Features:
- High-Density 16-Channel Redundancy
- Mechanical Polarization & Error Prevention
- Hazardous Area Ready (Zone 2/Div 2)
The ICS-TRIPLEX T9832 supports up to 16 independent analogue input channels in a dual configuration. This allows two T9432 modules to monitor the same field device, enabling 1oo2D voting for critical process variables without consuming extra cabinet space.
Equipped with a physical coding peg system (positions 2-1-3), the ICS-TRIPLEX T9832 prevents the insertion of incorrect module types (e.g., digital output modules). This hardware-level interlock eliminates common wiring errors during hot module replacement in a running safety system.
Certified for ATEX/IECEx Ex ec IIC T4 Gc and Class I Division 2 environments, the ICS-TRIPLEX T9832 allows direct termination of field signals from explosive atmospheres. It must be installed in an IP54 tool-accessible enclosure, ensuring operator safety during maintenance.
The T9832 ICS Triplex Analogue Input Termination Assembly may still be available for purchase and support from Apter Power beyond End-Of-Life (EOL) by the manufacturer (OEM).
ICS Triplex T9832 Analogue Input Termination Assembly Manuals,Datasheets,Link
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
ICS Triplex T9832 Analogue Input Termination Assembly
General
- Manufacturer ICS Triplex
- Model T9832
- Condition New Original ready stock
- Product Family T9801,T9802,T9803
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
- Wide Ambient Range: Rated for continuous operation from -25°C to +60°C, suitable for unheated control cabinets in arctic or desert climates.
- Condensation Control: Designed for 10-95% non-condensing humidity; requires normalizing temperature before power-up if moved from cold storage to prevent moisture damage.
- Pollution Control: Limited to Pollution Degree 2 environments (non-conductive pollution only); must be enclosed to prevent conductive dust ingress.
- Vibration Resistance: Withstands functional vibration up to 3.5 mm amplitude (5-9 Hz) and shock up to 15g peak (11 ms half-sine) per IEC 61131-2.
- Functional Safety: TÜV Rheinland certified for use in safety loops up to SIL 3 (IEC 61508:2010) when configured with dual T9432 modules.
- Hazardous Locations: ATEX (DEMKO 11 ATEX 1129711X) and IECEx (UL 12.0032X) for Ex ec IIC T4 Gc (Zone 2). UL/cUL listed for Class I, Division 2, Groups A, B, C, D.
- Marine & Offshore: Complies with material requirements for coastal and industrial environments per UL 61010-2-201.
- EMC Compliance: Tested to EN 61326-1 (Class A) and EN 61131-2 for industrial electromagnetic immunity, ensuring low false trip rates.
- Emergency Shutdown (ESD) Systems: Provides redundant analog pressure/temperature inputs for High Integrity Pressure Protection Systems (HIPPS).
- Fire & Gas (F&G) Monitoring: Interfaces with 4-20 mA gas detectors and smoke sensors requiring fault-tolerant input voting.
- Critical Burner Management (BMS): Monitors flame scanner intensity and furnace draft pressures in boiler control systems.
- Offshore Platform Monitoring: Facilitates signal termination for subsea instrumentation in corrosive, high-humidity environments.