Features:
- Receives 24V DC signals with 4.1 mA/channel and 2 kV AC isolation
- Counts edges with 20 ms minimum detection and 25 Hz max cycle
- Supports ATD5A-00 KS adapter, pressure clamp, and MIL connectors
The ADV151-P00 S2 ATD5A-00 provides 32 isolated digital input channels for receiving 24 V DC ON/OFF signals from field sensors and switches. Each channel draws 4.1 mA ±20% at rated voltage and offers withstanding voltage of 2 kV AC between input signal and system, ensuring excellent noise immunity in industrial environments. The ADV151-P00 S2 ATD5A-00 features common isolation every 16 channels with 500 V AC withstand voltage. Input ON voltage ranges from 18 to 26.4 V DC, while OFF voltage is 5.0 V DC or less.
The ADV151-P00 S2 ATD5A-00 includes pushbutton input functionality, enabling edge detection and counting of field pushbutton operations. This function provides minimum ON detection time of 20 ms and maximum ON/OFF cycle of 25 Hz. The ADV151-P00 S2 ATD5A-00 has status input response time of 8 ms or less, ensuring timely recognition of field events. This makes the ADV151-P00 S2 ATD5A-00 suitable for applications requiring operator interface and event counting, such as machine control panels and sequential operation monitoring .
The ADV151-P00 S2 ATD5A-00 includes the ATD5A-00 KS Cable Interface Adapter for simplified 32-channel digital connections. It supports multiple connection methods including pressure clamp terminal blocks (ATB5S-00/ATB5S-10) and MIL connector cables. The module weighs just 0.30 kg and consumes 500 mA at 5 V DC. The ADV151-P00 S2 ATD5A-00 supports dual redundant configurations, allowing installation in ESB Bus Node Units, Optical ESB Bus Node Units, and Field Control Units for increased system availability .
The ADV151-P00 S2 ATD5A-00 YOKOGAWA Digital Input Module may still be available for purchase and support from Apter Power beyond
End-Of-Life (EOL) by the manufacturer (OEM).
YOKOGAWA ADV151-P00 S2 ATD5A-00 Digital Input Module Manuals,
Datasheets, Drivers, Link
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not
included with this equipment unless listed in the above stock item description. All prices are
shown in USD.
YOKOGAWA ADV151-P00 S2 ATD5A-00 Digital Input Module Specs
General
- Manufacturer YOKOGAWA
- Model ADV151-P00 S2 ATD5A-00
- Condition New Original ready stock
- Product Family
ADV151-E63 S2,ADV151-E60 S2,ADV151-E50 S2
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not
included with this equipment unless listed in the above stock item description. All prices are
shown in USD.
- Petrochemical and Oil Refineries: Monitors field instrumentation states, including valve limit switches (Open/Closed confirmations) and level switches.
- Power Generation Facilities: Interfaces with pump status contacts, trip relays, and boiler sub-system alarm circuits.
- Sequence of Events (SOE) Recording: The -P00 variant acts as an explicit SOE input module. It records time-stamped voltage edge transitions down to millisecond accuracy, which is vital for post-incident root-cause analysis during a plant trip.
- Subordinate Microcode Execution: The ADV151 card does not maintain standalone network-facing firmware. Its internal operations are governed entirely by the Field Control Station (FCS) processor module (e.g., AAF11D, AFV30D) to which its I/O node nest connects.
- Online I/O Sub-module Upgrades: While certain specialized standalone Stardom/Fieldmate units permit browser-based I/O patching, updating the hardware drivers or logic processing definitions for an ADV151 in CENTUM VP requires an FCS software revision or software revision update via the Engineering Station (ENG).
- Hardware Style Consistency: The S2 designation stands for Style 2. When replacing modules, the physical style code must match or be explicitly supported by the existing FCS system software release version to guarantee backward driver compatibility.
- Configure the input parameters: Define the 32 channels as either standard Status Inputs or Pushbutton/SOE Inputs depending on the process requirements.
- The system will automatically bind two adjacent ADV151 modules together. If the primary card experiences an internal electronic failure, control switches instantly to the secondary module without dropping the field input state.
- Incorporate these tags directly into Control Drawings using Yokogawa’s native programming languages, such as Function Block Diagrams (FBD) or Sequence Tables.