Ask our team:
  • Phone: +86 181 0690 9650
  • E-Mail sales1@apterpower.com
  • Lifecycle status

    Active / Available from OEM
    Apter Power assists with high-density output loading, surge-terminal matching, documentation, and quotes.

SDV541-S5C/B4S10

/ 4.9
1001 reviews | Need a Specific Revision?
Yokogawa SDV541-S5C/B4S10 Digital Output Module for ProSafe-RS FIO Modules.
In Stock
Ships by Saturday, October 31
Fast Shipping Available
Get a quick price for SDV541-S5C/B4S10
Quantity
*E-mail
Company
*Mobile
*Content
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)

Technical specifications for SDV541-S5C/B4S10

  • Manufacturer:
    Yokogawa
  • Part Number:
    SDV541-S5C/B4S10
  • Product Family:
    Centum CS-Centum VP
  • Product Type:
    Digital Output Module
  • Stock:
    1
  • Channels:
    16 module-isolated digital outputs
  • Output Signal:
    24 V DC current-source
  • Load Current:
    0.2 A per output, 3.2 A total
  • Terminal Block:
    STB4S-10 pressure-clamp type
  • Surge Protection:
    included
  • Environmental Option:
    ISA G3 high-density installation, -20 to 70 deg C
  • Weight:
    0.64 lbs (0.29 kg)
  • Estimated shipping dimensions:
    32.8 x 130 x 107.5 mm
  • Tariff Code:
    Please confirm the destination before shipping.
  • Country of origin:
    Japan
  • Place of shipment:
    Xiamen,Fujian,China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals Specifications Sixteen Outputs Protected Block Output Diagnostics

Features:

  • Channels: 16 module-isolated digital outputs
  • Output Signal: 24 V DC current-source
  • Load Current: 0.2 A per output, 3.2 A total
The SDV541-S5C/B4S10 ordering code selects sixteen-channel isolated 24 V DC output module with G3 high-density option and STB4S-10 surge-absorber terminal block.

Sixteen isolated current-source outputs use the specified surge-absorber terminal block in a high-density G3 arrangement.

Observe high-density load restrictions, total output current, surge-terminal wiring, and the documented G3 derating.

Availability is subject to Apter Power inventory and sourcing confirmation.
Yokogawa SDV541-S5C/B4S10 Specifications

General

  • ManufacturerYokogawa
  • ModelSDV541-S5C/B4S10
  • ConditionNew and factory sealed
  • Product FamilyProSafe-RS FIO Modules
  • Minimum Load: 35 mA
  • Channel Limit: 0.2 A maximum per line
  • Total: 3.2 A maximum across all outputs
  • Terminal: STB4S-10 pressure-clamp block
  • Surge: surge absorber included
  • Supply: use a 24 V DC source with at least 3.4 A capacity
  • Response: 30 ms maximum
  • Isolation: 2 kV AC field-to-system for one minute
  • Redundancy: pair only matching output-module specifications
Description
Yokogawa SDV541-S5C/B4S10 is a digital output module. Sixteen-channel isolated 24 V DC output module with G3 high-density option and STB4S-10 surge-absorber terminal block.

Sixteen isolated current-source outputs use the specified surge-absorber terminal block in a high-density G3 arrangement.

Observe high-density load restrictions, total output current, surge-terminal wiring, and the documented G3 derating.
Alternative Names
SDV541S5CB4S10 SDV541 S5C B4S10 Yokogawa SDV541-S5C/B4S10 SDV541-S5C Digital Output Module SDV541-S5C/B4S10 module
Technical notes
SDV541-S5C/B4S10 uses the STB4S-10 surge terminal; apply the documented high-density output-load limits.
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
How many source outputs are available on SDV541-S5C/B4S10?
SDV541-S5C/B4S10 uses 16 module-isolated digital outputs for this configuration.
What nominal output voltage is provided?
Yokogawa documents 24 V DC current-source as the output signal.
What per-channel and total current limits apply?
This order code is specified with 0.2 A per output, 3.2 A total.
Which pressure-clamp terminal block is supplied?
Yokogawa specifies STB4S-10 pressure-clamp type for SDV541-S5C/B4S10.
Is surge absorption included in B4S10?
For SDV541-S5C/B4S10, the official surge protection is included.
What installation limits apply to the high-density G3 version?
The official specification lists ISA G3 high-density installation, -20 to 70 deg C under environmental option.