General Electric IC755CKW07CDM is a 7-inch QuickPanel+ configuration with integrated RSTi Modbus TCP connectivity for distributed I/O.
In Stock
Ships by Wednesday, October 28
Fast Shipping Available
Get a quick price for IC755CKW07CDM
Quantity
*E-mail
Company
*Mobile
*Content
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)

Technical specifications for IC755CKW07CDM

  • Manufacturer:
    General Electric
  • Part Number:
    IC755CKW07CDM
  • Product Family:
    GE QuickPanel
  • Product Type:
    QuickPanel+ 7-inch Screen with RSTi Modbus TCP
  • Stock:
    1
  • Processor:
    Freescale i.MX535, 1 GHz ARM Cortex-A8
  • Memory:
    1 GB DDR3 SDRAM; 512 MB SLC NAND Flash; 512 KB battery-backed SRAM
  • Display:
    7-inch TFT LCD, 800 x 480, projected-capacitive two-point touch
  • I/O Integration:
    RSTi Modbus TCP
  • Ethernet:
    2 x 10/100Base-T RJ-45
  • Serial I/O:
    1 x RS-232 and 1 x RS-485
  • Power:
    12/24 VDC ±20%; 30 W maximum
  • Operating Temperature:
    0 to 55 °C
  • Panel Cutout:
    183.5 x 128.5 mm
  • Weight:
    1.764 lbs (0.8 kg)
  • Estimated shipping dimensions:
    192 x 137 x 36 mm
  • Tariff Code:
    8537101190
  • Country of origin:
    United States
  • Place of shipment:
    Xiamen,Fujian,China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals Communication Configuration Diagnostics Applications

Features:

  • 7-inch 800 x 480 projected-capacitive operator display
  • Integrated RSTi Modbus TCP distributed-I/O connectivity
  • QuickPanel+ control, gateway, browser, and visualization resources
IC755CKW07CDM is the 7-inch QuickPanel+ ordering configuration that combines the widescreen panel with RSTi Modbus TCP.

The device can present operator graphics while exchanging process data with distributed RSTi I/O and other supported automation equipment.

Successful integration depends on the correct Modbus TCP node settings, register map, Ethernet topology, panel cutout, power supply, and stored application.

The General Electric IC755CKW07CDM QuickPanel+ 7-inch Screen with RSTi Modbus TCP is available for quotation, official documentation, and configuration support from Apter Power.
General Electric IC755CKW07CDM QuickPanel+ 7-inch Screen with RSTi Modbus TCP Manuals, Datasheets, Links Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.

RSTi and network data paths

  • RSTi link: Modbus TCP carries process data between the panel and compatible RSTi distributed I/O.
  • Dual Ethernet: Two 10/100Base-T ports support controller, I/O, and plant-network arrangements.
  • Serial access: RS-232 and RS-485 ports remain available for supported serial devices.
  • Data mapping: Register addresses, word order, data types, and update timing must match the RSTi configuration.

Network and I/O setup

  • IP plan: Assign unique addresses and verify subnet and switch settings before enabling communications.
  • Module layout: Configure the actual RSTi station order and data lengths used in the field.
  • Fault behavior: Define operator indications for lost nodes, invalid data, and communication timeouts.
  • Project archive: Store the QuickPanel+ project and the matching RSTi configuration together for recovery.

Commissioning checks

  • Link status: Confirm Ethernet link activity and stable Modbus TCP sessions.
  • I/O validation: Exercise each input and output point against the approved channel map.
  • Alarm handling: Verify that communication loss and module faults reach the operator display.
  • Service records: Record IP addresses, firmware levels, station layout, and tested register ranges.

Distributed-I/O operator projects

  • Remote I/O panels: IC755CKW07CDM combines a seven-inch interface with RSTi Modbus TCP connectivity for distributed-I/O stations.
  • Modular machines: The compact panel can provide local visualization for machine sections built around supported Ethernet I/O.
  • Cell-level operation: Multi-touch graphics and controller communication support operator access at individual automation cells.
  • Networked equipment: Ethernet connectivity allows supported device data and commands to be integrated into the panel application.
Description
IC755CKW07CDM pairs a 7-inch 800 x 480 projected-capacitive operator display with the RSTi Modbus TCP configuration identified in the QuickPanel+ ordering range. The platform provides responsive multi-touch visualization through its 1 GHz ARM processor and DDR3 memory.

In addition to local operator functions, IC755CKW07CDM can exchange data through dual Ethernet links, RS-232, RS-485, USB, and removable SD/SDHC storage. The RSTi Modbus TCP arrangement supports distributed I/O integration while retaining QuickPanel+ browser, control, and gateway capabilities.

When fitting IC755CKW07CDM, match the panel cutout, 12/24 VDC supply, Ethernet addressing, RSTi node configuration, and Modbus register mapping to the existing installation. Cooling is by natural convection, and the sealed front depends on correct gasket compression.
Alternative Names
IC755 CKW 07 CDM IC755-CKW-07-CDM GE IC755CKW07CDM General Electric IC755CKW07CDM GE RSTi IC755CKW07CDM IC755CKWO7CDM 1C755CKW07CDM IC755CKW07 CDM
Technical notes
IC755CKW07CDM combines QuickPanel+ visualization with RSTi Modbus TCP integration, allowing distributed I/O data and operator functions on one Ethernet platform.
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
How should IC755CKW07CDM be linked to an RSTi Modbus TCP station?
Connect IC755CKW07CDM through Ethernet, assign compatible IP and subnet settings, then configure the RSTi Modbus TCP node and register map used by the application.
What should be checked if touch targets do not align on IC755CKW07CDM?
For IC755CKW07CDM, confirm that the project was designed for the 800 x 480 display and that its projected-capacitive two-point touch objects are positioned correctly.
Why can field data appear in the wrong locations after IC755CKW07CDM connects to RSTi I/O?
IC755CKW07CDM depends on the configured register map, data types, and physical RSTi module order; a mismatch can shift or reinterpret the exchanged values.
How can serial field devices be integrated with IC755CKW07CDM?
IC755CKW07CDM provides RS-232 and RS-485 interfaces, so use the supported driver and match each device's wiring, baud rate, parity, address, and termination.
What mechanical checks apply when IC755CKW07CDM replaces another panel?
IC755CKW07CDM uses a 183.5 x 128.5 mm cutout; verify enclosure depth, mounting-bracket engagement, gasket condition, connector access, and cable clearance.
Which acceptance tests are required after commissioning IC755CKW07CDM?
Commission IC755CKW07CDM by testing RSTi input and output data, operator commands, alarms, network recovery, serial devices, user access, and application navigation.
How should enclosure cooling be arranged for IC755CKW07CDM?
IC755CKW07CDM relies on natural convection, so maintain the required clearances and keep the enclosure within the specified 0 to 55 °C operating range.