Reliance Electric 57C420 is a AutoMax 5-24 V DC Output Module. It provides thirty-two solid-state outputs for 5-24 V DC field loads.
In Stock
Ships by Wednesday, October 28
Fast Shipping Available
Get a quick price for 57C420
Quantity
*E-mail
Company
*Mobile
*Content
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)

Technical specifications for 57C420

  • Manufacturer:
    Reliance Electric
  • Part Number:
    57C420
  • Product Family:
    AutoMax PLC
  • Product Type:
    DC Output Module
  • Stock:
    1
  • Output points:
    32
  • Output range:
    5 to 24 V DC; maximum operating voltage 30 V DC
  • Maximum load:
    750 mA per output; 1.8 A per common
  • Isolation grouping:
    Four outputs per isolated common
  • Logic-to-output isolation:
    5000 V AC
  • Maximum saturated drop:
    1.5 V
  • Backplane power:
    +5 V at 850 mA
  • Dimensions:
    11.75 x 1.25 x 7.375 in
  • Environment:
    0 to 60 deg C operating; 5 to 90% RH noncondensing
  • Weight:
    0.82 kg
  • Estimated shipping dimensions:
    3x19x34.4cm
  • Tariff Code:
    8537101190
  • Country of origin:
    USA
  • Place of shipment:
    Xiamen,Fujian,China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals Applications Communication & Connectivity Configuration Environmental Ratings

Features:

  • Provides thirty-two solid-state outputs for 5-24 V DC field loads.
  • Allows up to 750 mA per point within the 1.8 A common-group limit.
  • Uses four outputs per isolated common with high logic-to-field isolation.
The module converts AutoMax backplane commands into thirty-two low-voltage DC switching outputs for field loads.

Application logic writes an output image to the module. Solid-state output circuits source the commanded 5-24 V DC state to each load, while isolated common groups limit the propagation of field-side faults.

Verify field-supply polarity, common grouping, cable and terminal-strip identity before enabling outputs. Removing or inserting the module or its cables can cause unexpected machine movement.

Availability is reviewed against the exact 57C420 order identity and requested supply condition; manufacturer lifecycle status: Discontinued / Obsolete by OEM.
Verified resources for Reliance Electric 57C420:Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
  • A single point may switch up to the documented 750 mA, but the four-output common is limited to 1.8 A. Thermal and power calculations must therefore consider the simultaneous load pattern, not only individual point current.
  • The outputs can drive compatible relays, indicators, solenoids and other DC loads in machine or process-control panels when surge suppression and field supply design are suitable.
  • Receives its commanded output image through the AutoMax rack backplane.
  • Provides 32 discrete outputs for AutoMax field-control circuits.
  • Operates across 5 to 24 V DC, with a 30 V maximum.
  • Field-supply polarity and terminal identity must match before outputs are enabled.
  • Each channel switches 750 mA; each common supports 1.8 A.
  • Four outputs share each isolated field common.
  • Logic-to-output isolation is rated at 5000 V AC.
  • Supports 0 to 60 deg C and 5–90% noncondensing humidity.
  • Maximum saturated output drop is 1.5 V.
  • Draws 850 mA from the +5 V backplane supply.
Description
Reliance Electric 57C420 The module converts AutoMax backplane commands into thirty-two low-voltage DC switching outputs for field loads. Application logic writes an output image to the module. Solid-state output circuits source the commanded 5-24 V DC state to each load, while isolated common groups limit the propagation of field-side faults.

A single point may switch up to the documented 750 mA, but the four-output common is limited to 1.8 A. Thermal and power calculations must therefore consider the simultaneous load pattern, not only individual point current. The outputs can drive compatible relays, indicators, solenoids and other DC loads in machine or process-control panels when surge suppression and field supply design are suitable.

Verify field-supply polarity, common grouping, cable and terminal-strip identity before enabling outputs. Removing or inserting the module or its cables can cause unexpected machine movement.
Alternative Names
57C420 57-C420 57 C420 Reliance Electric 57C420 AutoMax 57C420 57C420 DC Output Module 57C420 5-24 V DC Output Module Reliance Electric AutoMax 57C420 Output Module
Technical notes
De-energize field loads before disturbing Reliance Electric 57C420, and confirm supply polarity, isolated common grouping, cable, and terminal-strip identity because an incorrect output reconnection can start machinery unexpectedly.
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
Where do Reliance Electric 57C420 outputs connect in machine control?
The module converts AutoMax backplane commands into thirty-two low-voltage DC switching outputs for field loads.
Which output voltage limits apply to Reliance Electric 57C420?
The manufacturer data specifies Output range as 5 to 24 V DC; maximum operating voltage 30 V DC; the installed arrangement must match that exact value.
How does Reliance Electric 57C420 transfer rack commands to loads?
Application logic writes an output image to the module. Solid-state output circuits source the commanded 5-24 V DC state to each load, while isolated common groups limit the propagation of field-side faults.
What polarity and common checks protect a Reliance Electric 57C420 installation?
Verify field-supply polarity, common grouping, cable and terminal-strip identity before enabling outputs. Removing or inserting the module or its cables can cause unexpected machine movement.
Does commissioning alter the obsolete status of Reliance Electric 57C420?
The page records Discontinued / Obsolete by OEM. Apter Power reviews the exact order identity and condition without presenting this as an OEM delivery promise.
Which load-circuit evidence supports a Reliance Electric 57C420 quotation?
Submit the complete nameplate, Maximum saturated drop (1.5 V), installed system evidence, condition, quantity and destination so the document and quotation match 57C420.