Features:
- IC600BF914 provides six isolated Form C relay outputs.
- Each channel selects a normally open or closed idle state.
- Individual fuses and LEDs protect and indicate all six relays.
IC600BF914 supplies six electrically isolated relay-contact outputs for switching user AC or DC loads from a Series Six Plus control system.
Each circuit can be configured for normally-open or normally-closed de-energized operation, and its RC protection network can be included or bypassed with board jumpers.
The contacts are rated up to 240 VAC/DC, 100 VA, and 2 A continuous resistive current, while each circuit includes a dedicated fuse and coil-status indicator.
Apter Power can quote and source the General Electric IC600BF914 Reed Relay Output Module, provide the applicable manufacturer documentation, and assist with contact, protection-jumper, and replacement configuration.
General Electric IC600BF914 Reed Relay Output Module Manuals, Datasheets, Links
Rack and relay-load compatibility
- Rack location: IC600BF914 can be used in an I/O rack, a Model 60 CPU rack, or a Series Six Plus CPU rack.
- Reference allocation: The backplane DIP switch assigns six consecutive output references to the module.
- Contact type: Six Form C circuits allow normally-open or normally-closed de-energized operation.
- Load range: The contacts support AC or DC loads within the documented 240 V, 100 VA, and 2 A limits.
Relay-module environmental limits
- Operating temperature: The specified range is 0 to 60 °C at the outside of the rack.
- Storage temperature: The manufacturer lists −20 to +80 °C.
- Relative humidity: IC600BF914 is rated for 5 to 95% non-condensing humidity.
- Orientation: The module must be installed vertically in a right-side-up rack for correct relay operation.
Monitoring the six relay outputs
- Coil indication: One LED per circuit turns on when the corresponding relay coil is energized.
- Scan updates: The Series Six Plus CPU updates all six outputs during an I/O scan.
- Point identification: The markable lens area lets technicians record each output’s assigned load.
- Reference check: Coil indication can be compared with the six consecutive controller output references.
Contact isolation and output protection
- Individual fuses: Each relay output has a dedicated 3 A normal-blow fuse.
- Contact isolation: The manufacturer specifies a 1500 V test between field circuits and Series Six Plus logic.
- RC network: A per-circuit jumper includes or bypasses the 68 Ω and 0.012 µF protection network.
- Low-level signals: Bypassing the RC network supports appropriate low-level analog or instrumentation applications.