Technical specifications for AF260-30-11 1SFL537001R7011

  • Manufacturer:
    ABB
  • Part Number:
    AF260-30-11 1SFL537001R7011
  • Product Family:
    ABB Electrical
  • Product Type:
    Block Contactor
  • Stock:
    1
  • Main Contacts:
    3 NO
  • Auxiliary Contacts:
    1 NO + 1 NC
  • Number of Poles:
    3
  • Main Circuit Voltage:
    Up to 690 V
  • Control Voltage:
    100 to 250 V AC/DC
  • AC-3 Current:
    260 A at 380/400/415 V
  • Main Terminal:
    Bars
  • Net Weight:
    5.1 kg
  • Weight:
    12.79 lbs (5.8 kg)
  • Estimated shipping dimensions:
    20.3 x 24.5 x 18.8 cm
  • Tariff Code:
    8536490090
  • Country of origin:
    Sweden
  • Place of shipment:
    Xiamen,Fujian,China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals Switching Coil Control Installation Applications

Features:

  • Three-pole power switching for motor and distribution circuits.
  • Wide-range electronic coil for AC or DC control supplies.
  • Integrated auxiliary contacts for interlocking and feedback.
AF260-30-11 1SFL537001R7011 combines three normally open main poles with one normally open and one normally closed auxiliary contact in a block-contactor format.

Its electronic coil permits the same control device to operate across the supported 100 to 250 V AC/DC range.

The contactor serves motor-starting, isolation, bypass, and distribution arrangements when its utilization ratings match the connected load.

Beyond OEM end-of-life, ABB AF260-30-11 1SFL537001R7011 Block Contactor may still be available for purchase and support from Apter Power.
ABB AF260-30-11 1SFL537001R7011 Block Contactor Manuals, Datasheets, Links

Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.

AF260-30-11 1SFL537001R7011 switching duties

  • Motor duty: ABB rates the contactor for AC-3 motor service, including 260 A at 380/400/415 V.
  • General load: AC-1 thermal-current data supports distribution and non-motor switching assessment.
  • Contact layout: Three normally open main poles switch the power circuit without a main normally closed pole.
  • Motor power: At 400 V AC-3 service, the AF260 size is assigned a 140 kW operational motor-power rating.

AF260-30-11 1SFL537001R7011 control-circuit behavior

  • Supply range: The coil accepts 100 to 250 V at 50/60 Hz and the same 100 to 250 V range on DC.
  • Operating limits: Coil performance is specified from 0.85 times minimum to 1.1 times maximum control voltage at the stated temperature.
  • Feedback contacts: One NO and one NC auxiliary contact can support electrical interlocking and state indication.
  • Surge control: The electronic coil incorporates surge suppression, reducing the need for a separate external suppression device.

AF260-30-11 1SFL537001R7011 panel installation

  • Main connection: Bar terminals require correctly sized conductors, approved hardware, and the specified 28 N·m torque.
  • Protection: Short-circuit protection and conductor selection must follow the application current and ABB coordination data.
  • Environment: Allow for enclosure temperature, ventilation, altitude, and clearances around the 140 x 180.5 x 227 mm device.
  • Mounting position: The contactor supports the illustrated vertical and limited tilted positions while preserving the stated operating limits.

Supported projects for AF260-30-11 1SFL537001R7011

  • Motor starters: AF260-30-11 1SFL537001R7011 can switch three-phase motors within its published AC-3 current and power ratings.
  • Bypass circuits: AF260-30-11 1SFL537001R7011 can form a power bypass path when the interlocking design prevents conflicting contactor states.
  • Distribution panels: AF260-30-11 1SFL537001R7011 can provide isolation or feeder switching for loads covered by its AC-1 and voltage ratings.
  • Resistive-load control: AF260-30-11 1SFL537001R7011 can switch heating or comparable non-motor loads when the AC-1 duty and enclosure conditions are satisfied.
Description
ABB AF260-30-11 1SFL537001R7011 is a three-pole block contactor for motor starting, isolation, bypass, and distribution duties. Its utilization ratings let one contactor size serve both AC-3 motor loads and AC-1 general-load switching when the connected circuit remains within the assigned limits.

At 380 to 415 V, AF260-30-11 1SFL537001R7011 supports 260 A AC-3 service and a 140 kW motor rating, while the AC-1 thermal-current value reaches 400 A at 40 °C. These ratings distinguish motor duty from the broader thermal assessment used for feeders and non-motor loads.

Power conductors land on bar terminals in AF260-30-11 1SFL537001R7011, while separate auxiliary terminals carry interlocking and indication circuits. The divided terminal arrangement keeps the three main poles electrically and physically distinct from the control feedback path.

Panel selection for AF260-30-11 1SFL537001R7011 must account for conductor capacity, coordinated short-circuit protection, enclosure temperature, permissible mounting position, and the clearance required by the contactor body. These conditions determine whether the published switching performance can be maintained in the assembled starter.
Alternative Names
AF260-30-11-70 1SFL537001R7011 ABB AF260-30-11 1SFL537001R7011 AF260 30 11 1SFL537001R7011 AF260-30-11 1SFL 537 001 R7011 1SFL537001R7011 AF260-30-11 AF26O-30-11 1SFL537001R7011 AF260-3O-11 1SFL537001R7011 ABB AF Contactor 1SFL537001R7011
Technical notes
AF260-30-11 1SFL537001R7011 uses an electronic wide-range coil; replacement planning must match control voltage, terminal arrangement, auxiliary contacts, and panel clearances.
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
Which control supply can energize AF260-30-11 1SFL537001R7011?
AF260-30-11 1SFL537001R7011 accepts 100 to 250 V AC at 50/60 Hz or 100 to 250 V DC, so the connected control voltage must remain inside that range.
How should the main power conductors be landed on AF260-30-11 1SFL537001R7011?
AF260-30-11 1SFL537001R7011 uses bar-type main terminals; select approved conductors and hardware, then tighten the main circuit connections to ABB's specified 28 N·m torque.
Which contacts can be used for status feedback on AF260-30-11 1SFL537001R7011?
AF260-30-11 1SFL537001R7011 provides one normally open and one normally closed auxiliary contact for interlocking, status indication, or control-circuit feedback.
What enclosure temperature should be considered for AF260-30-11 1SFL537001R7011?
AF260-30-11 1SFL537001R7011 is specified from -40 to +70 °C without a thermal overload relay, while installations with a fitted overload relay use the stated -25 to +50 °C range.
How can AF260-30-11 1SFL537001R7011 be applied in a motor circuit?
AF260-30-11 1SFL537001R7011 supports three-phase motor starting and can also serve isolation, bypass, and distribution functions when its current and utilization ratings match the load.
Which replacement does ABB identify for AF260-30-11 1SFL537001R7011?
ABB identifies 1SFL547002R1311 as the replacement for AF260-30-11 1SFL537001R7011; confirm coil voltage, accessories, wiring, and panel clearances before substitution.
What should be checked after installing AF260-30-11 1SFL537001R7011?
After installing AF260-30-11 1SFL537001R7011, verify terminal torque, auxiliary-contact logic, coil supply, phase connections, protective devices, and mechanical clearance before an operational switching test.