Features:
- Provides 16 analog output channels with 4–20 mA signaling and HART communication.
- Supports extensive diagnostics, configurable safe-state behavior, and Removal and Insertion Under Power.
- Supports non-redundant and redundant installations through the appropriate Series 8 IOTA.
The 8C-PAOH51 51454355-175 provides 16 high-level constant-current outputs for actuators, valve positioners, and recording or indicating devices. HART communication allows compatible smart field devices to exchange digital diagnostic and configuration information over the same 4–20 mA loops.
The 8C-PAOH51 51454355-175 supports extensive self-diagnostics, open-wire detection, and configurable FAILOPT behavior on each channel. Depending on the control strategy, a channel can hold its last value or move to a configured safe value following a detected failure.
The 8C-PAOH51 51454355-175 is used with the 8C-TAOX51 non-redundant IOTA or the 8C-TAOX61 redundant IOTA. Redundant installation requires the matching redundant IOTA and the applicable Experion Series 8 configuration.
The 8C-PAOH51 51454355-175 Honeywell High-Performance Analog Output Module may still be available for purchase and support from Apter Power beyond End-Of-Life (EOL) by the manufacturer (OEM).
Honeywell 8C-PAOH51 51454355-175 High-Performance Analog Output Module Manuals,
Datasheets, Drivers, Link
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not
included with this equipment unless listed in the above stock item description. All prices are
shown in USD.
Honeywell 8C-PAOH51 51454355-175 High-Performance Analog Output Module Specs
General
- Manufacturer Honeywell
- Model 8C-PAOH51 51454355-175
- Condition New Original ready stock
- Product Family 8C-PAOH51,8U-PAOH51,CC-PAOH51
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
- Install the 8C-PAOH51 51454355-175 on an 8C-TAOX51 IOTA for non-redundant configurations.
- Use an 8C-TAOX61 IOTA when the 8C-PAOH51 51454355-175 is configured for output redundancy.
- Configure channel assignments, HART communication, diagnostics, and safe-state behavior through the applicable Experion control environment.
- Verify the IOTA model, hardware revision, field-loop load, wiring polarity, and system compatibility before commissioning.
- Provides 16 independently commanded 4–20 mA analog output channels.
- Supports HART communication for compatible device configuration and diagnostic access.
- Detects open field wiring and reports the condition through channel diagnostics.
- Supports configurable safe-state behavior and live module replacement through RIUP.
- Valve Positioning - Sends 4–20 mA commands to compatible control-valve positioners while enabling HART communication.
- Drive Reference - Provides an analog speed or demand reference to a compatible variable-frequency drive control input.
- Process Regulation - Controls final elements used in flow, pressure, temperature, and level-regulation loops.
- Legacy Maintenance - Supports replacement and maintenance of compatible Honeywell Experion Series 8 analog output installations.