Features:
- 6GK1411-5AB10 maps PROFIBUS devices into a PROFINET IO system as proxies.
- S7 and data-record routing carry engineering traffic across the network boundary.
- Two switched Ethernet ports support MRP ring participation.
The gateway links two protocol domains without hiding the engineering routes needed for downstream commissioning and parameter access.
Time synchronization can pass through SIMATIC time services or NTP, allowing the connected installation to use a coordinated time reference.
A removable C-PLUG holds configuration information independently of the base unit, and firmware loading supports controlled device updates.
The Siemens 6GK1411-5AB10 IE/PB LINK PN IO may be available for purchase and support from Apter Power.
Siemens 6GK1411-5AB10 IE/PB LINK PN IO Manuals,Datasheets,Link
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
PROFINET-to-PROFIBUS representation
- Device Mapping: PROFIBUS devices are represented to the PROFINET IO controller.
- Slave Scale: The proxy path covers as many as 64 DPV0 or DPV1 slaves.
- Fieldbus Links: DP/PA Link and DP/FF Link arrangements are supported.
- Real-Time Path: PROFINET IO real-time communication reaches the downstream PROFIBUS system.
Engineering traffic across both networks
- S7 Routing: Engineering access can be routed to S7 stations on PROFIBUS.
- Record Routing: Parameter data records pass to intelligent field devices.
- Clock Distribution: SIMATIC time and NTP provide time synchronization options.
- Management: SNMP v1 exposes network-management information.
Ethernet and supply resilience
- MRP: The integrated switch can participate in a Media Redundancy Protocol ring.
- Dual Ports: Two RJ45 ports form the switched Industrial Ethernet connection.
- Power Inputs: Two 24 V DC feeds can provide redundant supply.
- Independent Layers: Ethernet ring recovery and redundant power use separate mechanisms.
Stored configuration and software control
- C-PLUG: A removable C-PLUG can retain device configuration.
- Firmware Load: The operating firmware can be loaded into the link.
- Neighbor Data: LLDP reports adjacent Ethernet devices.
- Version Scope: The hardware configuration is associated with firmware version 4.0.