Technical specifications for 6GK1411-5AB10

  • Manufacturer:
    Siemens
  • Part Number:
    6GK1411-5AB10
  • Product Family:
    Siemens Simatic Net
  • Product Type:
    SIMATIC NET IE/PB LINK PN IO Gateway
  • Stock:
    1
  • Ethernet Ports:
    Two RJ45 interfaces with integrated switch
  • Ethernet Rate:
    10/100 Mbit/s
  • PROFIBUS Rate:
    9.6 kbit/s to 12 Mbit/s
  • Proxy Capacity:
    Up to 64 PROFIBUS DPV0/DPV1 slaves
  • Network Redundancy:
    Media Redundancy Protocol (MRP)
  • Time Services:
    SIMATIC time and NTP
  • Management Protocols:
    SNMP v1 and LLDP
  • Configuration Memory:
    C-PLUG support
  • Supply Arrangement:
    Redundant 24 V DC inputs
  • Firmware:
    Version 4.0
  • Weight:
    1.063 lbs (0.482 kg)
  • Estimated shipping dimensions:
    10×7.4×11.7 cm
  • Tariff Code:
    85176200
  • Country of origin:
    Germany
  • Place of shipment:
    Xiamen,Fujian,China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals Proxy Operation Routing Services Ring Recovery Firmware Handling

Features:

  • 6GK1411-5AB10 maps PROFIBUS devices into a PROFINET IO system as proxies.
  • S7 and data-record routing carry engineering traffic across the network boundary.
  • Two switched Ethernet ports support MRP ring participation.
The gateway links two protocol domains without hiding the engineering routes needed for downstream commissioning and parameter access.

Time synchronization can pass through SIMATIC time services or NTP, allowing the connected installation to use a coordinated time reference.

A removable C-PLUG holds configuration information independently of the base unit, and firmware loading supports controlled device updates.

The Siemens 6GK1411-5AB10 IE/PB LINK PN IO may be available for purchase and support from Apter Power.
Siemens 6GK1411-5AB10 IE/PB LINK PN IO Manuals,Datasheets,Link Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.

PROFINET-to-PROFIBUS representation

  • Device Mapping: PROFIBUS devices are represented to the PROFINET IO controller.
  • Slave Scale: The proxy path covers as many as 64 DPV0 or DPV1 slaves.
  • Fieldbus Links: DP/PA Link and DP/FF Link arrangements are supported.
  • Real-Time Path: PROFINET IO real-time communication reaches the downstream PROFIBUS system.

Engineering traffic across both networks

  • S7 Routing: Engineering access can be routed to S7 stations on PROFIBUS.
  • Record Routing: Parameter data records pass to intelligent field devices.
  • Clock Distribution: SIMATIC time and NTP provide time synchronization options.
  • Management: SNMP v1 exposes network-management information.

Ethernet and supply resilience

  • MRP: The integrated switch can participate in a Media Redundancy Protocol ring.
  • Dual Ports: Two RJ45 ports form the switched Industrial Ethernet connection.
  • Power Inputs: Two 24 V DC feeds can provide redundant supply.
  • Independent Layers: Ethernet ring recovery and redundant power use separate mechanisms.

Stored configuration and software control

  • C-PLUG: A removable C-PLUG can retain device configuration.
  • Firmware Load: The operating firmware can be loaded into the link.
  • Neighbor Data: LLDP reports adjacent Ethernet devices.
  • Version Scope: The hardware configuration is associated with firmware version 4.0.
Description
As an IE/PB LINK PN IO gateway, Siemens 6GK1411-5AB10 connects an Industrial Ethernet network with PROFIBUS. Its PROFINET IO proxy function represents downstream PROFIBUS devices on the Ethernet-side control system.

Routing services extend beyond the proxy path on Siemens 6GK1411-5AB10. S7 routing reaches PROFIBUS stations, data-record routing carries parameter data to field devices, and SIMATIC time or NTP can distribute clock information across the linked networks.

Network continuity on Siemens 6GK1411-5AB10 is supported by a two-port Industrial Ethernet interface with Media Redundancy Protocol. The unit also accepts redundant 24 V DC feeds, separating supply continuity from the Ethernet ring function.

Configuration and maintenance data for Siemens 6GK1411-5AB10 can be retained on the removable C-PLUG. Firmware can be loaded into the link, while SNMP v1 and LLDP expose management and neighbor information for the Ethernet segment.
Alternative Names
6GK14115AB10 6GK 1411-5AB10 6GK1411 5AB10 6GK1411-5ABI0 6GK141I-5AB10 6GK14I1-5AB10 6GK1411-SAB10 6GK 1411 5ABI0
Technical notes
Siemens 6GK1411-5AB10 bridges Industrial Ethernet and PROFIBUS while presenting connected field devices through a PROFINET IO proxy.
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
When is the proxy function of Siemens 6GK1411-5AB10 required?
Use the proxy function when PROFIBUS devices behind Siemens 6GK1411-5AB10 must appear as PROFINET IO devices to the Ethernet-side controller.
How can configuration data be retained when exchanging Siemens 6GK1411-5AB10?
Store the configuration on the removable C-PLUG so the replacement Siemens 6GK1411-5AB10 can use the retained device data.
Which routing path reaches PROFIBUS field-device parameters through Siemens 6GK1411-5AB10?
Data-record routing on Siemens 6GK1411-5AB10 carries parameter records from the Ethernet side to PROFIBUS field devices.
Does Siemens 6GK1411-5AB10 support an Ethernet ring?
Yes. The two switched Ethernet ports of Siemens 6GK1411-5AB10 support Media Redundancy Protocol for ring integration.
How are network neighbors identified around Siemens 6GK1411-5AB10?
LLDP provides neighbor information for Siemens 6GK1411-5AB10, while SNMP v1 supplies management access to the link.
What prevents a single power feed from stopping Siemens 6GK1411-5AB10?
Two 24 V DC supply inputs allow Siemens 6GK1411-5AB10 to be powered redundantly when both feeds are wired.