Features:
- Provides 250Mbps data transfer between Processor and Expansion chassis via UTP cables, supporting distances up to 30m copper or 10km fibre with converters.
- Supports dual-module active/standby configuration with interlocks preventing both modules from becoming active simultaneously. TMR Processor determines active module based on health status.
- Three front-panel Healthy LEDs (Channels A, B, C) indicate individual channel status. Steady green = healthy, flashing red = fault. Includes detailed troubleshooting via T8300 chassis board or diagnostic utility.
The T8311 is the critical communication bridge between the TMR Processor Chassis and Expansion Chassis in ICS Triplex Trusted systems. It provides a triplicated Expander Bus that operates at 250Mbps data transfer rate using standard UTP cables, ensuring high-integrity communication for safety-critical applications. The Expander Bus handles all message forwarding from the Controller Chassis IMB to the Expansion Chassis, as well as response messages back to the processor. For system design flexibility, the T8311 supports distances up to 30 meters using TC-301 copper cable, ideal for adjacent cabinet installations.
The T8311 is designed for high-availability systems requiring fault-tolerant operation. Two T8311 modules can be installed in an active/standby pair, providing seamless failover without system interruption. In this configuration, the TMR Processor continuously monitors the health of both modules and determines which should be active based on their condition. When both modules are healthy, active operation defaults to the left-most module by convention. The module includes hardware interlocks that prevent both modules from assuming active mode simultaneously, a critical safety feature that avoids communication conflicts on the Expander Bus.
The T8311 provides extensive diagnostic capabilities through its front-panel indicators and system-level fault reporting. Three Healthy LEDs—one for each TMR channel (A, B, and C)—allow operators to quickly assess module status at a glance. A steady green LED indicates a healthy channel, while a flashing red LED indicates a fault in that specific channel. The troubleshooting guide in the datasheet provides detailed symptom-cause-solution tables for diagnosing issues such as all front panel indicators off, single FCR flashing red, multiple FCR flashing red, or flashing standby indicator. For example, a flashing standby indicator indicates the TMR Processor has detected a fault and switched to the standby module.
The T8311 ICS TRIPLEX Interface Module may still be available for purchase and support from Apter Power beyond
End-Of-Life (EOL)by the manufacturer (OEM).
ICS TRIPLEX T8311 Interface Module Manuals,
Datasheets,Drivers,Link
Important Notice:Other accessories,manuals,cables,calibration data,software,etc.are not
included with this equipment unless listed in the above stock item description.All prices are
shown in USD.
ICS TRIPLEX T8311 Interface Module Specs
General
- Manufacturer ICS TRIPLEX
- Model T8311
- Condition New Original ready stock
- Product Family
T8310,T8300,T8311,T8300C
Important Notice:Other accessories,manuals,cables,calibration data,software,etc.are not
included with this equipment unless listed in the above stock item description.All prices are
shown in USD.
- Large-Scale Integrated Control and Safety Systems (ICSS): Manages hundreds of analog and digital safety points spread across multiple cabinets in sprawling oil refineries and ethylene cracker complexes.
- Distributed Emergency Shutdown Systems (ESD): Aggregates remote emergency trip loops from geographically separated process areas (e.g., wellheads, cracking towers, storage tanks) back to the central safety processors.
- Global Fire and Gas (F&G) Protection Plants: Connects centralized processing logic to rows of remote expansion chassis holding 16-point and 40-point safety input/output modules across vast production floors.
- Ambient Temperature: -40°C to +70°C (-40°F to +158°F) operating range under free convection (fanless) cabinet conditions.
- Storage Temperature: -40°C to +85°C.
- Relative Humidity: 5% to 95%, non-condensing.
- Vibration & Shock: Fully tested to survive high-impact low-frequency vibrations caused by nearby heavy rotating machinery (such as massive turbines or high-velocity gas compressors).
- Triple Modular Redundancy (TMR): The module contains three completely isolated Fault Containment Regions (FCR A, B, and C), tracking separate processing paths from the backplane to the expansion ports.
- 2-out-of-3 (2oo3) Hardware Voting: All incoming and outgoing chassis packets undergo continuous 2oo3 voting matrices at the hardware layer.
- High-Bandwidth Inter-Chassis Bus: Establishes point-to-point links over standard shielded twisted-pair (STP) cables at a blinding deterministic speed of 250 Mbps.