Features:
- Wiring interface for the 10001/1/1 and 10001/R/1 Vertical Bus Driver assemblies.
- J1–J4 and J5–J6 jumpers provide VBD and Central Part hardware addressing.
- The fixed wiring section permits electronic-part replacement without removing the vertical-bus flat cable.
Honeywell 10001/A/1 forms the wiring section of the FSC 10001/1/1 and 10001/R/1 Vertical Bus Driver assemblies. Its 96-pin connector and retaining bolts secure the wiring section to the 19-inch Central Part rack.
Honeywell 10001/A/1 provides hardware addressing through two jumper groups. Jumpers J1–J4 select the VBD number, while J5 and J6 select the Central Part number required by the installed FSC configuration.
Honeywell 10001/A/1 keeps the vertical-bus flat cable attached to the fixed wiring section while the electronic VBD section is serviced. Central Part power must be isolated before removing or replacing the VBD electronic section.
The 10001/A/1 Honeywell Wiring Part may still be available for purchase and support from Apter Power beyond End-Of-Life (EOL) by the manufacturer (OEM).
Honeywell 10001/A/1 Wiring Part Manuals,Datasheets,Link
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
Honeywell 10001/A/1 Wiring Part Specs
General
- Manufacturer Honeywell
- Model 10001/A/1
- Condition New Original ready stock
- Product Family 10001/1/1, 10001/R/1
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
- Install Honeywell 10001/A/1 as the fixed wiring section of a compatible 10001/1/1 or 10001/R/1 VBD assembly.
- Secure the wiring section to the 19-inch rack using the bolts provided on the 96-pin connector.
- Connect the vertical-bus flat cable to the wiring section according to the FSC cabinet configuration.
- Verify the J1–J6 addressing before installing the electronic VBD section and applying Central Part power.
- Honeywell 10001/A/1 is the wiring part used with 10001/1/1 and 10001/R/1 Vertical Bus Driver assemblies.
- The associated VBD connects the FSC Central Part to the I/O level through the vertical bus.
- Compatible horizontal bus arrangements use 10100/1/1 or 10100/2/1 Horizontal Bus Driver modules.
- Selection between 10001/1/1 and 10001/R/1 depends on the Central Part and I/O redundancy configuration.
- Fixed wiring interface for VBD assemblies installed in legacy Honeywell FSC Central Part racks.
- Maintenance replacement where the existing vertical-bus flat cable should remain connected to the rack wiring section.
- Hardware addressing of VBD and Central Part positions through the J1–J6 jumper groups.
- FSC installations using non-redundant or redundant I/O configurations with compatible 10001-series VBD assemblies.