Features:
- Full Channel-to-Channel Isolation
- Multi-Type Thermocouple & mV Support
- Built-in Burn-out Detection
The YOKOGAWA AAT145-S53 S1 provides 200 V AC isolation between input channels and 500 V AC between input and system. This eliminates cross-talk and ground loop errors, making it ideal for applications where multiple thermocouples share the same cable tray or junction box without signal interference.
With support for 8 thermocouple types (J, K, E, B, R, S, T, N) and two millivolt ranges, the YOKOGAWA AAT145-S53 S1 adapts to virtually any temperature sensor. Each channel can be individually configured via software, reducing spare part inventory and simplifying field upgrades.
The YOKOGAWA AAT145-S53 S1 includes programmable burn-out detection that forces the input either UP-scale or DOWN-scale when a sensor break is detected. With a fixed 60-second detection time, this feature provides fail-safe behavior for critical control loops, alerting operators immediately to wiring or sensor failures.
The AAT145-S53 S1 YOKOGAWA TC/mV Input Module may still be available for purchase and support from Apter Power beyond End-Of-Life (EOL) by the manufacturer (OEM).
YOKOGAWA AAT145-S53 S1 TC/mV Input Module Manuals,Datasheets,Link
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
YOKOGAWA AAT145-S53 S1 TC/mV Input Module
General
- Manufacturer YOKOGAWA
- Model AAT145-S53 S1
- Condition New Original ready stock
- Product Family AAR145-S50 S1,AAR145-S03 S1,AAT141-S03 S2
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
- Software Channel Configuration: Each channel of the YOKOGAWA AAT145-S53 S1 can be individually assigned as TC or mV input using the FCS engineering software (LHS5100). No hardware jumpers or DIP switches are required.
- Global Burn-out Setting: Burn-out detection direction (UP or DOWN) is configured globally for all 16 channels simultaneously on the YOKOGAWA AAT145-S53 S1 – per-channel settings are not available. Detection time is fixed at 60 seconds.
- Compatible FCS Models: The YOKOGAWA AAT145-S53 S1 runs on AFV30, AFV40, AFV10, AFS30, AFS40, AFG30, AFG40, AFG8, and AFF50 series Field Control Stations. Confirm your FCS model before ordering.
- Dual-Redundant Setup: To configure redundancy for the YOKOGAWA AAT145-S53 S1, install two identical modules in adjacent odd-numbered and even-numbered slots on the same node unit. The system automatically handles switchover without user programming.
- Channel-to-Channel Isolation: The YOKOGAWA AAT145-S53 S1 is tested at 200 V AC for 1 minute between input channels, preventing fault propagation from one sensor to another in high-voltage environments.
- System Isolation: With 500 V AC (1500 V AC for single-card use) isolation between field inputs and the system backplane, the YOKOGAWA AAT145-S53 S1 protects the controller from field wiring faults and surges.
- Corrosion Protection (ISA G3): The "3" suffix code qualifies the YOKOGAWA AAT145-S53 S1 for installation in environments with moderate levels of airborne contaminants (e.g., chemical plants), as defined by ISA Standard G3.
- No Explosion Protection: The "5" suffix indicates that the YOKOGAWA AAT145-S53 S1 does not include intrinsic safety barriers. For Zone 1/2 hazardous locations, an external isolation barrier must be installed between the field device and the module.
- Oil & Gas Refineries: Monitor reactor and distillation column temperatures using direct thermocouple inputs. The YOKOGAWA AAT145-S53 S1 provides isolated channels to prevent ground loops in large plants with long wiring runs.
- Chemical & Petrochemical Plants: Measure exothermic reaction temperatures with Type K or J thermocouples. The built-in burn-out detection of the YOKOGAWA AAT145-S53 S1 ensures fail-safe operation when sensors fail.
- Power Generation: Track boiler flue gas temperatures and turbine inlet conditions. With ISA G3 corrosion protection, the YOKOGAWA AAT145-S53 S1 withstands harsh environments containing sulfur and moisture.
- Steel & Metal Processing: Monitor furnace zones and heat treatment processes using Type B, R, or S thermocouples at high temperatures. The 16-channel density of the YOKOGAWA AAT145-S53 S1 reduces cabinet space requirements.