IC693PWR322

/ 4.9
1001 reviews | Need a Specific Revision?
IC693PWR322 is a GE Fanuc Series 90-30 30 W power supply for 24 VDC or 48 VDC input systems.
In Stock
Ships by Thursday, October 29
Fast Shipping Available
Get a quick price for IC693PWR322
Quantity
*E-mail
Company
*Mobile
*Content
Upload (gif, jpg, jpeg, png, bmp, doc, docx, xls, xlsx, ppt, pdf, csv)

Technical specifications for IC693PWR322

  • Manufacturer:
    General Electric
  • Part Number:
    IC693PWR322
  • Product Family:
    GE 90-30 Series PLC
  • Product Type:
    Series 90-30 24/48 VDC power supply
  • Stock:
    1
  • Nominal input:
    24 VDC or 48 VDC
  • Operating input:
    18 to 56 VDC
  • Starting input:
    21 to 56 VDC
  • Maximum input power:
    50 W
  • Total output:
    30 W
  • +5 VDC output capacity:
    15 W
  • +24 VDC relay output capacity:
    15 W
  • Isolated +24 VDC capacity:
    20 W
  • Input inrush:
    4 A peak, 100 ms maximum
  • Overvoltage protection:
    6.4 to 7.0 V on the 5 V output
  • Overcurrent protection:
    4 A maximum
  • Hold-up time:
    14 ms minimum
  • Tariff Code:
    8504401990
  • Country of origin:
    USA
  • Place of shipment:
    Xiamen,Fujian,China
By purchasing this item, you agree to the Terms & Conditions, ApterPower is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with ApterPower's 1-year warranty.

More Information

Overview Manuals Power Output Protection Installation Applications

Features:

  • Accepts nominal 24 VDC or 48 VDC input power
  • Supplies 30 W total across the Series 90-30 output rails
  • Provides logic, relay, and isolated 24 VDC outputs
IC693PWR322 is the low-voltage DC supply option for Series 90-30 baseplates served from a 24 VDC or 48 VDC plant source.

Its three output functions share one defined 30 W budget rather than operating as independent full-capacity supplies.

Input-start and run thresholds make source-voltage drop an important commissioning check.

The General Electric IC693PWR322 Series 90-30 24/48 VDC power supply may remain available for quotation and installed-system support from Apter Power.
General Electric IC693PWR322 Series 90-30 24/48 VDC power supply Manuals, Datasheets, LinksImportant Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.

Backplane supply functions

  • Logic rail: The +5 VDC output powers the CPU and logic circuitry of installed modules.
  • Relay rail: A +24 VDC relay output is available for supported module requirements.
  • Isolated source: The isolated +24 VDC output serves compatible field-side needs.
  • Shared capacity: Combined loading across all outputs is limited to 30 W.

Source and load behavior

  • Input window: The supply operates from 18 to 56 VDC after successful startup.
  • Starting threshold: Applied voltage must reach the applicable 21 to 56 VDC starting range.
  • Input demand: Maximum source power at full load is 50 W.
  • Inrush allowance: The upstream DC source must tolerate the supply's peak startup current.

DC wiring practice

  • Terminal connection: Incoming DC power is landed on the front terminal block with the required polarity.
  • Power budget: Every baseplate module load is totaled against the available rail capacities.
  • Source sizing: Cable drop and protective devices are selected so startup voltage remains above the minimum.
  • Baseplate position: The power supply occupies the dedicated left-hand position of a Series 90-30 baseplate.

Supported power arrangements

  • Battery-backed panels: A 24 VDC battery system can feed the PLC baseplate through IC693PWR322.
  • 48 VDC plants: Telecommunications and industrial panels with 48 VDC distribution can use the same supply model.
  • Mobile equipment: DC-powered machine platforms can operate Series 90-30 control without an AC conversion stage.
  • Remote skids: Field enclosures with a local DC bus can power their controller and I/O from one baseplate supply.
Description
IC693PWR322 is a Series 90-30 power-supply module that converts a nominal 24 VDC or 48 VDC source into the backplane power used by CPUs, I/O modules, and option modules.

When IC693PWR322 is applied, the supply provides a 30 W total output shared by the +5 VDC logic rail, the +24 VDC relay output, and the isolated +24 VDC output. It starts with 21 to 56 VDC applied and continues operating across an 18 to 56 VDC input range.

During operation of IC693PWR322, a front terminal block accepts the DC source, and the internal current limiting and peak inrush behavior must be considered when sizing wiring and upstream protection. The maximum input power is 50 W at full load.
Revisions

Revision Part #

Also known as

IC693PWR322A
IC693PWR322-A, Series A, Rev A
IC693PWR322B
IC693PWR322-B, Series B, Rev B
IC693PWR322C
IC693PWR322-C, Series C, Rev C
IC693PWR322D
IC693PWR322-D, Series D, Rev D
IC693PWR322E
IC693PWR322-E, Series E, Rev E
IC693PWR322F
IC693PWR322-F, Series F, Rev F
Alternative Names
IC 693 PWR322 IC693-PWR322 GE IC693PWR322 GE Fanuc IC693PWR322 Series 90-30 IC693PWR322 PWR322 IC693 PWR322 1C693PWR322
Technical notes
IC693PWR322 output ratings share one 30 W ceiling, so isolated 24 VDC use reduces the capacity remaining for the logic and relay rails.
Exceptional Service

Our Mission

  • 100% Satisfaction

    We believe expertise is priceless. With over 20 years of experience, and top engineers on staff, we can help you solve or avoid problems that threaten your business.
  • Trust Guaranteed

    Not only do we have a vast inventory, our team makes sure every piece of equipment is in working condition. Your purchases are also backed by our Warranty.
  • Expertise

    Time is money, especially when your equipment is down. We work quickly to get your equipment on its way so you can get it back up and running.

FAQS

The following is a list of questions commonly asked by our customers. Please contact us if you have a question about our process that is not answered below.
Why might IC693PWR322 fail to start on an otherwise live DC bus?
The DC-input power supply requires at least 21 VDC at startup; cable drop or a current-limited source can leave the terminal voltage below that threshold.
Can IC693PWR322 run from a 48 VDC system?
This DC-input power supply accepts nominal 48 VDC service and operates across the applicable 18 to 56 VDC range.
How is the 30 W rating of IC693PWR322 applied?
The installed DC-input power supply shares its 30 W capacity among the +5 VDC, +24 VDC relay, and isolated +24 VDC outputs.
Where is incoming power connected on IC693PWR322?
A configured DC-input power supply receives the DC source at its front terminal block, with polarity and protective wiring arranged for the installed panel.
What source capacity is needed for IC693PWR322?
The selected DC-input power supply can draw up to 50 W at full load, and the DC source must also accommodate startup inrush.
Does IC693PWR322 provide an isolated field supply?
The unit includes an isolated +24 VDC output in addition to the logic and relay power rails.
How should an IC693PWR322 replacement be load-checked?
Its replacement work should total every installed module requirement by rail and confirm the combined output remains within 30 W.