    Apter Power supplies verified Bently Nevada 3500 Series hardware to ensure reliable thermal monitoring, protect critical rotating equipment, and prevent unexpected plant downtime.

3500/61 133811-02

/ 4.9
1001 reviews | Need a Specific Revision?
The 3500/61 133811-02 is a Bently Nevada 3500/61 temperature monitor with six channels, recorder outputs, accepting RTD or TC inputs, and programmable alarm setpoints for machinery protection.
In Stock
Ships by Thursday, October 29
Fast Shipping Available
Get a quick price for 3500/61 133811-02
Quantity
*E-mail
Company
*Mobile
*Content
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)

Technical specifications for 3500/61 133811-02

  • Manufacturer:
    Bently Nevada
  • Part Number:
    3500/61 133811-02
  • Product Family:
    3500 System
  • Product Type:
    Temperature Monitor
  • Stock:
    1
  • Input Impedance:
    10 MΩ per lead
  • Power Consumption:
    9 W nominal
  • RTD Excitation Current:
    925 ±15 μA @ 25°C
  • Recorder Outputs:
    4-20 mA per channel (0-600 Ω load, 0-12V compliance)
  • Recorder Resolution:
    0.3662 μA/bit ±0.15% error at 25°C
  • Accuracy (RTD/TC, typical):
    ±1°C to ±3°C (depending on I/O type)
  • Operating Temperature:
    -30°C to +65°C (with external termination)
  • Storage Temperature:
    -40°C to +85°C
  • Functional Safety:
    SIL 2
  • Weight:
    0.98 kg
  • Estimated shipping dimensions:
    2.5x18.5x24.2cm
  • Tariff Code:
    8537101190
  • Country of origin:
    USA
  • Place of shipment:
    Xiamen, Fujian, China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals Specifications Application Operating Environment Monitoring & Control

Features:

  • Accepts RTD (Pt100, Ni120, Cu10) and thermocouple (J, K, T, E) inputs; supports 3‑wire or 4‑wire RTDs; each channel individually configurable.
  • Six isolated 4-20 mA outputs proportional to full‑scale temperature; 0.3662 μA/bit resolution; short‑circuit protected; update rate ≤100 ms.
  • Alert and Danger setpoints adjustable 0-100% of full scale; programmable delays (1‑60 seconds); accuracy ±0.13%; functional safety certified (SIL 2).
The 3500/61 133811-02 provides six channels of temperature measurement, each independently configurable for RTD or thermocouple input. This allows a single monitor to handle mixed sensor types – for example, three RTDs for bearing temperatures and three thermocouples for exhaust gas temperatures. Supported RTDs include the industry‑standard 100Ω platinum (alpha = 0.00385 or 0.00392), 120Ω nickel, and 10Ω copper. Supported thermocouples are types J, K, T, and E. For RTDs, both 3‑wire and 4‑wire connections are supported

The 3500/61 133811-02 differs from the 3500/60 by providing dedicated 4-20 mA recorder outputs for each of its six channels. These analog outputs are proportional to the monitor’s full‑scale temperature range and are used to interface with plant DCS, PLC, or SCADA systems for trending, logging, and control. For example, a bearing temperature of 0-150°C might be mapped to 4-20 mA, allowing the DCS to continuously track temperature rise and initiate pre‑alarms before the monitor’s alert setpoint is reached.

The 3500/61 133811-02 is not just a data acquisition device – it is a machinery protection monitor. It continuously compares each channel’s temperature against user‑programmable Alert and Danger setpoints. When a setpoint is exceeded, the monitor activates alarms, which can be used to alert operators, trigger shutdowns, or log events. Alarm setpoints are adjustable from 0 to 100% of the channel’s full‑scale range, with accuracy within 0.13% of the desired value.

The 3500/61 133811-02 Bently Nevada Temperature Monitor may still be available for purchase and support from Apter Power beyond End-Of-Life (EOL)by the manufacturer (OEM).
Bently Nevada 3500/61 133811-02 Temperature Module Manuals,Datasheets,Link Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
Bently Nevada 3500/61 133811-02 Temperature Monitor Specs

General

  • Manufacturer Bently Nevada
  • Model 3500/61 133811-02
  • Condition New Original ready stock
  • Product Family 3500/60 133811-01,3500/61 133811-03,3500/61 133811-04
Important Notice:Other accessories,manuals,cables,calibration data,software,etc.are not included with this equipment unless listed in the above stock item description.All prices are shown in USD.
  • Bearing Temperature Monitoring: Monitors radial and thrust bearings in turbines, pumps, and compressors to detect early signs of mechanical wear or lubrication failure.
  • Stator Winding Protection: Essential for large electric motors and generators to prevent insulation damage caused by electrical overloads or cooling system malfunctions.
  • Exhaust & Fluid Monitoring: Tracks exhaust gas temperatures (EGT) in gas turbines and lube oil/coolant temperatures in auxiliary systems.
  • Industrial Sectors: Widely used in Power Generation, Oil & Gas Refineries, Chemical Processing, and Water Treatment plants.
  • Humidity: Up to 95% non-condensing, providing resilience in humid coastal or tropical plant locations.
  • Electromagnetic Compatibility (EMC): Built to withstand high-interference environments near high-voltage switchgear and large motor drives, adhering to CE and CSA standards.
  • Hazardous Areas: When used with appropriate barriers or in North American/ATEX-certified racks, it is suitable for use in Class 1, Division 2 or Zone 2 environments.
  • High-Resolution Monitoring: Continuously digitizes analog temperature signals, allowing operators to see real-time trends via the System 1 software or local HMI.
  • Setpoint Control (Alert/Danger): Users program specific temperature thresholds. When reached, the module sends signals to the 3500 Relay Modules to initiate alarms or emergency machine shutdowns (trips).
  • Output Connectivity:Digital: Sends data via the 3500/22M TDI module to higher-level DCS or SCADA systems.
  • Condition Monitoring: Beyond simple alarms, it provides "Not OK" status monitoring, identifying if a sensor has failed rather than triggering a false machine trip.
Description
The 3500/61 133811-02 is a six-channel temperature monitor for the Bently Nevada 3500 series machinery protection system. It accepts both RTD (Resistance Temperature Detector) and thermocouple (TC) inputs. The monitor conditions these signals and compares them against user-programmable alarm setpoints. 

When using the 3500/61 133811-02, engineers can configure each channel for either RTD or TC measurement using the 3500 Rack Configuration Software. The module supports various RTD types (100Ω platinum 0.00385 or 0.00392 alpha, 120Ω nickel, 10Ω copper) and TC types (J, K, T, E). 

The 3500/61 133811-02 consumes 9 watts nominal and provides front panel LEDs (OK, TX/RX, Bypass) for status indication. RTD excitation current is 925 ±15 μA at 25°C. The recorder outputs are 4-20 mA (0-600 Ω load, 0-12V compliance) with 0.3662 μA per bit resolution and approximately 100 ms update rate. 
Alternative Names
3500/61 133908-01 3500/61 133916-01 3500/61 133924-01 3500/61 133932-01
Technical notes
The 3500/61 133811-02 requires 3500 Rack Configuration Software to set measurement types (RTD or TC), full‑scale ranges, alarm setpoints, and alarm delays. No field calibration is required; all calibration is done at the factory.
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
Can 3500/61 133811-02 set independent alarms per channel?
Yes. Each of the six channels can have its own Alert and Danger setpoints, adjustable from 0 to 100% of full scale via 3500 Rack Configuration Software. Accuracy is within 0.13% of the desired value. Alert delays: 1-60 seconds; Danger delays: 0.5-60 seconds.
Which RTD types work with 3500/61 133811-02?
The monitor supports 100Ω platinum RTD (alpha=0.00385 or 0.00392), 120Ω nickel RTD, and 10Ω copper RTD, in 3‑wire or 4‑wire configurations. The worldwide industrial standard is 100Ω platinum with 0.00385 alpha. Excitation current is 925 μA per transducer.
Does 3500/61 133811-02 provide analog outputs?
Yes. Each of the six channels has a 4-20 mA recorder output proportional to the monitor’s full‑scale range. Load resistance: 0‑600 Ω; voltage compliance: 0‑12V. Resolution: 0.3662 μA/bit (±0.15% at 25°C). Update rate is approximately 100 ms.
Is 3500/61 133811-02 approved for hazardous areas?
Yes. It is certified for Class I, Division 2 (CSA/NRTL/C) and ATEX/IECEx Zone 2 (Ex nA nC ic IIC T4 Gc) when used with appropriate I/O modules and installed per drawings 149243/149244. Temperature range: -20°C to +65°C for hazardous area installations.