Features:
- Provides two bipolar analog output circuits in one Series Three rack position.
- Covers negative and positive commands across a -10 to +10 VDC span.
- Assigns 33 load units to 5 VDC with no listed 12 VDC load.
General Electric IC630MDL367 is the bipolar-voltage member of the adjacent two-channel Series Three analog output group.
A signal path can cross zero and command either polarity, so the destination input and field wiring must preserve the intended sign.
Its 330 mA demand belongs in the 5 VDC rack budget before the module is added to an existing station.
The General Electric IC630MDL367 Series Three 2-Channel Bipolar Analog Output Module may still be available for purchase and support from Apter Power beyond End-Of-Life (EOL) by the manufacturer (OEM).
General Electric IC630MDL367 Series Three 2-Channel Bipolar Analog Output Module Manuals,Datasheets,Link
Important Notice: Other accessories, manuals, cables, calibration data, software, etc. are not included with this equipment unless listed in the above stock item description. All prices are shown in USD.
Bipolar Signal
- Range: The output span extends from -10 to +10 VDC for signed analog commands.
- Zero Crossing: Command values can move through 0 V between negative and positive setpoints.
- Receiver Match: The connected analog input must accept the same bipolar voltage range.
- Polarity Check: Signal and return conductors must preserve the required command direction.
Two-Circuit Layout
- Circuit Count: Two analog output circuits share one Series Three module position.
- Destination Assignment: Each circuit can be allocated to a separate compatible receiving interface.
- Range Consistency: Both connected destinations must be selected for the published bipolar span.
- Wiring Review: Field conductors should be checked separately for sign, return, and destination.
Rack Supply Planning
- 5 VDC Load: The module is assigned 33 load units on the Series Three 5 VDC supply.
- Current Equivalent: Thirty-three load units correspond to 330 mA under the rack convention.
- 12 VDC Entry: The rack-planning table lists no additional 12 VDC demand for this module.
- Capacity Check: Existing module loads must be added before available rack current is confirmed.
Adjacent Range Selection
- IC630MDL366A: Provides two 1-5 VDC or 4-20 mA analog output circuits.
- IC630MDL367A: Provides two -10 to +10 VDC bipolar analog output circuits.
- IC630MDL368A: Provides two 0-10 VDC or 4-20 mA analog output circuits.
- Selection Basis: Choose the variant whose published signal range matches the receiving interface.