Features:
- Two ±10 V inputs produce 12-bit-plus-sign values for an ET 200X station.
- Parameterizable integration suppresses either 50 Hz or 60 Hz interference.
- Channel diagnostics report range faults and configured limit events through the station.
Voltage signals enter Siemens 6ES7144-1FB31-0XB0 through its M12 field connections and are converted within the distributed I/O module.
Both channels of 6ES7144-1FB31-0XB0 use the selected integration setting while retaining individual upper and lower limit monitoring.
Protected encoder outputs on 6ES7144-1FB31-0XB0 supply attached sensors separately from the measured voltage conductors.
The Siemens 6ES7144-1FB31-0XB0 ET 200X EM 144 Analog Input Expansion Module may still be available for purchase and support from Apter Power beyond End-Of-Life (EOL) by the manufacturer (OEM).
Siemens 6ES7144-1FB31-0XB0 ET 200X EM 144 Analog Input Expansion Module Manuals,Datasheets,Link
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
Voltage Acquisition and Conversion
- Signal range: Each channel accepts a bipolar -10 V to +10 V measurement signal.
- Input impedance: The 100 kohm input resistance defines the load presented to the voltage source.
- Conversion: Integrated measurement produces a 12-bit value plus sign and a documented overrange.
- Protection limit: The voltage at an input must remain below the 30 V destruction limit.
Interference Rejection and Response
- 16.7 ms choice: This integration time aligns conversion with suppression of 60 Hz interference.
- 20 ms choice: This integration time aligns conversion with suppression of 50 Hz interference.
- Shared setting: Both analog inputs follow the parameterized conversion timing of the module.
- Cable boundary: Shielded measurement wiring is limited to a maximum length of 30 m.
Events and Front Indication
- Range faults: Overflow and underflow are diagnosed for the affected channel.
- Limit events: Upper and lower limits can generate channel-specific alarms.
- Hardware interrupt: The module can raise a hardware interrupt for configured events.
- SF indicator: The red SF LED summarizes a detected module or channel diagnostic condition.
Sensor Supply and Potential Group
- Field connectors: Four- and five-pin M12 circular connectors carry input and output conductors.
- Encoder feeds: Two electronically protected outputs provide the documented sensor supplies.
- Shared potential: The analog inputs are not galvanically isolated from one another.
- Temperature derating: Available encoder-supply current decreases from 0.9 A at 40 C to 0.7 A at 55 C.