Features:
- Two-out-of-three voting architecture for dependable watchdog supervision.
- Independent emergency shutdown inputs for direct de-energization.
- Combined monitoring of program timing, supply voltage, and memory faults.
Honeywell 10005/1/1 uses three watchdog sections and two-out-of-three voting to reduce dependence on a single monitoring path. This architecture supports dependable supervision of critical FSC controller operation and permits watchdog testing within the intended system design.
Honeywell 10005/1/1 provides hardware-based shutdown paths that do not depend solely on successful application-program execution. Its emergency shutdown inputs can remove the watchdog output when an external safety condition requires the connected system to enter its defined safe response.
Honeywell 10005/1/1 combines application-loop timing, internal supply-voltage supervision, and CPU, COM, and MEM error indications in the watchdog decision. These functions help detect abnormal controller execution before unsupervised operation can continue.
The 10005/1/1 Honeywell Watchdog Module may still be available for purchase and support from Apter Power beyond End-Of-Life (EOL) by the manufacturer (OEM).
Honeywell 10005/1/1 Watchdog Module Manuals,Datasheets,Link
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
Honeywell 10005/1/1 Watchdog Module Specs
General
- Manufacturer Honeywell
- Model 10005/1/1
- Condition New Original ready stock
- Product Family 10006/2/1, 10006/2/2, 10007/1/1
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
- Program Timing: Supervises both maximum and minimum application-loop execution times.
- Supply Monitoring: Detects internal 5 V DC overvoltage and undervoltage conditions outside the permitted range.
- Memory Supervision: Processes error indications from FSC CPU, COM, and MEM modules.
- Watchdog Response: De-energizes WDGOUT when the watchdog decision detects an applicable fault condition.
- Emergency Shutdown: Supports watchdog supervision within FSC emergency shutdown configurations.
- Burner Management: Provides controller-execution supervision in FSC-based burner and boiler management systems.
- Equipment Safeguarding: Supports FSC installations used for turbine and compressor safeguarding.
- Fire and Gas: Provides watchdog supervision within FSC fire-and-gas detection system configurations.
- FSC Installation: Designed for installation in the Honeywell Fail Safe Controller central-part configuration.
- Input Integration: Accepts the specified ESD1, ESD2, and reset signals used by the FSC watchdog circuit.
- Output Loading: Supplies the 5 V DC WDGOUT signal to compatible FSC output modules within the stated current limit.
- Load Expansion: Uses a compatible watchdog repeater when connected modules require more current than the watchdog output can supply.