    Apter Power provides quotations, technical documents and exact-model sourcing support for Honeywell FSC safety-system maintenance.

10216/2/1

/ 4.9
1001 reviews | Need a Specific Revision?
Honeywell 10216/2/1 is a four-channel 24 VDC fail-safe, loop-monitored digital output module for FSC systems.
In Stock
Ships by Thursday, October 29
Fast Shipping Available
Get a quick price for 10216/2/1
Quantity
*E-mail
Company
*Mobile
*Content
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)

Technical specifications for 10216/2/1

  • Manufacturer:
    Honeywell
  • Part Number:
    10216/2/1
  • Product Family:
    Honeywell FSC Series
  • Product Type:
    Fail-Safe Loop-Monitored Digital Output Module
  • Stock:
    1
  • Output channels:
    4
  • Output type:
    24 VDC solid-state source, short-circuit proof
  • Maximum channel current:
    1 A
  • Maximum total module load:
    3.6 A
  • Maximum load inductance:
    0.5 H
  • Maximum load capacitance:
    1 µF
  • Power requirements:
    5 VDC at 15 mA; internal 24 VDC at 50 mA; external 24 VDC at 15 mA without load
  • Software version:
    3.00 or later
  • Weight:
    0.14 kg
  • Estimated shipping dimensions:
    2 x 18.8 x 12.8 cm
  • Tariff Code:
    8537101190
  • Country of origin:
    United States
  • Place of shipment:
    Xiamen, Fujian, China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals Loop Monitoring Load Planning Backplane Interface Product Applications

Features:

  • Four monitored outputs: Four 24 VDC sourcing channels supervise their field loops.
  • Fail-safe architecture: A secondary path can de-energize outputs independently of application logic.
  • Fault diagnostics: Lead breakage and short-circuit conditions are monitored.
Each output supplies up to 1 A, while the complete module is limited to 3.6 A.

The channel monitor uses a 10216/A range-setting module selected for the connected load current.

The module operates with an I/O backplane and separate internal and external 24 VDC connections.

Apter Power supports Honeywell 10216/2/1 Fail-Safe Loop-Monitored Digital Output Module sourcing with quotation and documentation review.
Honeywell 10216/2/1 Fail-Safe Loop-Monitored Digital Output Module Manuals,Datasheets,LinkImportant Notice: Apply the complete Honeywell FSC safety documentation when engineering or commissioning this output module.
  • Open-circuit supervision: Every output is monitored for lead breakage.
  • Short-circuit supervision: The output circuits include short-circuit detection.
  • Range selection: 10216/A modules match the current-sense range to the connected load.
  • Spare-channel handling: Dummy loads prevent unused channels from producing false lead-break indications.
  • Channel limit: Each 24 VDC sourcing output is rated up to 1 A.
  • Module limit: The combined output load may not exceed 3.6 A.
  • Inductive boundary: Honeywell lists a maximum load inductance of 0.5 H.
  • Capacitive boundary: Honeywell lists a maximum load capacitance of 1 µF.
  • Backplane requirement: The module is used only with an FSC I/O backplane.
  • Internal supply: The electronics require the documented internal 24 VDC connection.
  • External supply: Field outputs and test loads require the documented external 24 VDC connection.
  • Key coding: Honeywell assigns A13 and C9 to the module and rack positions.
  • Monitored solenoid loops: The sourcing outputs supervise open and short field conditions.
  • Safety-related shutdown outputs: The secondary de-energization path supports the FSC architecture.
  • Four-channel 24 VDC control: The module serves loads that fit the selected monitoring range and total current limit.
Description
Four 24 VDC sourcing channels make 10216/2/1 a monitored FSC output module for field devices that need open-circuit and short-circuit supervision. Each channel can deliver up to 1 A, while the complete module is limited to 3.6 A.

Loop monitoring on 10216/2/1 is matched to the connected load through a 10216/A range-setting module. Correct range selection lets the FSC distinguish a healthy low-current load from a lead break without changing the output card.

A secondary de-energization path gives 10216/2/1 an independent way to switch off its outputs. The module operates in the FSC I/O backplane with the documented internal and external 24 VDC supplies, and unused channels require the specified dummy-load arrangement.
Alternative Names
10216-2-1 10216 2 1 1021621 Honeywell 10216/2/1 FSC 10216/2/1 10216 / 2 / 1 10216/2/I 10216/2/l
Technical notes
Honeywell specifies 1 A per channel for 10216/2/1, but limits the full module to 3.6 A. Four channels therefore cannot all be planned at 1 A simultaneously; the load schedule should respect the total-module limit as well as the selected range-setting modules.
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
Can four 1 A loads run continuously from 10216/2/1 at the same time?
No. The four channels are individually rated to 1 A, but Honeywell limits the module total to 3.6 A, so the combined load schedule must be reduced.
A healthy low-current load is showing a lead-break alarm on 10216/2/1. What should be checked?
Check the installed 10216/A range-setting module against the actual load current. A mismatched range can place a healthy loop outside the monitor window.
Why does an unused channel on 10216/2/1 report a field fault during testing?
An open spare channel is seen by the lead-break supervision. Use Honeywell's documented dummy-load arrangement on unused outputs.
Can 10216/2/1 be bench-operated without the FSC I/O backplane?
No. Honeywell specifies the I/O backplane because the output arrangement depends on the installed range-setting modules and the documented supply connections.
What should maintenance do when 10216/2/1 reports an output short circuit?
Treat the alarm as a field-loop stop signal: isolate and inspect the connected load and wiring before returning the channel to service.
Does the secondary de-energization path make any 10216/2/1 installation automatically fail-safe?
No. It supports the FSC fail-safe architecture, but the complete loop, backplane, range module, field device and safety application still require system-level validation.