Features:
- Provides thirty-two solid-state outputs for 5-24 V DC field loads.
- Allows up to 750 mA per point within the 1.8 A common-group limit.
- Uses four outputs per isolated common with high logic-to-field isolation.
The module converts AutoMax backplane commands into thirty-two low-voltage DC switching outputs for field loads.
Application logic writes an output image to the module. Solid-state output circuits source the commanded 5-24 V DC state to each load, while isolated common groups limit the propagation of field-side faults.
Verify field-supply polarity, common grouping, cable and terminal-strip identity before enabling outputs. Removing or inserting the module or its cables can cause unexpected machine movement.
Availability is reviewed against the exact 57C420 order identity and requested supply condition; manufacturer lifecycle status: Discontinued / Obsolete by OEM.
Verified resources for Reliance Electric 57C420:
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
- A single point may switch up to the documented 750 mA, but the four-output common is limited to 1.8 A. Thermal and power calculations must therefore consider the simultaneous load pattern, not only individual point current.
- The outputs can drive compatible relays, indicators, solenoids and other DC loads in machine or process-control panels when surge suppression and field supply design are suitable.
- Receives its commanded output image through the AutoMax rack backplane.
- Provides 32 discrete outputs for AutoMax field-control circuits.
- Operates across 5 to 24 V DC, with a 30 V maximum.
- Field-supply polarity and terminal identity must match before outputs are enabled.
- Each channel switches 750 mA; each common supports 1.8 A.
- Four outputs share each isolated field common.
- Logic-to-output isolation is rated at 5000 V AC.
- Supports 0 to 60 deg C and 5–90% noncondensing humidity.
- Maximum saturated output drop is 1.5 V.
- Draws 850 mA from the +5 V backplane supply.