Features:
- Sixteen safety inputs are arranged as four channel groups.
- Four monitored sensor supplies associate field-power faults with their input groups.
- PROFIsafe transfers verified channel states and diagnostics to the F-controller.
The configured evaluation determines whether one signal or a paired sensor arrangement forms the safety input.
Discrepancy and fault reactions belong to the safety parameters rather than ordinary PLC logic.
H1 and M1 terminal blocks define single-path or redundant station wiring.
The Siemens 6DL1136-6BA00-0PH1 ET 200SP HA Fail-Safe Input Module may still be available for purchase and support from Apter Power beyond End-Of-Life (EOL) by the manufacturer (OEM).
Siemens 6DL1136-6BA00-0PH1 ET 200SP HA Fail-Safe Input Module Manuals,Datasheets,Link
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
Turning sensor states into verified PROFIsafe process data
- Channel mode: The configured evaluation defines single-channel or paired-sensor processing.
- Discrepancy check: Paired signals must agree within the assigned timing condition.
- F-parameters: The module identity and safety settings must match the F-controller project.
- Passivation: A detected safety fault substitutes the configured safe behavior for the affected data.
Associating sixteen inputs with four monitored field-power paths
- Group structure: Each set of four inputs uses its assigned sensor-supply output.
- Short-circuit supervision: A fault on a monitored supply is reported for the corresponding channel group.
- 24 V sensors: The supply and input return wiring must follow the terminal-block diagram.
- Fault isolation: Separate groups help locate a field-power problem without treating every input as one circuit.
Separating field faults from module and communication conditions
- Channel LEDs: Local indications show the input state and associated channel condition.
- DIAG indication: Module diagnostics summarize parameter, communication or hardware conditions.
- Field diagnostics: Wire-break, discrepancy and short-circuit monitoring depend on the selected channel parameters.
- Recovery: The F-controller acknowledges reintegration only after the fault and required safety condition are cleared.
Selecting terminal hardware for availability requirements
- H1 terminal block: H1 supports the documented single module arrangement.
- M1 terminal block: M1 provides the connection basis for redundant module operation.
- Configuration match: The station hardware and engineering redundancy setting must agree.
- Replacement check: Terminal type, module article number and PROFIsafe parameters are verified before reintegration.