Ask our team:
  • Phone: +86 181 0690 9650
  • E-Mail sales1@apterpower.com

CM202

/ 4.9
1001 reviews | Need a Specific Revision?
The Bachmann CM202 is a high-performance CANopen master module that supports independent configuration of multiple networks, providing a reliable and flexible fieldbus solution for industrial automation.
Get a quick price for CM202
Quantity
*E-mail
Company
*Mobile
*Content
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)

Technical specifications for CM202

  • Manufacturer:
    Bachmann
  • Part Number:
    CM202
  • Product Family:
    Bachmann
  • Max. number of masters:
    4 per M1 controller
  • Number of CAN buses:
    2 per module
  • Max. number of nodes:
    64 per CAN bus
  • Protocol:
    CANopen to CiA DS 301
  • Device profile:
    In accordance with CiA DS 405
  • Firmware:
    Reloadable (FLASH technology)
  • Current consumption:
    320 mA / 5 VDC
  • Transfer rate:
    10 k to 1 Mbau
  • Bus length:
    Max. 5000 m
  • Connection:
    2x 9-pin D-Sub female connectors
  • Galvanic isolation:
    500 V
  • Operating temperature:
    -30 to +60 °C
  • Rel. humidity operation:
    5 to 95 % without condensation
  • Storage temperature:
    5 to 95 % with condensation
  • Weight:
    0.22 kg
  • Estimated shipping dimensions:
    5.4x5.5x11.8cm
  • Tariff Code:
    8537101190
  • Country of origin:
    Austria
  • Place of shipment:
    Xiamen, Fujian, China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.
Description
The Bachmann CM202 CANopen Master Module is designed for high-speed, reliable network communication in industrial automation. Each module is equipped with two independent CAN bus interfaces, which can be independently configured as an NMT master or slave according to application requirements, enabling flexible network topologies. The module provides reloadable firmware via FLASH technology for easy upgrades and maintenance, supports protocols compliant with the CiA DS 301 standard, and follows the CiA DS 405 device configuration file, ensuring compatibility with various CANopen devices.

In the M1 controller system, up to four CM202 modules can operate in parallel, enabling the system to manage up to four independent CANopen networks. Each CAN bus can connect up to 64 nodes, with transmission rates ranging from 10 kbaud to 1 Mbaud. The maximum bus length is 5000 meters (requires a signal repeater), and the module provides 500 V isolation protection to ensure network and device safety.

The CM202 features short-circuit protection, operates at only 320 mA @ 5 VDC, has an operating temperature range of -30°C to +60°C, a storage temperature range of 5°C to 95°C, and operates at up to 95% humidity without condensation, making it suitable for complex industrial environments. The module connects via two 9-pin D-Sub female interfaces, ensuring simple and reliable wiring and rapid integration into existing automation systems.

The CM202 CANopen Master Module excels in applications such as machine control, distributed I/O, energy management, and production line automation, providing secure, stable, and flexible communication solutions for industrial networks, making complex control tasks more efficient and reliable.

Alternative Names
CM2O2 CMZ0Z cm202
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
How many CAN buses does each CM202 module support?
Each CM202 module provides two independent CAN bus interfaces, which can be independently configured as an NMT master or slave.
Is the CM202 brand new?
Yes, the CM202 we supply is 100% brand new and comes in original packaging.
How many nodes does the CM202 support?
Each CAN bus supports up to 64 nodes, which can connect various sensors, actuators, and I/O devices.
What are the communication rate and bus length of the CM202?
The transmission rate ranges from 10 kbaud to 1 Mbaud, and the maximum bus length is up to 5000 meters (a signal repeater is required to ensure signal integrity).
Does the CM202 have isolation and protection functions?
The module provides 500V electrical isolation and short-circuit protection, ensuring the safe operation of the network and connected devices.