per channel
  • Surge current:
    40 A for 20 ms; 10 A for 1 s
  • Connection type:
    3-wire connections
  • Switching delay:
    At 50 Hz: ≤11 ms; at 60 Hz:≤9.3 ms
  • Off-state leakage current:
    Maximum 10 mA at 240 V
  • Internal protective circuit:
    Snubber circuit (RC element)
  • External protective circuit:
    Generally a varistor or fuse
  • Electrical isolation:
    Channel isolated from bus and I/O power supply; tested at 2500 VAC
  • Required terminal block:
    X20TB32, ordered separately
  • Required bus module:
    X20BM12, ordered separately
  • Degree of protection:
    IP20
  • Operating temperature:
    -25 to 60 °C horizontal; -25 to 50 °C vertical
  • Dimensions:
    1.25 × 5.3 × 9.8 cm
  • Tariff Code:
    8538900000
  • Country of origin:
    Germany
  • Place of shipment:
    ​Xiamen, Fujian, China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals AC Switching Protection Installation Application
  • Provides two zero-cross SSR outputs for 100 to 240 VAC field loads
  • Uses L-switching 3-wire connections with the AC supply fed directly to the module
  • Includes an internal snubber circuit, full-wave control, and 240 V mechanical coding

X20DO2623 is a B&R digital ssr output module designed for X20 System I/O stations.

The supply conductors L and N are connected directly to the module, which switches the two AC field loads while the X20 bus carries control and status information.

Before installation or replacement, verify the complete material number, the 100 to 240 VAC supply, load type, surge current, external protection, 240 V coding, X20TB32 terminal block, X20BM12 bus module, and installation conditions.

Availability, condition, price, and shipping time for X20DO2623 are confirmed during quotation.

B&R X20DO2623 Digital SSR Output Module Manuals, Datasheets, Links

Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.

  • Zero-cross switching is provided for documented 50 or 60 hertz AC loads
  • The two outputs share a total nominal current limit of 1 ampere
  • L-to-N supply voltage is not monitored by the module
  • An internal RC snubber circuit is integrated in each SSR output path
  • B&R specifies external protection generally using a varistor or fuse
  • Load surge current must remain within the documented short-duration limits
  • X20TB32 provides the required 12-pin 240 VAC-keyed terminal connection
  • X20BM12 provides the required 240 VAC-keyed X20 bus-module connection
  • Installation above 2000 meters is not permitted for this module
  • Zero-cross switching of documented 100 to 240 VAC field loads in X20 control stations
  • Distributed AC output expansion connected to standard fieldbus control systems
  • Machine-control output stations requiring compact two-channel solid-state switching
Description
X20DO2623 is a B&R digital ssr output module for the X20 System distributed I/O platform.

It provides two L-switching SSR outputs with zero-cross switching, integrated full-wave control, and an internal snubber circuit for documented AC loads.

Before installation or replacement, confirm the complete material number, the 100 to 240 VAC supply, load type, surge current, external protection, 240 V coding, X20TB32 terminal block, X20BM12 bus module, and installation conditions.
Alternative Names
X20DO2623 X20 DO 2623 X20-DO2623 B&R X20DO2623 BR X20DO2623 B&R X20 DO 2623 X20 System X20DO2623
Technical notes
X20DO2623 switches 100 to 240 VAC loads and does not monitor L-to-N voltage; verify supply isolation, external fuse or varistor protection, load surge current, 240 V coding, X20TB32, and X20BM12 before installation.
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
Can B&R X20DO2623 switch DC loads?
No. X20DO2623 is specified for 100 to 240 VAC operation with L-switching SSR outputs. Select a documented DC output module for DC loads.
Which base components must be ordered for B&R X20DO2623?
Order the 240 VAC-keyed X20TB32 terminal block and X20BM12 bus module separately from the electronic module.
Why is external protection still needed with B&R X20DO2623?
The internal RC snubber supports the SSR output, but B&R also specifies external protection, generally a varistor or fuse, selected for the connected load and circuit.
How should high-inrush loads be checked for B&R X20DO2623?
Compare the load's starting current and duration with the module's surge-current limits and its shared total-current limit before commissioning.
Will B&R X20DO2623 report a missing AC supply?
No. The module does not provide L-to-N voltage monitoring, so loss of field power must be detected elsewhere if the application requires it.
What wiring safety checks matter for B&R X20DO2623?
Verify isolation, protective devices, L and N terminal assignment, 240 V coding, conductor ratings, enclosure protection, and de-energized working procedures.
What should be recorded before replacing B&R X20DO2623?
Record the complete material number, load type, AC frequency, output assignments, protection components, terminal and bus modules, and Automation Studio hardware configuration.