Ask our team:
  • Phone: +86 181 0690 9650
  • E-Mail sales1@apterpower.com
  • Lifecycle status

    Discontinued / Obsolete by OEM
    Apter Power provides PDIL51 quotes, spare sourcing, official lifecycle records, and IOTA compatibility support.

CC-PDIL51

/ 4.9
1001 reviews | Need a Specific Revision?
Honeywell CC-PDIL51 is a 32-channel Series C digital input module for 24 VDC discrete signals and does not provide open-wire detection.
In Stock
Ships by Thursday, October 29
Fast Shipping Available
Get a quick price for CC-PDIL51
Quantity
*E-mail
Company
*Mobile
*Content
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)

Technical specifications for CC-PDIL51

  • Manufacturer:
    Honeywell
  • Part Number:
    CC-PDIL51
  • Product Family:
    Honeywell Experion PKS ( C200, C300 )
  • Product Type:
    24 VDC Digital Input Module
  • Stock:
    1
  • Input Channels:
    32
  • Power Voltage Range:
    18-30 VDC
  • ON Threshold:
    13 VDC or 3 mA minimum
  • OFF Threshold:
    5 VDC or 1.2 mA maximum
  • Isolation:
    1000 VAC RMS
  • Input Delay:
    5 ms ±20%
  • Open-Wire Detection:
    Not supported
  • Tariff Code:
    Please confirm the destination before shipping.
  • Country of origin:
    USA
  • Place of shipment:
    Xiamen, Fujian, China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals Specifications PDIL51 Input Window No OWD Distinction PDIL01 Replacement

Product overview:

  • Digital inputs: 32 channels for 24 VDC discrete signals
  • Key distinction: No open-wire detection
  • Supply status: Phase Out with installed-base spare availability
Honeywell CC-PDIL51 is a 32-channel Series C digital input module for 24 VDC discrete signals and does not provide open-wire detection.

Availability is subject to Apter Power's current inventory and configuration confirmation.
Honeywell CC-PDIL51 Specifications

General

  • ManufacturerHoneywell
  • ModelCC-PDIL51
  • ConditionNew and factory sealed
  • Product FamilyHoneywell Experion Series C I/O
  • Power range: 18-30 VDC
  • ON sensing: 13 VDC or 3 mA minimum
  • OFF sensing: 5 VDC or 1.2 mA maximum
  • Open-wire: CC-PDIL51 does not support open-wire detection
  • Isolation: Optical system-to-field isolation is provided
  • Diagnostics: Internal diagnostics support data integrity without OWD
  • Lifecycle: CC-PDIL51 is in Phase Out
  • Spares: The same module remains available for the installed base
  • Expansion: Honeywell recommends CC-PDIL01 and its matching IOTAs
Description
Honeywell CC-PDIL51 is a 32-channel Series C digital input module for 24 VDC discrete signals and does not provide open-wire detection.

The module supports optical isolation, direct or reverse indication, internal or external field power, onboard excitation, and optional redundancy with CC-TDIL51 or CC-TDIL61.

Honeywell classifies the PDIL51 hardware family as Phase Out, keeps the same model available for installed-base spares, and recommends CC-PDIL01 for new and expansion projects.

Alternative Names
CC-PDIL51 Honeywell CC-PDIL51 Honeywell Experion CC-PDIL51 CC-PDIL51 24 VDC Digital Input Module CC-PDIL51 datasheet CC-PDIL51 quotation CCPDIL51
Technical notes
CC-PDIL51: Phase-out 32-channel 24 VDC digital input module without open-wire detection; installed-base spares remain available. Confirm the exact Honeywell model and compatible hardware before ordering.
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
Does CC-PDIL51 detect an open input wire?
No. Honeywell explicitly documents no open-wire detection.
How many inputs are provided by PDIL51?
It provides 32 discrete 24 VDC inputs.
What field-power range is accepted by CC-PDIL51?
Honeywell specifies 18 to 30 VDC.
What isolation rating applies to the PDIL51 model?
The official Series C specification lists 1000 VAC RMS.
Which IOTA is used for nonredundant PDIL51 installation?
Honeywell lists CC-TDIL51.
Which IOTA enables redundant PDIL51 operation?
Honeywell lists CC-TDIL61.
What is the current Honeywell lifecycle phase for PDIL51?
The May 2026 notice classifies the family as Phase Out.
Which digital input is preferred for greenfield expansion?
Honeywell recommends CC-PDIL01 with its current IOTA family.