Technical specifications for X20BM12

  • Manufacturer:
    B&R
  • Part Number:
    X20BM12
  • Product Family:
    B&R X20 System
  • Product Type:
    240 VAC Bus Module
  • Stock:
    1
  • Bus-module keying:
    240 VAC
  • I/O supply nominal voltage:
    24 VDC
  • Permissible contact load:
    10 A
  • Bus power consumption:
    0.13 W
  • Module function:
    Base for 240 VAC X20 I/O modules
  • Keying coverage:
    Bus module, electronic module, and terminal block use 240 V coding
  • Module pitch:
    12.5 mm +0.2 mm
  • Degree of protection:
    IP20
  • Operating temperature:
    -25 to 60 °C horizontal; -25 to 50 °C vertical
  • Operating humidity:
    5 to 95%, non-condensing
  • Dimensions:
    1.42 × 5.2 × 10.96 cm
  • Tariff Code:
    8538900000
  • Country of origin:
    Germany
  • Place of shipment:
    Xiamen, Fujian, China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals Keying Potential Group Safety Application
  • Provides the bus base for standard-width 240 VAC X20 I/O modules
  • Interconnects the internal I/O supply across the potential group
  • Uses coordinated 240 V coding for the bus, electronic, and terminal modules

X20BM12 is a B&R 240 vac bus module designed for the X20 System.

The module supports the electronic module and terminal block, preserves the 240 V coding relationship, and continues the internal I/O supply to adjacent compatible slices.

Before installation or replacement, verify the complete material number, 240 VAC keying, electronic-module and terminal-block compatibility, potential-group boundary, 10 A contact-load limit, isolation and protective devices, neighboring bus modules, and station layout.

Availability, condition, price, and shipping time for X20BM12 are confirmed during quotation.

B&R X20BM12 240 VAC Bus Module Manuals, Datasheets, Links

Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.

  • The bus module is mechanically coded for 240 VAC X20 I/O equipment
  • The electronic module and terminal block must use the matching 240 V coding
  • The keyed arrangement helps prevent mixing with incompatible 24 VDC slices
  • The internal I/O supply is interconnected through the module
  • The module continues an existing compatible supply group rather than creating a new one
  • Potential-group boundaries must follow the documented station power design
  • Power must be removed before changing the bus, electronic, or terminal module
  • The installed protective devices and isolation must suit the connected 240 VAC circuits
  • The permissible contact load and complete station power plan must be verified
  • Building standard 240 VAC X20 I/O slices
  • Continuing the internal I/O supply within a compatible potential group
  • Providing the keyed bus base for 240 VAC electronic and terminal modules
Description
X20BM12 is a B&R 240 vac bus module for the X20 System automation platform.

It forms the mechanical and electrical base for standard-width 240 VAC X20 I/O slices while interconnecting the internal I/O supply across the potential group.

Before installation or replacement, confirm the complete material number, 240 VAC keying, electronic-module and terminal-block compatibility, potential-group boundary, 10 A contact-load limit, isolation and protective devices, neighboring bus modules, and station layout.
Alternative Names
X20BM12 X20 BM 12 X20-BM12 B&R X20BM12 BR X20BM12 B&R X20 BM12
Technical notes
X20BM12 is keyed for 240 VAC X20 I/O modules and passes the internal I/O supply through; verify matching electronic and terminal modules, 10 A contact load, potential-group boundaries, protection, and station layout before replacement.
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
Can B&R X20BM12 be substituted for a 24 VDC bus module?
No. X20BM12 is 240 VAC keyed and must be used only with the officially compatible electronic module and terminal block.
Does B&R X20BM12 create a new potential group?
No. Its internal I/O supply is connected through. Use the documented supply-bus arrangement when an electrical group must be interrupted or newly fed.
Why is keying important when ordering B&R X20BM12?
The bus module, electronic module, and terminal block use coordinated 240 V coding, so a visually similar 24 VDC component is not an acceptable replacement.
What should be checked if a 240 VAC slice on B&R X20BM12 does not operate?
Remove power and verify the upstream supply, protective device, terminal block, electronic module, keying, bus contacts, potential-group continuity, and controller diagnostics.
Is the 24 VDC value in B&R X20BM12 data the external 240 VAC field circuit rating?
No. The official I/O-supply table lists a 24 VDC nominal internal supply, while the module keying and compatible slice type are for 240 VAC equipment; keep these functions distinct.
How should the contact-load limit of B&R X20BM12 be checked?
Calculate the current carried through the relevant bus contacts for the complete compatible group and keep it within the documented 10 A limit.
What should be documented before replacing B&R X20BM12?
Record the exact slice position, compatible electronic and terminal modules, 240 V keying, potential-group boundaries, upstream protection, wiring, and station power calculation.