Features:
- llows installation in tight spaces where standard probes cannot fit
- Agency approval option 05 includes CSA, ATEX, and IECEx certifications for safe operation in explosive environments.
- Patented TipLoc and CableLoc molding with 330 N pull strength; gold-plated ClickLoc connectors with finger-tight installation
The 330105-XX-XX-10-02-05 MOD: 157310-07 is specifically designed for reverse mount installations where the probe must be inserted from the opposite side of the target surface. This configuration is ideal for turbomachinery with limited access or where standard probe mounting is physically impossible. The integrated probe sleeve provides additional mechanical protection and serves a critical function: it prevents oil and other liquids from leaking through the cable interior.
Equipped with agency approval option 05, the 330105-XX-XX-10-02-05 MOD: 157310-07 carries CSA, ATEX, and IECEx certifications for use in potentially explosive atmospheres. This makes it suitable for refineries, chemical plants, and power generation facilities where flammable gases or dust may be present. The 3300 XL Proximitor Sensor's enhanced RFI/EMI immunity satisfies European CE mark requirements without special shielded metallic conduits, allowing installation directly in fiberglass housings.
The 330105-XX-XX-10-02-05 MOD: 157310-07 incorporates the same patented durability features as the standard 3300 XL series. TipLoc molding creates a permanent bond between the probe tip and body, eliminating a common failure point. CableLoc technology secures the cable with 330 N (75 lbf) pull strength, preventing accidental disconnection during installation or operation. The gold-plated ClickLoc connectors are corrosion-resistant and require only finger-tight torque—audible clicks confirm proper engagement, and the locking mechanism prevents loosening from vibration.
The 330105-XX-XX-10-02-05 MOD: 157310-07 Bently Nevada Reverse Mount Probe may still be available for purchase and support from Apter Power beyond
End-Of-Life (EOL)by the manufacturer (OEM).
Bently Nevada 330105-XX-XX-10-02-05 MOD: 157310-07 Reverse Mount Probe Manuals,
Datasheets,Drivers,Link
Important Notice:Other accessories,manuals,cables,calibration data,software,etc.are not
included with this equipment unless listed in the above stock item description.All prices are
shown in USD.
Bently Nevada 330105-XX-XX-10-02-05 MOD: 157310-07 Reverse Mount Probe Specs
General
- Manufacturer Bently Nevada
- Model 330105-XX-XX-10-02-05 MOD: 157310-07
- Condition New Original ready stock
- Product Family 330105-02-12-15-02-CN,330105-02-12-05-02-00
Important Notice:Other accessories,manuals,cables,calibration data,software,etc.are not included with this equipment unless listed in the above stock item description.All prices are shown in USD.
- Industrial Gas & Steam Turbines: Positioned deep within localized blind-hole bearing housings to capture micrometric shaft dynamics.
- High-Pressure Centrifugal Compressors: Reverse-locked into thrust bearing blocks in petrochemical processing plants and natural gas transmission stations.
- Heavy Duty Expanders & Gearboxes: Embedded internally to monitor rotating components operating under intense aerodynamic loads.
- Golden ClickLoc™ Interface (-02 Suffix): Terminated with a miniature gold-plated ClickLoc™ coaxial connector. It provides a pull-and-snap mechanical self-locking interface that actively resists high-frequency mechanical vibration.
- The 5m/9m Loop Calibration Constraint: To balance the Proximitor’s high-frequency RF bridge, this 1.0-meter internal cable must be combined with a 4.0-meter extension cable (yielding a 5-meter system) or an 8.0-meter extension cable (yielding a 9-meter system). Mismatching cable lengths alters loop impedance, introducing severe signal non-linearity.
- Loop "NOT OK" Diagnostics: The host monitoring rack continuously monitors the DC bias window of the probe loop. If a field cable is accidentally severed, or the ClickLoc™ junction breaks open, the voltage instantly drifts outside the operational -2V to -18V DC boundary.
- Automated Machinery Interlock Control: Upon identifying a signal fault, the 3500 rack activates a channel fault condition within 100 milliseconds, illuminating the red "NOT OK" LED. Crucially, the rack automatically bypasses (blocks) that channel's machine-trip relays. This prevents simple physical wiring failures from inducing accidental, multi-million-dollar emergency plant shutdowns.