Features:
- Triple-phase voltage sensing combined with precise digital frequency tracking.
- Wide-range auxiliary power unit supporting 110–250 Vdc and 110–230 Vac operation.
- Withdrawable 1/4 19-inch 4U chassis housed in a 304 stainless steel enclosure.
The GE Multilin MIVII3000E00HI00 ordering option features a 10–250 Vac measuring input range, English front panel interface, and a high-voltage auxiliary power module without conformal coating.
Engineered for automated power system protection, this unit provides real-time under/overvoltage and frequency supervision across generators, busbars, and industrial feeders.
During cabinet installation, ensure proper jumper JX configuration when isolating output relay contacts, and maintain adequate clearance for the drawout chassis.
Availability, condition, price, and shipping time for MIVII3000E00HI00 are confirmed during quotation.
GE Multilin MIVII3000E00HI00 Protection Relay Manuals, Datasheets, Link
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
- Automatic transfer systems requiring continuous line voltage and frequency monitoring.
- Synchronous generator protection against islanding, load shedding, and grid disconnection.
- Substation busbar protection schemes for rapid secondary voltage fault isolation.
- Rear panel RS485 two-wire serial interface supporting standard Modbus RTU protocol.
- Front panel RS232 port dedicated to local PC software commissioning and parameter setup.
- Selectable serial communication baud rates ranging from 300 bps to 19,200 bps.
- Integrated non-volatile memory storing up to 24 millisecond-tagged historical event logs.
- Oscillography function capturing 24-cycle fault waveforms at 8 samples per power cycle.
- Six output contacts including one dedicated Form-C fail-safe hardware alarm relay.
- IP52 / NEMA 12 rated dust-resistant front panel for industrial switchgear cabinet mounting.
- Wide operating temperature range from -20 °C to +60 °C (-4 °F to +140 °F).
- Dielectric insulation testing up to 2.0 kV AC for 1 minute compliant with IEC 60255-5.