SE4304T01 KL3022X1-BA1

/ 4.9
1001 reviews | Need a Specific Revision?
Emerson SE4304T01 KL3022X1-BA1 is a DeltaV AO 4–20 mA HART CHARM for analog control output and HART communication in Electronic Marshalling.
In Stock
Ships by Wednesday, October 28
Fast Shipping Available
Get a quick price for SE4304T01 KL3022X1-BA1
Quantity
*E-mail
Company
*Mobile
*Content
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)

Technical specifications for SE4304T01 KL3022X1-BA1

  • Manufacturer:
    Emerson
  • Part Number:
    SE4304T01 KL3022X1-BA1
  • Product Family:
    DeltaV
  • Product Type:
    AO 4–20 mA HART CHARM
  • Stock:
    1
  • Signal Type:
    4–20 mA output with HART
  • Channels:
    1
  • Module Type:
    CHARM
  • CHARM Bus Power:
    6.3 VDC at 32 mA
  • Field Circuit:
    24 VDC at 30 mA
  • Terminal Key:
    4A
  • Ambient Temperature:
    -40°C to +70°C
  • Storage Temperature:
    -40°C to +85°C
  • Relative Humidity:
    5% to 95%, non-condensing
  • Shock:
    10 g for 11 ms
  • Vibration:
    1 mm p-p to 13.2 Hz; 0.7 g to 150 Hz
  • Airborne Contaminants:
    ISA-S71.04 Class G3
  • Protection Rating:
    IP20
  • Calibration:
    Not required
  • User-Serviceable Parts:
    None
  • Tariff Code:
    Please confirm the destination before shipping
  • Country of origin:
    USA
  • Place of shipment:
    Xiamen,Fujian,China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals Output Interface Power and Keying Service Limits Product Applications

Features:

  • 4–20 mA analog-output control with HART communication
  • Individual CHARM channel function for flexible Electronic Marshalling
  • 4A terminal keying with no calibration requirement
SE4304T01 KL3022X1-BA1 provides one DeltaV Electronic Marshalling output channel for a compatible 4–20 mA final-control device.

HART communication supports device identification and diagnostics while the analog current carries the commanded process output.

The keyed CHARM format supports controlled channel replacement when bus power, field power, terminal fit and hazardous-location rules are verified.

For SE4304T01 KL3022X1-BA1 AO 4–20 mA HART CHARM sourcing, Apter Power can help confirm the Emerson model, terminal key and installed DeltaV architecture.
Emerson SE4304T01 KL3022X1-BA1 AO 4–20 mA HART CHARM Manuals,Datasheets,Link
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
  • Output signal: One 4–20 mA analog-output channel.
  • Device protocol: HART communication is supported for compatible devices.
  • Field circuit: Rated for 24 VDC at 30 mA.
  • CHARM bus: Uses 6.3 VDC at 32 mA.
  • Terminal key: Requires the 4A keyed position.
  • Module scope: No user-serviceable parts are provided.
  • Ambient range: -40°C to +70°C.
  • Enclosure boundary: IP20 equipment requires a suitable cabinet.
  • Maintenance: Periodic calibration is not required.
  • Hazardous locations: Follow the approved DeltaV installation procedure.
  • Final-control output: Commands compatible 4–20 mA actuators and positioners.
  • HART maintenance: Retains device identification and diagnostics.
  • Electronic Marshalling: Supports flexible channel-by-channel cabinet engineering.
Description
SE4304T01 KL3022X1-BA1 provides one 4–20 mA analog-output channel with HART communication for compatible final-control devices. The CHARM architecture assigns the signal function at the individual channel, supporting flexible Electronic Marshalling cabinet designs and straightforward late-stage I/O changes.

SE4304T01 KL3022X1-BA1 uses 4A terminal keying and operates from the CHARM bus plus the specified 24 VDC field circuit. It requires no calibration and has no user-serviceable parts, so replacement planning should confirm the exact order code, keyed terminal, output loop and hazardous-area procedure.
Alternative Names
KL3022X1-BA1 KL3022X1 BA1 KL3022X1BA1 SE4304T01 Emerson SE4304T01 KL3022X1-BA1 DeltaV AO 4–20 mA HART CHARM
Technical notes
Before installing SE4304T01 KL3022X1-BA1, verify 4A terminal keying, CHARM bus power and the 24 VDC output circuit. The module requires no calibration and has no user-serviceable parts. Confirm loop polarity and enclosure protection. In hazardous locations, de-energize or confirm a nonhazardous atmosphere before insertion, removal or field-wiring changes.
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
What output does SE4304T01 KL3022X1-BA1 provide?
It provides one 4–20 mA analog output and supports HART communication with a compatible final-control device.
Which terminal key is required for SE4304T01 KL3022X1-BA1?
Use the 4A keyed terminal position and confirm the CHARM carrier before insertion.
Does SE4304T01 KL3022X1-BA1 need periodic calibration?
No. The CHARM requires no calibration and contains no user-serviceable parts.
What power checks apply to SE4304T01 KL3022X1-BA1?
Confirm 6.3 VDC CHARM bus power and the specified 24 VDC output field circuit.
Can SE4304T01 KL3022X1-BA1 be wired in an energized hazardous area?
Follow the applicable DeltaV hazardous-location instruction and isolate energy unless the approved procedure permits the work.
What should an RFQ for SE4304T01 KL3022X1-BA1 include?
State the complete order and hardware identity, quantity, installed carrier, 4A terminal key and destination.
How should the output loop be checked after installing SE4304T01 KL3022X1-BA1?
Verify commanded current, HART communication and final-control response before returning the loop to automatic operation.