HONEYWELL-8C-PAOH51-51454355-175
HONEYWELL-8C-PAOH51-51454355-175
HONEYWELL-8C-PAOH51-51454355-175
HONEYWELL-8C-PAOH51-51454355-175
HONEYWELL-8C-PAOH51-51454355-175
HONEYWELL-8C-PAOH51-51454355-175
Ask our team:
  • Phone: +86 181 0690 9650
  • E-Mail sales1@apterpower.com
How We Verify Your Order
Before dispatch, we confirm the exact model, revision, condition, inspection requirements and shipping documents for your order.
See a real on-site verification case >>
  • Lifecycle status

    Active / Available from OEM
    Apter Power provides quotations, technical documentation and HART-loop configuration support for this Honeywell analog output module.

8C-PAOH51 51454355-175

/ 4.9
1001 reviews | Need a Specific Revision?
Honeywell 8C-PAOH51 51454355-175 is a coated Series 8 analog output module with 16 HART-enabled 4-20 mA channels, configurable safe-state behavior and optional redundancy.
In Stock
Ships by Tuesday, November 10
Fast Shipping Available
Get a quick price for 8C-PAOH51 51454355-175
Quantity
*E-mail
Company
*Mobile
*Content
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)

Technical specifications for 8C-PAOH51 51454355-175

  • Manufacturer:
    Honeywell
  • Part Number:
    8C-PAOH51 51454355-175
  • Product Family:
    Honeywell Experion PKS ( C200, C300 )
  • Product Type:
    Analog Output with HART Module
  • Stock:
    1
  • Output channels:
    16
  • Output type:
    4-20 mA with HART
  • Settable output current:
    0 mA or 2.9-21.1 mA
  • Maximum open-circuit voltage:
    22 V
  • Response time:
    Within 1% of final value in 80 ms
  • Compatible IOTAs:
    8C-TAOX51 nonredundant; 8C-TAOX61 redundant
  • Weight:
    0.3 kg
  • Estimated shipping dimensions:
    6x15.6x14.3cm
  • Tariff Code:
    Please confirm the destination before shipping
  • Country of origin:
    USA
  • Place of shipment:
    Xiamen,Fujian,China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals Output Channels Diagnostics IOTA Setup Applications

Features:

  • Sixteen 4-20 mA analog output channels with HART communication.
  • Open-wire diagnostics and configurable per-channel safe-state behavior.
  • Nonredundant or redundant Series 8 installation through the matching IOTA.
8C-PAOH51 51454355-175 provides high-level constant-current outputs for compatible final-control devices and supports HART digital communication on the same field loops.

8C-PAOH51 51454355-175 can report open field wiring and apply a configured hold-last or shed-to-safe-value response when a channel or module fault is detected.

8C-PAOH51 51454355-175 is paired with 8C-TAOX51 for nonredundant service or 8C-TAOX61 for redundant service; the installed IOTA and project configuration determine the final arrangement.

8C-PAOH51 51454355-175 Honeywell Analog Output with HART Module documentation and configuration-matching support are available from Apter Power.
Honeywell 8C-PAOH51 51454355-175 Analog Output with HART Module Manuals,Datasheets,Link
  • Sixteen independently commanded output channels are provided.
  • Each channel supports a standard 4-20 mA signal with HART communication.
  • The directly settable range is 0 mA or 2.9 mA to 21.1 mA.
  • Maximum open-circuit voltage is 22 V.
  • Open field wiring can be reported as a channel diagnostic.
  • Each channel can hold its last value or shed to a configured safe value.
  • Output response settles within 1% of final value in 80 ms.
  • Maintenance planning must account for loss of normal output control while the IOM is absent.
  • 8C-TAOX51 is the coated nonredundant IOTA for this module.
  • 8C-TAOX61 is the coated redundant IOTA for this module.
  • The redundant output gap is specified at 10 ms maximum during switchover.
  • IOTA model, field-loop load and Experion configuration must be checked together.
  • Commanding compatible control-valve positioners over 4-20 mA loops.
  • Driving I/P converters and actuator interfaces that accept analog demand signals.
  • Providing analog references to compatible drive or indicating equipment.
  • Maintaining HART-enabled final-control loops in Honeywell Series 8 cabinets.
Description
The 8C-PAOH51 51454355-175 is a coated Honeywell Series 8 analog output module that provides 16 independently commanded 4-20 mA channels with HART communication for compatible final-control devices.

The 8C-PAOH51 51454355-175 supports open-wire diagnostics, per-channel hold-last or shed-to-safe-value behavior, and removal and insertion under power in accordance with Honeywell maintenance procedures.

The 8C-PAOH51 51454355-175 uses the 8C-TAOX51 IOTA in a nonredundant arrangement or the 8C-TAOX61 IOTA in a redundant arrangement. Field-loop load, IOTA type and project configuration must be verified before commissioning.
Alternative Names
8C-PAOH51 51454355-175 8C PAOH51 8CPAOH51 8C-PAOH-51 8C-PAOH51-51454355-175 8C PAOH51 51454355 175 8CPAOH5151454355175 51454355175 Honeywell 8C-PAOH51
Technical notes
Before commissioning 8C-PAOH51 51454355-175, verify the installed IOTA, loop polarity, field-device load, HART requirement and configured fail option. A module can support removal and insertion under power, but the affected outputs still require a controlled maintenance plan because normal channel control is interrupted while the IOM is absent.
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
What control-loop work is 8C-PAOH51 51454355-175 suited for?
It is intended for sixteen 4-20 mA final-control loops that may also use HART communication, such as compatible valve positioners, I/P converters and actuator interfaces.
How should a maintenance team plan a live swap of 8C-PAOH51 51454355-175?
Honeywell supports removal and insertion under power, but the affected outputs are not normally controlled while the IOM is absent. Review the configured fail option, place the process in a safe condition and follow the site maintenance procedure before removal.
Which IOTA arrangement supports a redundant 8C-PAOH51 51454355-175 installation?
Use the coated 8C-TAOX61 redundant IOTA. A nonredundant installation uses 8C-TAOX51; confirm the installed IOTA and Experion project configuration before commissioning.
What should be checked if a valve loop reports open wire after installing 8C-PAOH51 51454355-175?
Check terminal wiring, polarity, field-device continuity, loop load and the channel diagnostic first. The module can detect and report an open field wire, so the physical loop should be verified before changing control configuration.
How do fail-option settings affect 8C-PAOH51 51454355-175 during an IOM fault?
Each channel can be configured to hold its last output or shed to a defined safe value. The selected behavior must match the process hazard review and the final-control device response.
What evidence should be recorded when commissioning 8C-PAOH51 51454355-175?
Record the full module label, IOTA model, redundancy arrangement, field-loop load, HART requirement and configured safe-state values. These records support later maintenance and make channel behavior traceable.