Features:
- Compares one thermocouple input with two independently adjustable alarm setpoints.
- Provides one SPDT relay output for each setpoint.
- Accepts a 9–30 V DC isolated supply with 2.5 W maximum consumption.
- Operates from 0 to 55 °C and stores from −15 to 70 °C.
Eurotherm G128-0001 uses one temperature input to operate two independent limit decisions.
The two SPDT relays let separate external circuits respond to the lower and upper configured thresholds.
Adjustable deadband stabilizes each output when the measured signal remains near its switching point.
The Eurotherm G128-0001 Dual-Setpoint Thermocouple Input Limit Alarm may still be available through Apter Power after OEM discontinuation.
Eurotherm G128-0001 Dual-Setpoint Thermocouple Input Limit Alarm Manuals,Datasheets,Link
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
How one sensor drives two alarm decisions
- Thermocouple input: One thermocouple signal enters the alarm module.
- First setpoint: Setpoint 1 controls the first SPDT relay.
- Second setpoint: Setpoint 2 controls the second SPDT relay.
- Deadband: Each switching decision can be stabilized near its threshold.
Contact capabilities for external circuits
- At 120 V AC: Each relay is rated 5 A resistive.
- At 240 V AC: Each relay is rated 2 A resistive.
- At 28 V DC: Each relay is rated 5 A resistive.
- Contact form: Two SPDT relays provide changeover outputs.
Electrical separation and supply loading
- Supply window: The module accepts 9–30 V DC.
- Typical load: Power consumption is 1.5 W under typical conditions.
- Maximum load: The documented maximum is 2.5 W.
- Isolation: Contacts, input, and power are separated by 1800 V DC isolation.
Environmental limits for the installed alarm
- Operating range: Maintain the module between 0 and 55 °C.
- Storage range: Unpowered storage is permitted from −15 to 70 °C.
- Operating humidity: The limit is 15–95% at 45 °C without condensation.
- Humidity soak: The module withstands 90% for 24 h at 65 °C without condensation.