Features:
- Provides eight independently isolated 120 VAC input points for separately referenced field signals.
- Maintains 300 VAC continuous isolation from point to point.
- Uses defined 70–120 VAC on and 0–20 VAC off recognition windows.
IC670MDL233 presents eight separately isolated AC input states to a Field Control Bus Interface Unit without sharing field commons between points.
Its 70–120 VAC on window and 0–20 VAC off window provide defined recognition levels for 120 VAC contact and status circuits.
Point-to-point isolation is rated 300 VAC continuously, while the specified input delays establish predictable response for independently referenced signals.
Beyond manufacturer End-of-Life (EOL), Apter Power may continue to supply and support the General Electric IC670MDL233 120 VAC Isolated Discrete Input Module.
General Electric IC670MDL233 120 VAC Isolated Discrete Input Module Manuals,Datasheets,Link
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
General Electric IC670MDL233 120 VAC Isolated Discrete Input Module Specs
General
- ManufacturerGeneral Electric
- ModelIC670MDL233
- ConditionNew Original ready stock
- Product FamilyGE Genius I/O
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
Independent Input Isolation:
- Input arrangement: 8 independently isolated AC input points
- Field range: 0–132 VAC at 47–63 Hz
- Input current: 13 mA typical per point at rated voltage
- Point isolation: 300 VAC continuous between inputs
120 VAC Recognition Levels:
- On-state range: 70–120 VAC
- Off-state range: 0–20 VAC
- Signal frequency: 47–63 Hz AC field circuits
- Field references: Each isolated point can use its own input reference
Input Transfer Performance:
- Turn-on response: 10 ms typical
- Turn-off response: 20 ms typical
- BIU current: 40 mA maximum
- System interface: Field Control Bus Interface Unit