Features:
- Displays 1280 x 800 graphics in 16.7 million colors on a 15.4-inch touchscreen.
- Connects through PROFINET, PROFIBUS, MPI and EtherNet/IP communication paths.
- Stores HMI projects in 24 MB of configuration memory with SD expansion.
The TP1500 Comfort format combines visualization and resistive touch entry in an Alfa Laval panel design.
Network, USB and SD interfaces separate controller communication from peripheral and removable-storage tasks.
Alarm, recipe and scheduled-task objects are built in TIA Portal and executed by the panel runtime.
The Siemens 6AV2144-6QC10-0AL1 TP1500 Comfort OEM Touch Panel may still be available for purchase and support from Apter Power beyond End-Of-Life (EOL) by the manufacturer (OEM).
Siemens 6AV2144-6QC10-0AL1 TP1500 Comfort OEM Touch Panel Manuals,Datasheets,Link
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
Operator input and visual output
- Widescreen: The 15.4-inch TFT presents 1280 x 800 process graphics.
- Color depth: The display renders 16,777,216 colors.
- Touch layer: Analog-resistive sensing supports gloved or direct finger input.
- Direct keys: Forty touch areas can be configured as S7 input signals.
How controller and Ethernet traffic are separated
- PROFINET: Industrial Ethernet ports carry PROFINET IO and standard TCP/IP services.
- MPI/PROFIBUS: The combined RS 422/485 interface supports legacy controller communication.
- Switch path: Two Ethernet ports form an integrated switch while a separate path remains independent.
- Media redundancy: MRP is available for an Ethernet ring configuration.
Projects, alarms and recipes
- Project storage: Twenty-four megabytes are available for user configuration data.
- Alarm buffer: The panel retains a circulating buffer of 1,024 message entries.
- Recipe records: Five hundred recipes can each contain up to 1,000 data records.
- Scheduled jobs: Configured runtime tasks can be triggered by the panel scheduler.
Panel orientation and enclosure boundary
- Orientation: Vertical landscape and portrait mounting are supported.
- Inclination: The permitted angle without external ventilation is 35 degrees.
- Front seal: The installed front is rated IP65 and NEMA Type 4/4x.
- Rear area: The IP20 rear section remains inside the control enclosure.