Features:
- Powers a Series Three remote I/O base from either 115 VAC or 230 VAC.
- Keeps the remote station's backplane source separate from the supply fitted to the CPU base.
- Provides high-capacity allocations on both Series Three backplane rails.
IC630PWR320 is selected by station role as well as by input voltage: it is the AC unit for a remote I/O base, not the local processor rack.
The remote cabinet receives its own supply, and the terminal-board arrangement adapts that supply to the available AC line.
Module demand is calculated for the population of the remote base so that its two rail totals are checked independently.
Current purchasing enquiries for the General Electric IC630PWR320 AC remote I/O base power supply may be directed to Apter Power under its active OEM lifecycle classification.
General Electric IC630PWR320 High-Capacity Remote I/O Base Power Supply Manuals,Datasheets,Link
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
Separating remote-station power from the CPU rack
- Assigned station: IC630PWR320 is designated for a Series Three remote I/O base.
- Local contrast: The matching high-capacity AC supply for the processor base is IC630PWR310.
- Independent source: Every remote base receives power from the supply installed in that station.
- Backplane destination: The unit feeds the remote base electronics and installed modules rather than the CPU rack.
Adapting the remote cabinet to its AC feed
- Two line options: The same IC630PWR320 can be connected for either 115 VAC or 230 VAC service.
- Terminal setting: The terminal-board arrangement establishes which of the two input voltages is applied.
- Frequency: The accepted AC source operates at 50/60 Hz.
- Before energizing: Line voltage and terminal selection must agree at the remote location.
Using the supply-state outputs
- RUN contact: The RUN circuit provides an external indication of normal supply operation.
- FAULT contact: A separate contact reports the supply fault state.
- Remote visibility: These contacts allow a distant cabinet to return power-condition information to supervisory wiring.
- Interpretation: A reported supply fault is separated from individual I/O point status in the remote base.
Evaluating the remote-base module population
- Station scope: Only the modules assigned to this remote base enter its power calculation.
- Separate rails: The +5 V and +12 V loads are totaled independently.
- Published units: Each installed module contributes the load units listed for the rail it uses.
- Capacity check: The completed remote-station totals are compared with the IC630PWR320 allocations before the base is accepted.