Technical specifications for FS-SAI-0410

  • Manufacturer:
    Honeywell
  • Part Number:
    FS-SAI-0410
  • Product Family:
    Honeywell FSC Series
  • Product Type:
    4-Channel Safe Analog Input Module
  • Stock:
    1
  • Safe analog channels:
    4
  • Direct input range:
    0–2 V DC
  • Input resistance:
    Greater than 100 kΩ
  • Loop supply:
    26 V DC ±1 V
  • Loop protection:
    Short-circuit protected
  • Active input threshold:
    Greater than 21 mA
  • Conversion performance:
    12-bit; error no more than 0.75%
  • Construction:
    Non-conformal-coated FS version
  • Tariff Code:
    85389000
  • Country of origin:
    USA
  • Place of shipment:
    Xiamen,Fujian,China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals Signal Data Converter Fit Safety Use Installation Check

Features:

  • Four safe analog input channels
  • 0–2 V DC direct measurement
  • Protected 26 V DC loop supply
FS-SAI-0410 accepts conditioned field signals through the documented converter arrangement and delivers supervised analog values to the Safety Manager application.

Converter selection, scaling, loop power and diagnostic thresholds must be reviewed as one signal chain before commissioning.

Converter selection, loop power, scaling and diagnostic limits should be validated as one signal chain rather than as independent module settings.

The Honeywell FS-SAI-0410 4-Channel Safe Analog Input Module is available for quotation and technical support from Apter Power.
Verified resources for FS-SAI-0410:

Signal Data:

  • Direct range 0–2 V DC
  • Input resistance above 100 kΩ
  • 12-bit conversion
Include module and converter accuracy when setting application trip margins.

Converter Fit:

  • BSAI-04x for analog conversion
  • BSDIL-0426 for loop-monitored digital use
  • Verify range and channel wiring
Do not connect a 4–20 mA loop directly without the specified conversion arrangement.

Safety Use:

  • Four supervised safety channels
  • Short-circuit-protected loop supply
  • Migration parameters require review
Validate diagnostic coverage and application scaling for the complete installed loop.

Installation Check:

  • Verify 26 V loop power
  • Inject calibrated test signals
  • Confirm alarms, scaling and trip action
Document the as-left readings for every commissioned channel.
Description
Honeywell FS-SAI-0410 4-Channel Safe Analog Input Module is a non-conformal-coated four-channel safe analog input module for Honeywell Safety Manager. Its direct measuring range is 0–2 V DC, and standard current or voltage field signals are connected through the documented BSAI-04x or BSDIL-0426 conversion hardware.

The module has input resistance greater than 100 kΩ, a protected 26 V DC ±1 V loop supply and 12-bit conversion with documented error not exceeding 0.75%. With the correct converter, the channel arrangement can serve 0(4)–20 mA, 0(1)–5 V, 0(2)–10 V or loop-monitored digital signals.

Select the converter, scaling, loop power and diagnostic thresholds as one complete signal chain. When migrating an installed SAI-0410 loop, review the current-input implementation rather than copying settings directly, then validate low, mid and high test values, alarms and trip action.
Alternative Names
FS-SAI-0410 FS SAI 0410 FSSAI0410 Honeywell FS-SAI-0410 Honeywell FS SAI 0410 Honeywell FSSAI0410 FS-SAI-0410 4-Channel Safe Analog Input Module Honeywell SAI-0410 4-Channel Safe Analog Input Module
Technical notes
FS-SAI-0410 is a four-channel 0–2 V DC safe analog input module that works with documented BSAI or BSDIL conversion hardware. Confirm converter type, range and migration parameters before applying field signals.
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
Why does FS-SAI-0410 require a signal converter for 4–20 mA transmitters?
The module directly measures 0–2 V DC, so the documented BSAI-04x or BSDIL-0426 hardware converts and conditions standard field signals.
Which field ranges can be used with FS-SAI-0410?
With the correct converter, supported applications include 0(4)–20 mA, 0(1)–5 V, 0(2)–10 V and loop-monitored digital signals.
How should the 26 V loop supply be checked?
Verify 26 V DC within ±1 V at the converter, confirm short-circuit protection and account for field wiring voltage drop under load.
What resolution and error are documented for FS-SAI-0410?
The analog conversion is 12-bit with a documented maximum error of 0.75%, subject to the complete converter and loop arrangement.
Why is migration from SAI-0410 not a direct settings copy?
Later Safety Manager analog input hardware handles 0(4)–20 mA differently, so range, converter, diagnostics and application scaling require engineering review.
Can FS-SAI-0410 and FC-SAI-0410 be interchanged?
Only after confirming the coating requirement, converter interface, approved hardware list and cabinet environment.
What commissioning tests are required for FS-SAI-0410?
Inject calibrated low, mid and high signals, verify scaling and alarms, test loop faults and confirm the safety application channel mapping.
What data is required to quote FS-SAI-0410?
Provide the exact model, signal range, converter or FTA type, loop-power design, coating requirement, channel count, quantity and destination.

Product Browsing History